Where
-Infinity
0
Severity
7
EPSS
0.04%
Code Injection
CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:L/VI:L/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

A Local Code Injection Vulnerability exists in the product and version listed above. The vulnerability is due to incorrect default permissions and allows for DLLs to be executed with higher level permissions.

Remedy

Upgrade to V15 or apply patch. Answer ID 1152304
First published (updated )
Severity
7
EPSS
0.04%
CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:L/VI:L/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

An Incorrect Permission Assignment Vulnerability exists in the product and version listed above. The vulnerability is due to incorrect permissions being assigned to the remote debugger port and can allow for unauthenticated access to the system configuration.

Remedy

Upgrade to V15 or apply patch, answer ID 1152306.
First published (updated )
Severity
7.8
Input Validation
AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H

A remote code execution vulnerability exists in the affected product. The vulnerability allows users to save projects within the public directory allowing anyone with local access to modify and/or delete files. Additionally, a malicious user could potentially leverage this vulnerability to escalate their privileges by changing the macro to execute arbitrary code.

Remedy

Upgrade to Version 15
First published (updated )
Severity
9.8
Command Injection, XSS, Path Traversal
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

CVE-2024-45824 IMPACT

A remote code vulnerability exists in the affected products. The vulnerability occurs when chained with Path Traversal, Command Injection, and XSS Vulnerabilities and allows for full unauthenticated remote code execution. The link in the mitigations section below contains patches to fix this issue.

Remedy

Navigate to the following link and apply patches https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1151301 , directions are on the link page ( https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1151301 )
First published (updated )
Severity
8.8
EPSS
0.04%
CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

CVE-2024-7513 IMPACT

A code execution vulnerability exists in the affected product. The vulnerability occurs due to improper default file permissions allowing any user to edit or replace files, which are executed by account with elevated permissions.

Remedy

Upgrade to v15.0
First published (updated )
Severity
8.8
CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

A privilege escalation vulnerability exists in the affected product. The vulnerability allows low-privilege users to edit scripts, bypassing Access Control Lists, and potentially gaining further access within the system.

Remedy

AFFECTED PRODUCTS AND SOLUTION     Affected Product         First Known in software version         Corrected in software version         FactoryTalk® View SE         V12.0         v14   Mitigations and Workarounds Users using the affected software, who are not able to upgrade to one of the corrected versions, are encouraged to apply security best practices, where possible.    * Use the Secure Install option when installing FactoryTalk® Services Platform. * Security Best Practices https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight
First published (updated )
Severity
8.2
CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

A user authentication vulnerability exists in the Rockwell Automation FactoryTalk® View SE. The vulnerability allows a user from a remote system with FTView to send a packet to the customer’s server to view an HMI project. Due to the lack of proper authentication, this action is allowed without proper authentication verification.

Remedy

* Corrected in software version v14.0. * Users using the affected software, who are not able to upgrade to one of the corrected versions, are encouraged to apply security best practices, where possible.    * It is recommended that users enforce proper access controls within the network and segment networks containing sensitive information using IPSec: https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1090456 * Security Best Practice https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight s
First published (updated )
Severity
8.2
CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

A user authentication vulnerability exists in the Rockwell Automation FactoryTalk® View SE v12. The vulnerability allows a user from a remote system with FTView to send a packet to the customer’s server to view an HMI project. This action is allowed without proper authentication verification.

Remedy

* Corrected in software version v14.0. * Users using the affected software, who are not able to upgrade to one of the corrected versions, are encouraged to apply security best practices, where possible.    * It is recommended that users enforce proper access controls within the network and segment networks containing sensitive information using IPSec: https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1090456 * Security Best Practices https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight
First published (updated )
Severity
7.5
Input Validation
AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Rockwell Automation FactoryTalk View Site Edition insufficiently validates user input, which could potentially allow threat actors to send malicious data bringing the product offline. If exploited, the product would become unavailable and require a restart to recover resulting in a denial-of-service condition.

Remedy

* Install the patch that remediates the issue: BF29581 - Patch: External Service Interaction (HTTP), FactoryTalk View SE 11.0, 12.0 13.0 https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1140243 .
First published (updated )
Severity
9.8
Malicious File Upload, Input Validation
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Rockwell Automation FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets.  The device has the functionality, through a CIP class, to execute exported functions from libraries.  There is a routine that restricts it to execute specific functions from two dynamic link library files.  By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.

