CVE-2020-25184: Rockwell Automation ISaGRAF5 Runtime Unprotected Storage of Credentials

First published: Fri Mar 18 2022(Updated: )

Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x stores the password in plaintext in a file that is in the same directory as the executable file. ISaGRAF Runtime reads the file and saves the data in a variable without any additional modification. A local, unauthenticated attacker could compromise the user passwords, resulting in information disclosure.

Credit: ics-cert@hq.dhs.gov

Affected SoftwareAffected VersionHow to fix
Rockwell Automation AADvance Controller
Rockwell Automation ISaGRAF Free Runtime in ISaGRAF6 Workbench
Rockwell Automation Micro800
Schneider Electric Easergy T300 Firmware<=2.7.1
Schneider Electric Easergy T300 Firmware
Schneider-electric Easergy C5<1.1.0
Schneider-electric Easergy C5
Schneider-electric Micom C264 Firmware<d6.1
Schneider-electric Micom C264 Firmware
Schneider-electric Pacis Gtw Firmware=5.1
Schneider-electric Pacis Gtw Firmware=5.2
Schneider-electric Pacis Gtw Firmware=6.1
Schneider-electric Pacis Gtw Firmware=6.3
Schneider-electric Pacis Gtw Firmware=6.3
Schneider-electric Pacis Gtw Firmware
Schneider-electric Saitel Dp<=11.06.21
Schneider-electric Saitel Dp Firmware
Schneider-electric Epas Gtw Firmware=6.4
Schneider-electric Epas Gtw Firmware=6.4
Schneider-electric Epas Gtw Firmware
Saitel DR<=11.06.12
Schneider-electric Saitel Dr Firmware
Schneider-electric SCD2200 Firmware<=10024
Schneider Electric CP-3
Schneider-electric Mc-31
Rockwell Automation AADvance Controller<=1.40
Isagraf<=6.6.8
Rockwell Automation Isagraf Runtime>=5.0<6.0
Rockwell Automation Micro810 Firmware
Rockwell Automation Micro810
Rockwell Automation Micro820 Firmware
Rockwell Automation Micro820
Rockwell Automation Micro830 Firmware
Rockwell Automation Micro830 Firmware
Rockwell Automation Micro850 Firmware
Rockwell Automation Micro850
Rockwell Automation Micro870 Firmware
Rockwell Automation Micro870
Xylem Multismart Firmware<3.2.0

Remedy

Rockwell Automation recommends users update to ISaGRAF Runtime 5 Version 5.72.00. End users are encouraged to restrict or block access on TCP 1131 and TCP 1132 from outside the industrial control system. Confirm the least-privilege user principle is followed and user/service account access to Runtime's folder location is granted with a minimum amount of rights needed. Rockwell Automation recommends users of affected versions evaluate the mitigations provided and apply the appropriate mitigations to deployed products. Users are encouraged to combine this guidance with the general security guidelines for a comprehensive defense-in-depth strategy. To reduce risk, Rockwell Automation recommends users: Employ proper network segmentation and security controls. Minimize network exposure for all control system devices. Locate control systems behind firewalls. Isolate control systems from other networks when possible. Refer to the Converged Plantwide Ethernet (CPwE) Design and Implementation Guide for best practices deploying network segmentation and broader defense-in-depth strategies. Consider using proper network infrastructure controls, such as firewalls, UTM devices, VPN, or other security appliances. Ensure the least-privilege user principle is followed, and user/service account access to Runtime’s folder location is granted with a minimum amount of rights, as needed. Please see publications from Rockwell Automation and Schneider Electric, Xylem, or contact GE for further information about how to mitigate these vulnerabilities in additional affected products.

Never miss a vulnerability like this again

Sign up to SecAlerts for real-time vulnerability data matched to your software, aggregated from hundreds of sources.

Parent vulnerabilities

(Appears in the following advisories)

Frequently Asked Questions

  • What is CVE-2020-25184?

    CVE-2020-25184 refers to a vulnerability in Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x that stores passwords in plaintext in a file in the same directory as the executable file.

  • How severe is CVE-2020-25184?

    CVE-2020-25184 has a severity level of 5.5, categorized as high.

  • Which software versions are affected by CVE-2020-25184?

    Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x are affected by CVE-2020-25184.

  • Is CVE-2020-25184 vulnerable to local unauthenticated attackers?

    Yes, a local, unauthenticated attacker could exploit CVE-2020-25184.

  • Are there any references related to CVE-2020-25184?

    Yes, references related to CVE-2020-25184 can be found at the provided links.

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.
© 2025 SecAlerts Pty Ltd.
ABN: 70 645 966 203, ACN: 645 966 203