Where
-Infinity
0
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 does not protect against additional software programming connections. An attacker can connect to the PLC while an existing connection is already active.

Remedy

Automation Direct reports these vulnerabilities are all mitigated by Version 3.00 and recommends users update software and firmware to the latest version. Automation Direct also recommends users follow its security guidelines.
First published (updated )
Severity
7.5
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

The programming protocol allows for a previously entered password and lock state to be read by an attacker. If the previously entered password was successful, the attacker can then use the password to unlock Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00.

Remedy

Automation Direct reports these vulnerabilities are all mitigated by Version 3.00 and recommends users update software and firmware to the latest version. Automation Direct also recommends users follow its security guidelines.
First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

All programming connections receive the same unlocked privileges, which can result in a privilege escalation. During the time Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 is unlocked by an authorized user, an attacker can connect to the PLC and read the project without authorization.

Remedy

Automation Direct reports these vulnerabilities are all mitigated by Version 3.00 and recommends users update software and firmware to the latest version. Automation Direct also recommends users follow its security guidelines.
First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

After Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 is unlocked by an authorized user, the unlocked state does not timeout. If the programming software is interrupted, the PLC remains unlocked. All subsequent programming connections are allowed without authorization. The PLC is only relocked by a power cycle, or when the programming software disconnects correctly.

Remedy

Automation Direct reports these vulnerabilities are all mitigated by Version 3.00 and recommends users update software and firmware to the latest version. Automation Direct also recommends users follow its security guidelines.
First published (updated )
Severity
7.5
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 passwords are sent as plaintext during unlocking and project transfers. An attacker who has network visibility can observe the password exchange.

Remedy

Automation Direct reports these vulnerabilities are all mitigated by Version 3.00 and recommends users update software and firmware to the latest version. Automation Direct also recommends users follow its security guidelines.
First published (updated )

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.