First published: Tue Jun 26 2018(Updated: )
A vulnerability has been identified in IEC 61850 system configurator (All versions < V5.80), DIGSI 5 (affected as IEC 61850 system configurator is incorporated) (All versions < V7.80), DIGSI 4 (All versions < V4.93), SICAM PAS/PQS (All versions < V8.11), SICAM PQ Analyzer (All versions < V3.11), SICAM SCC (All versions < V9.02 HF3). A service of the affected products listening on all of the host's network interfaces on either port 4884/TCP, 5885/TCP, or port 5886/TCP could allow an attacker to either exfiltrate limited data from the system or to execute code with Microsoft Windows user permissions. Successful exploitation requires an attacker to be able to send a specially crafted network request to the vulnerable service and a user interacting with the service's client application on the host. In order to execute arbitrary code with Microsoft Windows user permissions, an attacker must be able to plant the code in advance on the host by other means. The vulnerability has limited impact to confidentiality and integrity of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known. Siemens confirms the security vulnerability and provides mitigations to resolve the security issue.
Credit: productcert@siemens.com productcert@siemens.com
Affected Software | Affected Version | How to fix |
---|---|---|
Siemens Ec 61850 System Configurator Firmware | <5.80 | |
Siemens Ec 61850 System Configurator | ||
Siemens Sicam Pq Analyzer Firmware | <3.11 | |
Siemens Sicam Pq Analyzer | ||
Siemens Sicam Scc Firmware | ||
Siemens Sicam Scc | ||
Siemens Digsi 4 Firmware | ||
Siemens Digsi 4 | ||
Siemens Digsi 5 Firmware | <7.80 | |
Siemens Digsi 5 | ||
Siemens Sicam Pas\/pqs | <8.11 |
Sign up to SecAlerts for real-time vulnerability data matched to your software, aggregated from hundreds of sources.
The severity of CVE-2018-4858 is critical with a CVSS score of 7.8.
The affected software versions are IEC 61850 system configurator (All versions < V5.80), DIGSI 5 (All versions < V7.80), DIGSI 4 (All versions < V4.93), SICAM PAS/PQS (All versions < V8.11), SICAM PQ Analyzer (All versions < V3.11), SICAM SCC, and Digsi 5.
To fix CVE-2018-4858, update the affected software versions to at least V5.80 for IEC 61850 system configurator, V7.80 for DIGSI 5, V4.93 for DIGSI 4, V8.11 for SICAM PAS/PQS, or V3.11 for SICAM PQ Analyzer.
You can find more information about CVE-2018-4858 on the following references: http://www.securityfocus.com/bid/105933, https://cert-portal.siemens.com/productcert/pdf/ssa-159860.pdf, and https://ics-cert.us-cert.gov/advisories/ICSA-18-317-01.
The CWE category of CVE-2018-4858 is CWE-284.