First published: Sat Dec 17 2011(Updated: )
The Schneider Electric Quantum Ethernet Module, as used in the Quantum 140NOE771* and 140CPU65* modules, the Premium TSXETY* and TSXP57* modules, the M340 BMXNOE01* and BMXP3420* modules, and the STB DIO STBNIC2212 and STBNIP2* modules, uses hardcoded passwords for the (1) AUTCSE, (2) AUT_CSE, (3) fdrusers, (4) ftpuser, (5) loader, (6) nic2212, (7) nimrohs2212, (8) nip2212, (9) noe77111_v500, (10) ntpupdate, (11) pcfactory, (12) sysdiag, (13) target, (14) test, (15) USER, and (16) webserver accounts, which makes it easier for remote attackers to obtain access via the (a) TELNET, (b) Windriver Debug, or (c) FTP port.
Credit: cve@mitre.org
Affected Software | Affected Version | How to fix |
---|---|---|
Schneider Electric Quantum Ethernet Module 140NOE77101 | <=4.9 | |
Schneider Electric Quantum Ethernet Module 140CPU65260 | <=3.5 | |
Schneider Electric Quantum Ethernet Module 140CPU65160 | <=3.5 | |
Schneider Electric Quantum Ethernet Module 140NOE77100 | <=3.3 | |
Schneider Electric Quantum Ethernet Module 140CPU65150 | <=3.5 | |
Schneider Electric Quantum Ethernet Module 140NOE77100 | <=3.4 | |
Schneider Electric Quantum Ethernet Module 140NOE77111 | <=5.0 | |
Schneider Electric Premium Ethernet Module TSXP576634M | <=3.5 | |
Schneider Electric Premium Ethernet Module TSXP57163M | <=4.9 | |
Schneider Electric Premium Ethernet Module TSXETY5103 | <=5.0 | |
Schneider Electric Premium Ethernet Module | <=4.9 | |
Schneider Electric Premium Ethernet Module TSXETY4103 | <=5.0 | |
Schneider Electric Premium Ethernet Module TSXP573634M | <=4.9 | |
Schneider Electric Premium Ethernet Module | <=3.5 | |
Schneider Electric Premium Ethernet Module TSXP574634M | <=3.5 | |
Schneider Electric M340 Ethernet Module | <=2.3 | |
schneider-electric M340 Ethernet Module | <=2.2 | |
Schneider Electric M340 Ethernet Module BMXP342030 | <=2.2 | |
Schneider Electric M340 Ethernet Module | <=4.65 | |
Schneider Electric STB DIO Ethernet Module STBNIP2311 | <=3.01 | |
STB DIO Ethernet Module STBNIP2212 | <=2.73 | |
Schneider Electric STBNIC2212 Firmware | <=2.10 |
Sign up to SecAlerts for real-time vulnerability data matched to your software, aggregated from hundreds of sources.
CVE-2011-4859 is categorized as a high-severity vulnerability due to the use of hardcoded passwords.
To fix CVE-2011-4859, update the affected Schneider Electric Quantum Ethernet Module to a version that does not use hardcoded passwords.
CVE-2011-4859 affects multiple Schneider Electric Quantum Ethernet Modules, including versions up to 4.9 for selected models.
CVE-2011-4859 impacts Ethernet modules in the Schneider Electric Quantum, Premium, and M340 series.
Currently, there is no documented workaround for CVE-2011-4859; the recommended solution is to apply the appropriate software updates.