Remedy

* Install the security patches for the respective versions referencing BF29493 - Patch: FactoryTalk Linx CIP Vulnerability issue, FactoryTalk View ME 12.0, 13.0 https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1139946 .
First published (updated )
Severity
8.8
CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N

Due to usernames/passwords being stored in plaintext in Random Access Memory (RAM), a local, authenticated attacker could gain access to certain credentials, including Windows Logon credentials.

First published (updated )
Severity
8.8
Weak Encryption
CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H

The DeskLock tool provided with FactoryTalk View SE uses a weak encryption algorithm that may allow a local, authenticated attacker to decipher user credentials, including the Windows user or Windows DeskLock passwords. If the compromised user has an administrative account, an attacker could gain full access to the user’s operating system and certain components of FactoryTalk View SE.

First published (updated )
Severity
8.1
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N

In all versions of FactoryTalk View SEA remote, an authenticated attacker may be able to utilize certain handlers to interact with the data on the remote endpoint since those handlers do not enforce appropriate permissions. Rockwell Automation recommends enabling built in security features found within FactoryTalk View SE. Users should follow guidance found in knowledge base articles 109056 and 1126943 to set up IPSec and/or HTTPs.

Remedy

Rockwell Automation has released new versions of the affected products to mitigate the reported vulnerabilities. Affected users who are not able to apply the latest update are encouraged to seek additional mitigations or workarounds from the vendor’s published guidelines in their security advisory. Rockwell Automation recommends enabling built in security features found within FactoryTalk View SE. Users should follow guidance found in knowledge base articles 109056 and 1126943 to set up IPSec and/or HTTPs.
First published (updated )
Severity
4.3
Infoleak
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:L/I:N/A:N

All versions of FactoryTalk View SE disclose the hostnames and file paths for certain files within the system. A remote, authenticated attacker may be able to leverage this information for reconnaissance efforts. Rockwell Automation recommends enabling built in security features found within FactoryTalk View SE. Users should follow guidance found in knowledge base articles 109056 and 1126943 to set up IPSec and/or HTTPs.

Remedy

Rockwell Automation has released new versions of the affected products to mitigate the reported vulnerabilities. Affected users who are not able to apply the latest update are encouraged to seek additional mitigations or workarounds from the vendor’s published guidelines in their security advisory. Rockwell Automation recommends enabling built in security features found within FactoryTalk View SE. Users should follow guidance found in knowledge base articles 109056 and 1126943 to set up IPSec and/or HTTPs.
First published (updated )
Severity
7.8
Buffer Overflow
CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H

In all versions of FactoryTalk View SE, after bypassing memory corruption mechanisms found in the operating system, a local, authenticated attacker may corrupt the associated memory space allowing for arbitrary code execution. Rockwell Automation recommends applying patch 1126290. Before installing this patch, the patch rollup dated 06 Apr 2020 or later MUST be applied. 1066644 – Patch Roll-up for CPR9 SRx.

Remedy

Rockwell Automation has released new versions of the affected products to mitigate the reported vulnerabilities. Affected users who are not able to apply the latest update are encouraged to seek additional mitigations or workarounds from the vendor’s published guidelines in their security advisory. Rockwell Automation recommends applying patch 1126290. Before installing this patch, the patch rollup dated 06 Apr 2020 or later MUST be applied. 1066644 – Patch Roll-up for CPR9 SRx.
First published (updated )
Severity
9
Input Validation
CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H

All versions of FactoryTalk View SE do not properly validate input of filenames within a project directory. A remote, unauthenticated attacker may be able to execute a crafted file on a remote endpoint that may result in remote code execution (RCE). Rockwell Automation recommends applying patch 1126289. Before installing this patch, the patch rollup dated 06 Apr 2020 or later MUST be applied. 1066644 – Patch Roll-up for CPR9 SRx.

Remedy

Rockwell Automation has released new versions of the affected products to mitigate the reported vulnerabilities. Affected users who are not able to apply the latest update are encouraged to seek additional mitigations or workarounds from the vendor’s published guidelines in their security advisory. Rockwell Automation recommends applying patch 1126289. Before installing this patch, the patch rollup dated 06 Apr 2020 or later MUST be applied. 1066644 – Patch Roll-up for CPR9 SRx.
First published (updated )

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.
© 2026 SecAlerts Pty Ltd.
ABN: 70 645 966 203, ACN: 645 966 203