First published: Tue Nov 09 2021(Updated: )
A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions < V3.5.4), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.19), APOGEE PXC Modular (BACnet) (All versions < V3.5.4), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.19), Capital VSTAR (All versions with enabled Ethernet options), Desigo PXC00-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC00-U (All versions >= V2.3 and < V6.30.016), Desigo PXC001-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC100-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC12-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC128-U (All versions >= V2.3 and < V6.30.016), Desigo PXC200-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC22-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC22.1-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC36.1-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC50-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC64-U (All versions >= V2.3 and < V6.30.016), Desigo PXM20-E (All versions >= V2.3 and < V6.30.016), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.4), Nucleus ReadyStart V4 (All versions < V4.1.1), Nucleus Source Code (All versions), PLUSCONTROL 1st Gen (All versions), SIMOTICS CONNECT 400 (All versions < V0.5.0.0), TALON TC Compact (BACnet) (All versions < V3.5.4), TALON TC Modular (BACnet) (All versions < V3.5.4). The total length of an TCP payload (set in the IP header) is unchecked. This may lead to various side effects, including Information Leak and Denial-of-Service conditions, depending on the network buffer organization in memory. (FSMD-2021-0017)
Credit: productcert@siemens.com productcert@siemens.com
Affected Software | Affected Version | How to fix |
---|---|---|
Google Android | ||
Siemens Capital Vstar | ||
Siemens Nucleus NET | ||
Siemens Nucleus ReadyStart v3 | <2017.02.4 | |
Siemens Nucleus ReadyStart v4 | <4.1.1 | |
Siemens Nucleus Source Code | ||
Siemens Apogee Modular Building Controller Firmware | ||
Siemens Apogee Modular Building Controller | ||
Siemens Apogee Modular Equiment Controller Firmware | ||
Siemens Apogee Modular Equiment Controller | ||
Siemens Apogee Pxc Compact Firmware | ||
Siemens Apogee Pxc Compact | ||
Siemens Apogee Pxc Modular Firmware | ||
Siemens Apogee Pxc Modular | ||
Siemens Talon Tc Compact Firmware | ||
Siemens Talon Tc Compact | ||
Siemens Talon Tc Modular Firmware | ||
Siemens Talon Tc Modular | ||
All of | ||
Siemens Apogee Modular Building Controller Firmware | ||
Siemens Apogee Modular Building Controller | ||
All of | ||
Siemens Apogee Modular Equiment Controller Firmware | ||
Siemens Apogee Modular Equiment Controller | ||
All of | ||
Siemens Apogee Pxc Compact Firmware | ||
Siemens Apogee Pxc Compact | ||
All of | ||
Siemens Apogee Pxc Modular Firmware | ||
Siemens Apogee Pxc Modular | ||
All of | ||
Siemens Talon Tc Compact Firmware | ||
Siemens Talon Tc Compact | ||
All of | ||
Siemens Talon Tc Modular Firmware | ||
Siemens Talon Tc Modular |
Sign up to SecAlerts for real-time vulnerability data matched to your software, aggregated from hundreds of sources.
CVE-2021-31890 is a vulnerability identified in APOGEE MBC (PPC) (BACnet) and other Siemens software versions.
All versions of APOGEE MBC (PPC) (BACnet), APOGEE MBC (PPC) (P2 Ethernet), APOGEE MEC (PPC) (BACnet), APOGEE MEC (PPC) (P2 Ethernet), and APOGEE PXC Compact (BACnet) are affected, with APOGEE PXC Compact versions prior to V3.5.4 being vulnerable.
CVE-2021-31890 has a severity rating of 9.1 (critical).
You can find more information about CVE-2021-31890 in the Siemens ProductCERT advisories SSA-044112, SSA-114589, and SSA-223353.
CVE-2021-31890 is associated with CWE-240.