First published: Tue Mar 20 2018(Updated: )

A vulnerability has been identified in SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC CP 343-1 (incl. SIPLUS variants) (All versions), SIMATIC CP 343-1 Advanced (incl. SIPLUS variants) (All versions), SIMATIC CP 443-1 (All versions < V3.3), SIMATIC CP 443-1 (All versions < V3.3), SIMATIC CP 443-1 Advanced (All versions < V3.3), SIMATIC ET 200pro IM154-8 PN/DP CPU (All versions < V3.2.16), SIMATIC ET 200pro IM154-8F PN/DP CPU (All versions < V3.2.16), SIMATIC ET 200pro IM154-8FX PN/DP CPU (All versions < V3.2.16), SIMATIC ET 200S IM151-8 PN/DP CPU (All versions < V3.2.16), SIMATIC ET 200S IM151-8F PN/DP CPU (All versions < V3.2.16), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V1.7.0), SIMATIC S7-1500 Software Controller (All versions < V1.7.0), SIMATIC S7-300 CPU 314C-2 PN/DP (All versions < V3.3.16), SIMATIC S7-300 CPU 315-2 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 315F-2 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 315T-3 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 317-2 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 317F-2 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 317T-3 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 317TF-3 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 319-3 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 319F-3 PN/DP (All versions < V3.2.16), SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.7), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.1), SIMATIC WinAC RTX 2010 (All versions < V2010 SP3), SIMATIC WinAC RTX F 2010 (All versions < V2010 SP3), SINUMERIK 828D (All versions < V4.7 SP6 HF1), SIPLUS ET 200S IM151-8 PN/DP CPU (All versions < V3.2.16), SIPLUS ET 200S IM151-8F PN/DP CPU (All versions < V3.2.16), SIPLUS NET CP 443-1 (All versions < V3.3), SIPLUS NET CP 443-1 Advanced (All versions < V3.3), SIPLUS S7-300 CPU 314C-2 PN/DP (All versions < V3.3.16), SIPLUS S7-300 CPU 315-2 PN/DP (All versions < V3.2.16), SIPLUS S7-300 CPU 315F-2 PN/DP (All versions < V3.2.16), SIPLUS S7-300 CPU 317-2 PN/DP (All versions < V3.2.16), SIPLUS S7-300 CPU 317F-2 PN/DP (All versions < V3.2.16), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), Softnet PROFINET IO for PC-based Windows systems (All versions). Responding to a PROFINET DCP request with a specially crafted PROFINET DCP packet could cause a denial of service condition of the requesting system. The security vulnerability could be exploited by an attacker located on the same Ethernet segment (OSI Layer 2) as the targeted device. A manual restart is required to recover the system.

Credit: productcert@siemens.com

Affected SoftwareAffected VersionHow to fix
Siemens Simatic Cp 343-1 Firmware
Siemens Simatic Cp 343-1
Siemens Simatic Cp 343-1 Firmware
Siemens Simatic Cp 343-1
Siemens Simatic Cp 443-1 Firmware
Siemens Simatic Cp 443-1
Siemens Simatic Cp 443-1 Firmware
Siemens Simatic Cp 443-1
Siemens Simatic S7-1500 Firmware<1.7.0
Siemens Simatic S7-1500
Siemens Simatic S7-300 Firmware
Siemens Simatic S7-300
Siemens Simatic S7-400 H V6 Firmware
Siemens Simatic S7-400 H V6
Siemens Simatic S7-400 Pn\/dp V6 Firmware<6.0.7
Siemens Simatic S7-400 Pn\/dp V6
Siemens Simatic S7-400 Pn\/dp V7 Firmware
Siemens Simatic S7-400 Pn\/dp V7
Siemens Simatic S7-410 Firmware<8.1
Siemens Simatic S7-410
Siemens Simatic Winac Rtx 2010 Firmware
Siemens Simatic Winac Rtx 2010
Siemens Sinumerik 828d Firmware
Siemens Sinumerik 828d
Siemens Softnet Pn-io Linux Firmware Windows
Siemens Softnet Pn-io Linux

Never miss a vulnerability like this again

Sign up to SecAlerts for real-time vulnerability data matched to your software, aggregated from hundreds of sources.

Frequently Asked Questions

  • What is the vulnerability ID of this vulnerability?

    The vulnerability ID is CVE-2018-4843.

  • What is the severity of CVE-2018-4843?

    The severity of CVE-2018-4843 is medium (6.5).

  • Which versions of SIMATIC S7-400 CPU are affected by CVE-2018-4843?

    All versions of SIMATIC S7-400 CPU 414-3 PN/DP V7, SIMATIC S7-400 CPU 414F-3 PN/DP V7, SIMATIC S7-400 CPU 416-3 PN/DP V7, and SIMATIC S7-400 CPU 416F-3 PN/DP V7 prior to V7.0.3 are affected.

  • Which software is affected by CVE-2018-4843?

    The affected software includes Siemens Simatic CP 343-1 Firmware and Siemens Simatic S7-400 Pn/dp V7 Firmware.

  • Is there a fix available for CVE-2018-4843?

    Yes, updating to version V7.0.3 for SIMATIC S7-400 CPU 414-3 PN/DP V7, SIMATIC S7-400 CPU 414F-3 PN/DP V7, SIMATIC S7-400 CPU 416-3 PN/DP V7, and SIMATIC S7-400 CPU 416F-3 PN/DP V7 can fix the vulnerability.

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.