Where
-Infinity
0
Severity
10
Buffer Overflow
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

An exploitable stack buffer overflow vulnerability exists in the command line utility getcouplerdetails of WAGO PFC200 Firmware versions 03.01.07(13) and 03.00.39(12), and WAGO PFC100 Firmware version 03.00.39(12). A specially crafted set of packets sent to the iocheckd service "I/O-Check" can cause a stack buffer overflow in the sub-process getcouplerdetails, resulting in code execution. An attacker can send unauthenticated packets to trigger this vulnerability.

First published (updated )
Severity
10
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

In 3S-Smart Software Solutions GmbH CODESYS Control V3 products prior to version 3.5.14.0, user access management and communication encryption is not enabled by default, which could allow an attacker access to the device and sensitive information, including user credentials.

First published (updated )
Severity
10
Buffer Overflow
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

An exploitable heap buffer overflow vulnerability exists in the iocheckd service ''I/O-Chec'' functionality of WAGO PFC 200 Firmware version 03.01.07(13) and 03.00.39(12), and WAGO PFC100 Firmware version 03.00.39(12). A specially crafted set of packets can cause a heap buffer overflow, potentially resulting in code execution. An attacker can send unauthenticated packets to trigger this vulnerability.

First published (updated )
Severity
10
Buffer Overflow
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

An exploitable stack buffer overflow vulnerability exists in the iocheckd service ''I/O-Check'' functionality of WAGO PFC200 Firmware version 03.01.07(13), WAGO PFC200 Firmware version 03.00.39(12) and WAGO PFC100 Firmware version 03.00.39(12). A specially crafted set of packets can cause a stack buffer overflow, resulting in code execution. An attacker can send unauthenticated packets to trigger this vulnerability.

First published (updated )
Severity
10
Buffer Overflow
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

CODESYS V3 web server before 3.5.15.40, as used in CODESYS Control runtime systems, has a buffer overflow.

First published (updated )
Severity
9.8
Buffer Overflow
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

An exploitable heap buffer overflow vulnerability exists in the iocheckd service "I/O-Check" functionality of WAGO PFC200 Firmware versions 03.01.07(13) and 03.00.39(12), and WAGO PFC100 Firmware version 03.00.39(12). A specially crafted set of packets can cause a heap buffer overflow, potentially resulting in code execution. An attacker can send unauthenticated packets to trigger this vulnerability.

First published (updated )
Severity
9.8
Buffer Overflow
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

CODESYS 3 web server before 3.5.15.20, as distributed with CODESYS Control runtime systems, has a Buffer Overflow.

First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

CODESYS V3 web server, all versions prior to 3.5.14.10, allows an attacker to send specially crafted http or https requests which could cause a stack overflow and create a denial-of-service condition or allow remote code execution.

First published (updated )
Severity
9.8
Buffer Overflow
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

eap.c in pppd in ppp 2.4.2 through 2.4.8 has an rhostname buffer overflow in the eaprequest and eapresponse functions.

1 / 3
First published (updated )
Severity
9.8
Buffer Overflow
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

An exploitable heap buffer overflow vulnerability exists in the iocheckd service I/O-Check functionality of WAGO PFC200 Firmware version 03.01.07(13), WAGO PFC200 Firmware version 03.00.39(12), and WAGO PFC100 Firmware version 03.00.39(12). A specially crafted set of packets can cause a heap buffer overflow, potentially resulting in code execution. An attacker can send unauthenticated packets to trigger this vulnerability.

First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

An issue was discovered in 3S-Smart CODESYS V3 products. The CODESYS Gateway does not correctly verify the ownership of a communication channel. All variants of the following CODESYS V3 products in all versions prior to v3.5.14.20 that contain the CmpGateway component are affected, regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control V3 Runtime System Toolkit, CODESYS Gateway V3, CODESYS V3 Development System.

First published (updated )
Severity
9.8
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

The Web-GUI on WAGO Series 750-88x (750-330, 750-352, 750-829, 750-831, 750-852, 750-880, 750-881, 750-882, 750-884, 750-885, 750-889) and Series 750-87x (750-830, 750-849, 750-871, 750-872, 750-873) devices has undocumented service access.

First published (updated )
Severity
9.8
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

An Improper Authentication issue was discovered in WAGO PFC200 Series 3S CoDeSys Runtime versions 2.3.X and 2.4.X. An attacker can execute different unauthenticated remote operations because of the CoDeSys Runtime application, which is available via network by default on Port 2455. An attacker could execute some unauthenticated commands such as reading, writing, or deleting arbitrary files, or manipulate the PLC application during runtime by sending specially-crafted TCP packets to Port 2455.

First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

In CODESYS V3 products in all versions prior V3.5.16.0 containing the CmpUserMgr, the CODESYS Control runtime system stores the online communication passwords using a weak hashing algorithm. This can be used by a local attacker with low privileges to gain full control of the device.

First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

The configuration backend allows an unauthenticated user to write arbitrary data with root privileges to the storage, which could lead to unauthenticated remote code execution and full system compromise.

First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

The configuration backend of the web-based management can be used by unauthenticated users, although only authenticated users should be able to use the API. The vulnerability allows an unauthenticated attacker to read and set several device parameters that can lead to full compromise of the device.

