A vulnerability has been identified in SIMATIC WinCC OA Operator iOS App (All versions < V1.4). Insufficient protection of sensitive information (e.g. session key for accessing server) in Siemens WinCC OA Operator iOS app could allow an attacker with physical access to the mobile device to read unencrypted data from the app's directory. Siemens provides mitigations to resolve the security issue.
A vulnerability has been identified in Cerberus DMS (All versions), Desigo CC (All versions), Desigo CC Compact (All versions), SIMATIC WinCC OA V3.16 (All versions in default configuration), SIMATIC WinCC OA V3.17 (All versions in non-default configuration), SIMATIC WinCC OA V3.18 (All versions in non-default configuration). Affected applications use client-side only authentication, when neither server-side authentication (SSA) nor Kerberos authentication is enabled. In this configuration, attackers could impersonate other users or exploit the client-server protocol without being authenticated.