CVE-2025-11784: Stack-based buffer overflow vulnerability in Circutor SGE-PLC1000/SGE-PLC50
Stack-based buffer overflow vulnerability in Circutor SGE-PLC1000/SGE-PLC50 v9.0.2. In the 'ShowMeterDatabase()' function, there is an unlimited user input that is copied to a fixed-size buffer via 'sprintf()'. The 'GetParameter(meter)' function retrieves the user input, which is directly incorporated into a buffer without size validation. An attacker can provide an excessively large input for the 'meter' parameter.
Affected Software
Remediation
Recommended actions to resolve this vulnerability, in priority order.
- Upgrade
Upgrade
Circutor Compact DC / GEDE EDCto a version that resolves this vulnerability.Fixed in 2.0.4
Event History
Frequently Asked Questions
What is the severity of CVE-2025-11784?
CVE-2025-11784 has a high severity due to the potential for a stack-based buffer overflow that can lead to code execution.
How do I fix CVE-2025-11784?
To fix CVE-2025-11784, update your Circutor SGE-PLC1000 or SGE-PLC50 devices to the latest version that addresses this vulnerability.
Which devices are affected by CVE-2025-11784?
CVE-2025-11784 affects Circutor SGE-PLC1000 and SGE-PLC50 running version 9.0.2.
What causes the vulnerability in CVE-2025-11784?
CVE-2025-11784 is caused by an unlimited user input being copied to a fixed-size buffer, leading to a stack-based buffer overflow.
Could CVE-2025-11784 be exploited remotely?
Yes, CVE-2025-11784 could potentially be exploited remotely if an attacker can send specially crafted input to the affected devices.