Multiple stack-based buffer overflow vulnerabilities were found in Honeywell Experion PKS all versions prior to R400.6, all versions prior to R410.6, and all versions prior to R430.2 modules that could lead to possible remote code execution, dynamic memory corruption, or denial of service. Honeywell strongly encourages and recommends all customers running unsupported versions of EKPS prior to R400 to upgrade to a supported version.
An arbitrary memory write vulnerability exists in the dualonsrv.exe module in Honeywell Experion PKS R40x before R400.6, R41x before R410.6, and R43x before R430.2, that could lead to possible remote code execution or denial of service. Honeywell strongly encourages and recommends all customers running unsupported versions of EKPS prior to R400 to upgrade to a supported version.
Multiple heap-based buffer overflow vulnerabilities exist in Honeywell Experion PKS all versions prior to R400.6, all versions prior to R410.6, and all versions prior to R430.2 modules, which could lead to possible remote code execution or denial of service. Honeywell strongly encourages and recommends all customers running unsupported versions of EKPS prior to R400 to upgrade to a supported version.
A file inclusion vulnerability exists in the confd.exe module in Honeywell Experion PKS R40x before R400.6, R41x before R410.6, and R43x before R430.2, which could lead to accepting an arbitrary file into the function, and potential information disclosure or remote code execution. Honeywell strongly encourages and recommends all customers running unsupported versions of EKPS prior to R400 to upgrade to a supported version.
Honeywell Experion LX through 2022-05-06 has Missing Authentication for a Critical Function. According to FSCT-2022-0055, there is a Honeywell Experion LX Control Data Access (CDA) EpicMo protocol with unauthenticated functionality issue. The affected components are characterized as: Honeywell Control Data Access (CDA) EpicMo (55565/TCP). The potential impact is: Firmware manipulation, Denial of service. The Honeywell Experion LX Distributed Control System (DCS) utilizes the Control Data Access (CDA) EpicMo protocol (55565/TCP) for device diagnostics and maintenance purposes. This protocol does not have any authentication features, allowing any attacker capable of communicating with the ports in question to invoke (a subset of) desired functionality. There is no authentication functionality on the protocol in question. An attacker capable of invoking the protocols' functionalities could issue firmware download commands potentially allowing for firmware manipulation and reboot devices causing denial of service.
A directory traversal vulnerability exists in the confd.exe module in Honeywell Experion PKS R40x before R400.6, R41x before R410.6, and R43x before R430.2, which could lead to possible information disclosure. Honeywell strongly encourages and recommends all customers running unsupported versions of EKPS prior to R400 to upgrade to a supported version.
An issue was discovered in Honeywell Experion Process Knowledge System (PKS) platform: Experion PKS, Release 3xx and prior, Experion PKS, Release 400, Experion PKS, Release 410, Experion PKS, Release 430, and Experion PKS, Release 431. Experion PKS does not properly validate input. By sending a specially crafted packet, an attacker could cause the process to terminate. A successful exploit would prevent firmware uploads to the Series-C devices.