7.5
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

ABB, Phoenix Contact, Schneider Electric, Siemens, WAGO - Programmable Logic Controllers, multiple versions. Researchers have found some controllers are susceptible to a denial-of-service attack due to a flood of network packets.

Remedy

Fixes are available in  Schneider Electric Modicon M221 firmware v1.10.0.0 and EcoStruxure Machine Expert – Basic v1.0 software (formerly SoMachine Basic) using either of the following options: Use this link to download the Machine Expert Basic software. Or run the Schneider Electric Software Update tool in order to download and install EcoStruxure Machine Expert – Basic v1.0 software. For additional information, see the Schneider Electric security notice SEVD-2019-045-01. (https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2019-045-01) Schneider Electric strongly recommends following industry cybersecurity best practices, such as: * Physical controls should be in place so no unauthorized person would have access to the ICS and safety controllers, peripheral equipment, or the ICS and safety networks. * All controllers should reside in locked cabinets and never be left in the “Program” mode. * All programming software should be kept in locked cabinets and should never be connected to any network other than the network for the devices it is intended. * All methods of mobile data exchange with the isolated network (e.g., CDs, USB drives, etc.) should be scanned before use in terminals or any node connected to these networks. * Laptops that have connected to any other network besides the intended network should never be allowed to connect to the safety or control networks without proper sanitation.
First published (updated )
Severity
7.3
CVSS:3.1/AV:A/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:N

A CWE-334: Small Space of Random Values vulnerability exists in Modicon M221 (all references, all versions) that could allow the attacker to break the encryption keys when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller.

First published (updated )
Severity
7.1
CVSS:3.1/AV:A/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N

A CWE-311: Missing Encryption of Sensitive Data vulnerability exists in Modicon M221 (all references, all versions) that could allow the attacker to find the password hash when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller and broke the encryption keys.

First published (updated )
Severity
7.5
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

An Environment (CWE-2) vulnerability exists in SoMachine Basic, all versions, and Modicon M221(all references, all versions prior to firmware V1.10.0.0) which could cause cycle time impact when flooding the M221 ethernet interface while the Ethernet/IP adapter is activated.

First published (updated )
Severity
7.5
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

An Improper Check for Unusual or Exceptional Conditions vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to remotely reboot Modicon M221 using crafted programing protocol frames.

First published (updated )
Severity
7.5
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

A Permissions, Privileges, and Access Control vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to decode the password using rainbow table.

First published (updated )
Severity
7.3
Weak Encryption
CVSS:3.1/AV:A/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:N

A CWE-326: Inadequate Encryption Strength vulnerability exists in Modicon M221 (all references, all versions) that could allow the attacker to break the encryption key when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller.

First published (updated )
Severity
8.2
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:H

A CWE-306: Missing Authentication for Critical Function vulnerability exists which could cause a modification of device IP configuration (IP address, network mask and gateway IP address) when a specific Ethernet frame is received in all versions of: Modicon M100, Modicon M200, Modicon M221, ATV IMC drive controller, Modicon M241, Modicon M251, Modicon M258, Modicon LMC058, Modicon LMC078, PacDrive Eco ,PacDrive Pro, PacDrive Pro2

First published (updated )

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.
© 2026 SecAlerts Pty Ltd.
ABN: 70 645 966 203, ACN: 645 966 203