First published (updated )
Severity
9.8
OS Command Injection
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

In multiple products of WAGO a vulnerability allows an unauthenticated, remote attacker to create new users and change the device configuration which can result in unintended behaviour, Denial of Service and full system compromise.

First published (updated )
Severity
9.4
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H

An exploitable denial of service vulnerability exists in the iocheckd service "I/O-Check" functionality of WAGO PFC200 Firmware versions 03.01.07(13) and 03.00.39(12), and WAGO PFC100 Firmware version 03.00.39(12). A specially crafted set of packets can cause a denial of service, resulting in the device entering an error state where it ceases all network communications. An attacker can send unauthenticated packets to trigger this vulnerability.

First published (updated )
Severity
9.1
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N

An issue was discovered in WAGO 750-8202/PFC200 prior to FW04 (released August 2015), WAGO 750-881 prior to FW09 (released August 2016), and WAGO 0758-0874-0000-0111. By accessing a specific uniform resource locator (URL) on the web server, a malicious user is able to edit and to view settings without authenticating.

First published (updated )
Severity
9.1
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H

An exploitable denial-of-service vulnerability exists in the iocheckd service "I/O-Check" functionality of WAGO PFC 200 Firmware versions 03.01.07(13) and 03.00.39(12), and WAGO PFC100 Firmware version 03.00.39(12). A single packet can cause a denial of service and weaken credentials resulting in the default documented credentials being applied to the device. An attacker can send an unauthenticated packet to trigger this vulnerability.

First published (updated )
Severity
9.1
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H

An exploitable denial-of-service vulnerability exists in the iocheckd service ‘’I/O-Chec’’ functionality of WAGO PFC 200 Firmware versions 03.01.07(13) and 03.00.39(12), and WAGO PFC 100 Firmware version 03.00.39(12). A specially crafted set of packets can cause a denial of service, resulting in the device entering an error state where it ceases all network communications. An attacker can send unauthenticated packets to trigger this vulnerability.

First published (updated )
Severity
9.1
Path Traversal
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N

On WAGO PFC200 devices in different firmware versions with special crafted packets an authorised attacker with network access to the device can access the file system with higher privileges.

Remedy

WAGO recommends all effected users with CODESYS 2.3 Runtime PLCs to update to the firmware versions listed at https://cert.vde.com/en-us/advisories/vde-2021-014 in the solution paragraph.
First published (updated )
Severity
9.1
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:H

Improper Authentication vulnerability in WAGO 750-8XX series with FW version <= FW07 allows an attacker to change some special parameters without authentication. This issue affects: WAGO 750-852, WAGO 750-880/xxx-xxx, WAGO 750-881, WAGO 750-831/xxx-xxx, WAGO 750-882, WAGO 750-885/xxx-xxx, WAGO 750-889 in versions FW07 and below.

Remedy

Upgrade devices to the latest standard firmware (> FW07).
First published (updated )
Severity
9.1
CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:C/C:H/I:H/A:H

An exploitable remote code execution vulnerability exists in the Cloud Connectivity functionality of WAGO PFC200 versions 03.02.02(14), 03.01.07(13), and 03.00.39(12). A specially crafted XML file will direct the Cloud Connectivity service to download and execute a shell script with root privileges.

First published (updated )
Severity
9.1
CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:C/C:H/I:H/A:H

An exploitable improper host validation vulnerability exists in the Cloud Connectivity functionality of WAGO PFC200 Firmware versions 03.02.02(14), 03.01.07(13), and 03.00.39(12). A specially crafted HTTPS POST request can cause the software to connect to an unauthorized host, resulting in unauthorized access to firmware update functionality. An attacker can send an authenticated HTTPS POST request to direct the Cloud Connectivity software to connect to an attacker controlled Azure IoT Hub node.

First published (updated )
Severity
9
CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H

An exploitable code execution vulnerability exists in the Web-Based Management (WBM) functionality of WAGO PFC 200 03.03.10(15). A specially crafted series of HTTP requests can cause code execution resulting in remote code execution. An attacker can make an authenticated HTTP request to trigger this vulnerability.

First published (updated )
Severity
9
Command Injection, OS Command Injection
CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H

An exploitable command injection vulnerability exists in the cloud connectivity feature of WAGO PFC200. An attacker can inject operating system commands into any of the parameter values contained in the firmware update command. This affects WAGO PFC200 Firmware version 03.02.02(14), version 03.01.07(13), and version 03.00.39(12)

First published (updated )
Severity
8.8
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H

An issue was discovered in 3S-Smart CODESYS V3 through 3.5.12.30. A user with low privileges can take full control over the runtime.

First published (updated )
Severity
8.8
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

An issue was discovered in 3S-Smart CODESYS V3 products. The application may utilize non-TLS based encryption, which results in user credentials being insufficiently protected during transport. All variants of the following CODESYS V3 products in all versions containing the CmpUserMgr component are affected regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control RTE V3, CODESYS Control RTE V3 (for Beckhoff CX), CODESYS Control Win V3 (also part of the CODESYS Development System setup), CODESYS V3 Simulation Runtime (part of the CODESYS Development System), CODESYS Control V3 Runtime System Toolkit, CODESYS HMI V3.

First published (updated )
Severity
8.8
Path Traversal
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H

The CODESYS runtime system in multiple versions allows an remote low privileged attacker to use a path traversal vulnerability to access and modify all system files as well as DoS the device.

First published (updated )

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.