First published: Thu Apr 22 2021(Updated: )
A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions < V5.2), Nucleus Source Code (Versions including affected DNS modules), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS domain name record decompression functionality does not properly validate the pointer offset values. The parsing of malformed responses could result in a write past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to execute code in the context of the current process or cause a denial-of-service condition.
Credit: productcert@siemens.com productcert@siemens.com
Affected Software | Affected Version | How to fix |
---|---|---|
Siemens Nucleus NET | <5.2 | |
Siemens Nucleus Source Code |
Sign up to SecAlerts for real-time vulnerability data matched to your software, aggregated from hundreds of sources.
The severity of CVE-2020-27009 is high with a severity value of 8.1.
The affected software of CVE-2020-27009 includes Siemens Nucleus Net versions up to exclusive 5.2 and Siemens Nucleus Source Code.
To fix CVE-2020-27009, it is recommended to update to the latest version (V3.5.5 for APOGEE PXC Compact (BACnet) and APOGEE PXC Modular (BACnet), V2.8.20 for APOGEE PXC Compact (P2 Ethernet) and APOGEE PXC Modular (P2 Ethernet), and V5.2 for Nucleus NET).
The Common Weakness Enumeration (CWE) ID of CVE-2020-27009 includes CWE-787 and CWE-823.
You can find more information about CVE-2020-27009 in the Siemens ProductCERT advisory: [link](https://cert-portal.siemens.com/productcert/pdf/ssa-180579.pdf) and [link](https://cert-portal.siemens.com/productcert/pdf/ssa-185699.pdf).