First published: Tue May 10 2022(Updated: )
A vulnerability has been identified in SIMATIC CP 442-1 RNA (All versions < V1.5.18), SIMATIC CP 443-1 RNA (All versions < V1.5.18). The affected devices improperly handles excessive ARP broadcast requests. This could allow an attacker to create a denial of service condition by performing ARP storming attacks, which can cause the device to reboot.
Credit: productcert@siemens.com
Affected Software | Affected Version | How to fix |
---|---|---|
Siemens Simatic CP 442-1 RNA | <1.5.18 | |
Siemens Simatic CP 442-1 RNA Firmware | ||
Siemens Simatic CP 443-1 RNA | <1.5.18 | |
Siemens Simatic CP 443-1 RNA Firmware |
Sign up to SecAlerts for real-time vulnerability data matched to your software, aggregated from hundreds of sources.
CVE-2022-27640 has been classified as a high severity vulnerability due to the potential for denial of service attacks.
To address CVE-2022-27640, upgrade your Siemens SIMATIC CP 442-1 RNA or CP 443-1 RNA devices to firmware version 1.5.18 or higher.
CVE-2022-27640 affects all versions of Siemens SIMATIC CP 442-1 RNA and CP 443-1 RNA below version 1.5.18.
CVE-2022-27640 can be exploited to create an ARP storm, leading to a denial of service condition.
As of now, there are no reported active exploits for CVE-2022-27640, but it poses a significant risk if not mitigated.