Where
-Infinity
0
Severity
7.5
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N

Download of Code Without Integrity Check vulnerability in PHOENIX CONTACT classic line PLCs allows an unauthenticated remote attacker to modify some or all applications on a PLC.

First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Incorrect Permission Assignment for Critical Resource vulnerability in multiple products of the PHOENIX CONTACT classic line allow an remote unauthenticated attacker to gain full access of the affected device.

First published (updated )
Severity
7.8
AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H

Phoenix Contact Classic Automation Worx Software Suite in Version 1.87 and below is affected by a remote code execution vulnerability. Manipulated PC Worx or Config+ projects could lead to a remote code execution when unallocated memory is freed because of incompletely initialized data. The attacker needs to get access to an original bus configuration file (.bcp) to be able to manipulate data inside. After manipulation the attacker needs to exchange the original file by the manipulated one on the application programming workstation. Availability, integrity, or confidentiality of an application programming workstation might be compromised by attacks using these vulnerabilities. Automated systems in operation which were programmed with one of the above-mentioned products are not affected.

1 / 2

Remedy

Temporary Fix / Mitigation We strongly recommend customers to exchange project files only using secure file exchange services. Project files should not be exchanged via unencrypted email. Remediation With the next version of Automationworx Software Suite the affected data will be initialized completely and thereby freeing of unallocated memory will be prevented.
First published (updated )
Severity
7.8
AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H

An issue was discovered in PHOENIX CONTACT PC Worx through 1.86, PC Worx Express through 1.86, and Config+ through 1.86. A manipulated PC Worx or Config+ project file could lead to an Out-of-bounds Read and remote code execution. The attacker needs to get access to an original PC Worx or Config+ project to be able to manipulate data inside. After manipulation, the attacker needs to exchange the original files with the manipulated ones on the application programming workstation.

1 / 3
First published (updated )

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.