Where
-Infinity
0
Severity
7.5
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N

Insufficient verification of data authenticity issue exists in NJ Series CPU Unit all versions and NX Series CPU Unit all versions. If a user program in the affected product is altered, the product may not be able to detect the alteration.

First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

FINS (Factory Interface Network Service) is a message communication protocol, which is designed to be used in closed FA (Factory Automation) networks, and is used in FA networks composed of OMRON products. Multiple OMRON products that implement FINS protocol contain following security issues -- (1)Plaintext communication, and (2)No authentication required. When FINS messages are intercepted, the contents may be retrieved. When arbitrary FINS messages are injected, any commands may be executed on, or the system information may be retrieved from, the affected device. Affected products and versions are as follows: SYSMAC CS-series CPU Units, all versions, SYSMAC CJ-series CPU Units, all versions, SYSMAC CP-series CPU Units, all versions, SYSMAC NJ-series CPU Units, all versions, SYSMAC NX1P-series CPU Units, all versions, SYSMAC NX102-series CPU Units, all versions, and SYSMAC NX7 Database Connection CPU Units (Ver.1.16 or later)

First published (updated )
Severity
9.4
CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H

Use of hard-coded credentials vulnerability exists in Machine automation controller NJ series all models V 1.48 and earlier, Machine automation controller NX7 series all models V1.28 and earlier, Machine automation controller NX1 series all models V1.48 and earlier, Automation software 'Sysmac Studio' all models V1.49 and earlier, and Programmable Terminal (PT) NA series NA5-15W/NA5-12W/NA5-9W/NA5-7W models Runtime V1.15 and earlier, which may allow a remote attacker who successfully obtained the user credentials by analyzing the affected product to access the controller.

First published (updated )
Severity
8.3
CVSS:3.1/AV:A/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H

Authentication bypass by capture-replay vulnerability exists in Machine automation controller NX7 series all models V1.28 and earlier, Machine automation controller NX1 series all models V1.48 and earlier, and Machine automation controller NJ series all models V 1.48 and earlier, which may allow an adjacent attacker who can analyze the communication between the controller and the specific software used by OMRON internally to cause a denial-of-service (DoS) condition or execute a malicious program.

First published (updated )
Severity
8.1
CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H

Authentication bypass by capture-replay vulnerability exists in Machine automation controller NJ series all models V 1.48 and earlier, Machine automation controller NX7 series all models V1.28 and earlier, Machine automation controller NX1 series all models V1.48 and earlier, Automation software 'Sysmac Studio' all models V1.49 and earlier, and Programmable Terminal (PT) NA series NA5-15W/NA5-12W/NA5-9W/NA5-7W models Runtime V1.15 and earlier, which may allow a remote attacker who can analyze the communication between the affected controller and automation software 'Sysmac Studio' and/or a Programmable Terminal (PT) to access the controller.

First published (updated )

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.
© 2026 SecAlerts Pty Ltd.
ABN: 70 645 966 203, ACN: 645 966 203