In Festo Controller CECC-X-M1 product family in multiple versions, the http-endpoint "cecc-x-acknerr-request" POST request doesn’t check for port syntax. This can result in unauthorized execution of system commands with root privileges due to improper access control command injection.
In multiple products by Festo a remote unauthenticated attacker could use functions of an undocumented protocol which could lead to a complete loss of confidentiality, integrity and availability.
The Festo CECX-X-C1 Modular Master Controller with CoDeSys and CECX-X-M1 Modular Controller with CoDeSys and SoftMotion do not require authentication for connections to certain TCP ports, which allows remote attackers to (1) modify the configuration via a request to the debug service on port 4000 or (2) delete log entries via a request to the log service on port 4001.
The Festo CECX-X-C1 Modular Master Controller with CoDeSys and CECX-X-M1 Modular Controller with CoDeSys and SoftMotion provide an undocumented access method involving the FTP protocol, which could allow a remote attacker to execute arbitrary code or cause a denial of service (application crash) via unspecified vectors.