A security issue exists within the Rockwell Automation Driver Package x64 Microsoft Installer File (MSI) repair functionality, installed with FTLinx. Authenticated attackers with valid Windows Users credentials can initiate a repair and hijack the resulting console window for vbpinstall.exe. This allows the launching of a command prompt running with SYSTEM-level privileges, allowing full access to all files, processes, and system resources.
A security issue exists within the x86 Microsoft Installer File (MSI), installed with FTLinx. Authenticated attackers with valid Windows user credentials can initiate a repair and hijack the resulting console window. This allows the launching of a command prompt running with SYSTEM-level privileges, allowing full access to all files, processes, and system resources.
An attacker can craft and send an OpenNamespace message to port 4241 with valid session-id that triggers an unhandled exception in CFTLDManager::HandleRequest function in RnaDaSvr.dll, resulting in process termination. Observed in FactoryTalk Linx 6.11. All versions of FactoryTalk Linx are affected.
An attacker-controlled memory allocation size can be passed to the C++ new operator in RnaDaSvr.dll by sending a specially crafted ConfigureItems message to TCP port 4241. This will cause an unhandled exception, resulting in termination of RSLinxNG.exe. Observed in FactoryTalk 6.11. All versions of FactoryTalk Linx are affected.
An attacker-controlled memory allocation size can be passed to the C++ new operator in the CServerManager::HandleBrowseLoadIconStreamRequest in messaging.dll. This can be done by sending a specially crafted message to 127.0.0.1:7153. Observed in FactoryTalk Linx 6.11. All versions of FactoryTalk Linx are affected.