Incomplete List of Disallowed Inputs vulnerability in Mitsubishi Electric MC Works64 versions 4.00A (10.95.201.23) to 4.04E (10.95.210.01), ICONICS GENESIS64 versions 10.95.3 to 10.97, ICONICS Hyper Historian versions 10.95.3 to 10.97, ICONICS AnalytiX versions 10.95.3 to 10.97 and ICONICS MobileHMI versions 10.95.3 to 10.97 allows a remote unauthenticated attacker to bypass the authentication of MC Works64, GENESIS64, Hyper Historian, AnalytiX and MobileHMI, and gain unauthorized access to the products, by sending specially crafted WebSocket packets to FrameWorX server, one of the functions of the products.
Plaintext Storage of a Password vulnerability in Mitsubishi Electric MC Works64 versions 4.04E (10.95.210.01) and prior and ICONICS GENESIS64 versions 10.90 to 10.97 allows a local authenticated attacker to gain authentication information and to access the database illegally. This is because when configuration information of GridWorX, a database linkage function of GENESIS64 and MC Works64, is exported to a CSV file, the authentication information is saved in plaintext, and an attacker who can access this CSV file can gain the authentication information.
Cross-site Scripting vulnerability in Mitsubishi Electric MC Works64 versions 4.04E (10.95.210.01) and prior and ICONICS MobileHMI versions 10.96.2 and prior allows a remote unauthenticated attacker to gain authentication information of an MC Works64 or MobileHMI and perform any operation using the acquired authentication information, by injecting a malicious script in the URL of a monitoring screen delivered from the MC Works64 server or MobileHMI server to an application for mobile devices and leading a legitimate user to access this URL.