CVE-2019-13927: Medium severity siemens pxc00-e.d firmware vulnerability

Published Dec 12, 2019
·
Updated

A vulnerability has been identified in Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D with Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2 (All firmware versions < V6.00.320), Desigo PX automation controllers PXC00-U, PXC64-U, PXC128-U with Desigo PX Web modules PXA30-W0, PXA30-W1, PXA30-W2 (All firmware versions < V6.00.320), Desigo PX automation controllers PXC22.1-E.D, PXC36-E.D, PXC36.1-E.D with activated web server (All firmware versions < V6.00.320). The device contains a vulnerability that could allow an attacker to cause a denial of service condition on the device's web server by sending a specially crafted HTTP message to the web server port (tcp/80). The security vulnerability could be exploited by an attacker with network access to an affected device. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise the availability of the device's web service. While the device itself stays operational, the web server responds with HTTP status code 404 (Not found) to any further request. A reboot is required to recover the web interface. At the time of advisory publication no public exploitation of this security vulnerability was known.

Affected Software

32 affected components
Siemens Pxc00-e.d Firmware<6.00.320
Siemens Pxc00-e.d
Siemens Pxc50-e.d Firmware<6.00.320
Siemens Pxc50-e.d
Siemens Pxc100-e.d Firmware<6.00.320
Siemens Pxc100-e.d
Siemens Pxc200-e.d Firmware<6.00.320
Siemens Pxc200-e.d
Siemens Pxa40-w0 Firmware<6.00.320
Siemens Pxa40-w0
Siemens Pxa40-w1 Firmware<6.00.320
Siemens Pxa40-w1
Siemens Pxa40-w2 Firmware<6.00.320
Siemens Pxa40-w2
Siemens Pxc00-u Firmware<6.00.320
Siemens Pxc00-u
Siemens Pxc64-u Firmware<6.00.320
Siemens Pxc64-u
Siemens Pxc128-u Firmware<6.00.320
Siemens Pxc128-u
Siemens Pxa30-w0 Firmware<6.00.320
Siemens Pxa30-w0
Siemens Pxa30-w1 Firmware<6.00.320
Siemens Pxa30-w1
Siemens Pxa30-w2 Firmware<6.00.320
Siemens Pxa30-w2
Siemens Pxc22.1-e.d Firmware<6.00.320
Siemens Pxc22.1-e.d
Siemens Pxc36-e.d Firmware<6.00.320
Siemens Pxc36-e.d
Siemens Pxc36.1-e.d Firmware<6.00.320
Siemens Pxc36.1-e.d

Event History

Dec 12, 2019
CVE Published
via MITRE·01:19 PM
Data Sourced
via MITRE·01:19 PM
DescriptionWeakness
Free Weekly Intel

Don't miss critical vulnerabilities

Join thousands of security professionals who receive our weekly digest of trending CVEs, zero-days, and exploited vulnerabilities.

No spam. Unsubscribe anytime.

Frequently Asked Questions

1

What is the severity of CVE-2019-13927?

CVE-2019-13927 is rated as a high severity vulnerability affecting specific Siemens Desigo PX automation controllers and modules.

2

How do I fix CVE-2019-13927?

To fix CVE-2019-13927, update affected devices to firmware version 6.00.320 or newer.

3

Which devices are affected by CVE-2019-13927?

CVE-2019-13927 affects Siemens Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D, and specific PXA Web modules.

4

What are the potential risks associated with CVE-2019-13927?

The potential risks of CVE-2019-13927 include unauthorized access and manipulation of automation operations.

5

Is there any workaround for CVE-2019-13927?

Currently, there are no documented workarounds for CVE-2019-13927 other than applying the firmware update.

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.