First published: Thu Jul 28 2022(Updated: )

Honeywell Experion PKS Safety Manager (SM and FSC) through 2022-05-06 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0053, there is a Honeywell Experion PKS Safety Manager insufficient logic security controls issue. The affected components are characterized as: Honeywell FSC runtime (FSC-CPU, QPP), Honeywell Safety Builder. The potential impact is: Remote Code Execution, Denial of Service. The Honeywell Experion PKS Safety Manager family of safety controllers utilize the unauthenticated Safety Builder protocol (FSCT-2022-0051) for engineering purposes, including downloading projects and control logic to the controller. Control logic is downloaded to the controller on a block-by-block basis. The logic that is downloaded consists of FLD code compiled to native machine code for the CPU module (which applies to both the Safety Manager and FSC families). Since this logic does not seem to be cryptographically authenticated, it allows an attacker capable of triggering a logic download to execute arbitrary machine code on the controller's CPU module in the context of the runtime. While the researchers could not verify this in detail, the researchers believe that the microprocessor underpinning the FSC and Safety Manager CPU modules is incapable of offering memory protection or privilege separation capabilities which would give an attacker full control of the CPU module. There is no authentication on control logic downloaded to the controller. Memory protection and privilege separation capabilities for the runtime are possibly lacking. The researchers confirmed the issues in question on Safety Manager R145.1 and R152.2 but suspect the issue affects all FSC and SM controllers and associated Safety Builder versions regardless of software or firmware revision. An attacker who can communicate with a Safety Manager controller via the Safety Builder protocol can execute arbitrary code without restrictions on the CPU module, allowing for covert manipulation of control operations and implanting capabilities similar to the TRITON malware (MITRE ATT&CK software ID S1009). A mitigating factor with regards to some, but not all, of the above functionality is that these require the Safety Manager physical keyswitch to be in the right position.

Credit: cve@mitre.org cve@mitre.org

Affected SoftwareAffected VersionHow to fix
Honeywell Safety Manager Firmware
Honeywell Safety Manager

Never miss a vulnerability like this again

Sign up to SecAlerts for real-time vulnerability data matched to your software, aggregated from hundreds of sources.

Frequently Asked Questions

  • What is the vulnerability ID?

    CVE-2022-30315

  • What is the severity of CVE-2022-30315?

    The severity of CVE-2022-30315 is critical with a score of 9.8.

  • Which software is affected by CVE-2022-30315?

    The Honeywell Experion PKS Safety Manager (SM and FSC) software is affected by CVE-2022-30315.

  • What is the vulnerability description of CVE-2022-30315?

    CVE-2022-30315 is an insufficient verification of data authenticity vulnerability in Honeywell Experion PKS Safety Manager (SM and FSC) software.

  • How can I fix CVE-2022-30315?

    To fix CVE-2022-30315, apply the necessary security updates provided by Honeywell.

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.