Where
AND
-Infinity
0
Severity
7.5
Input Validation
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Improper Input Validation vulnerability in the handling of a specially crafted IEC 61850 packet with a valid data item but with incorrect data type in the IEC 61850 OPC Server in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. The vulnerability may cause a denial-of-service on the IEC 61850 OPC Server part of the SYS600 product. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscadaprosys600:9.0::::::: cpe:2.3:a:hitachienergy:microscadaprosys600:9.1::::::: cpe:2.3:a:hitachienergy:microscadaprosys600:9.2::::::: cpe:2.3:a:hitachienergy:microscadaprosys600:9.3::::::: cpe:2.3:a:hitachienergy:microscadaprosys600:9.4::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10.1::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10.1.1::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10.2::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10.2.1::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10.3::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10.3.1:::::::

Remedy

Remediated in SYS600 10.4 For MicroSCADA Pro SYS600 - Upgrade to at least SYS600 version 10.4. For MicroSCADA X SYS600 - Update to at least SYS600 version 10.4.
First published (updated )
Severity
7.5
Input Validation
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Improper Input Validation vulnerability in the handling of a malformed IEC 104 TCP packet in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a denial-of-service if the affected connection is left open. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscadaprosys600:9.0::::::: cpe:2.3:a:hitachienergy:microscadaprosys600:9.1::::::: cpe:2.3:a:hitachienergy:microscadaprosys600:9.2::::::: cpe:2.3:a:hitachienergy:microscadaprosys600:9.3::::::: cpe:2.3:a:hitachienergy:microscadaprosys600:9.4::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10.1::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10.1.1::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10.2::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10.2.1::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10.3::::::: cpe:2.3:a:hitachienergy:microscadaxsys600:10.3.1:::::::

Remedy

Remediated in SYS600 10.4 For MicroSCADA Pro SYS600 - Upgrade to at least SYS600 version 10.4. For MicroSCADA X SYS600 - Update to at least SYS600 version 10.4.
First published (updated )

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.
© 2026 SecAlerts Pty Ltd.
ABN: 70 645 966 203, ACN: 645 966 203