Where
AND
-Infinity
0
Severity
9.9
AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H

A vulnerability exists in the query validation of the MicroSCADA Pro/X SYS600 product. If exploited this could allow an authenticated attacker to inject code towards persistent data. Note that to successfully exploit this vulnerability an attacker must have a valid credential.

First published (updated )
Severity
9.9
Path Traversal
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H

The MicroSCADA Pro/X SYS600 product allows an authenticated user input to control or influence paths or file names that are used in filesystem operations. If exploited the vulnerability allows the attacker to access or modify system files or other files that are critical to the application.

First published (updated )
Severity
10
Buffer Overflow, Input Validation
CVSS:3.1/AV:L/AC:L/PR:H/UI:N/S:U/C:N/I:N/A:H

Improper Input Validation vulnerability in Hitachi Energy MicroSCADA X SYS600 while reading a specific configuration file causes a buffer-overflow that causes a failure to start the SYS600. The configuration file can only be accessed by an administrator access. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscadaxsys600:10::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10.1::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10.1.1::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10.2::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10.2.1::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10.3::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10.3.1:::::::

Remedy

Remediated in SYS600 10.4 Update to at least SYS600 version 10.4.
First published (updated )
Severity
8.2
AV:L/AC:L/PR:H/UI:N/S:C/C:H/I:H/A:H

An attacker with local access to machine where MicroSCADA X SYS600 is installed, could enable the session logging supporting the product and try to exploit a session hijacking of an already established session. By default, the session logging level is not enabled and only users with administrator rights can enable it.

First published (updated )
Severity
8.8
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H

Improper Authorization vulnerability exists in the Workplace X WebUI of the Hitachi Energy MicroSCADA X SYS600 allows an authenticated user to execute any MicroSCADA internal scripts irrespective of the authenticated user's role. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscadaxsys600:10::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10.1::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10.1.1::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10.2::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10.2.1::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10.3::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10.3.1:::::::

Remedy

Remediated in SYS600 10.4 Update to at least SYS600 version 10.4.
First published (updated )

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.
© 2026 SecAlerts Pty Ltd.
ABN: 70 645 966 203, ACN: 645 966 203