Where
-Infinity
0
Severity
7
EPSS
0.03%
CVSS:4.0/AV:P/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

A code execution security issue exists in the affected product. An attacker with physical access could abuse the maintenance menu of the controller with a crafted payload. The security issue can result in arbitrary code execution.

Remedy

Best security practices should be applied.
First published (updated )
Severity
8.6
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H

A malformed Class 3 common industrial protocol message with a cached connection can cause a denial-of-service condition in Rockwell Automation Logix Controllers, resulting in a major nonrecoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online.

Remedy

Rockwell Automation recommends users update to the latest firmware version to mitigate this vulnerability. Users are directed towards the risk mitigation provided below and are encouraged (where possible) to combine these with the general security guidelines below to employ multiple strategies simultaneously. Users should go to Rockwell Automation's Product Compatibility & Download Center to download the latest firmware. CompactLogix 5380, Compact GuardLogix 5380, CompactLogix 5480, ControlLogix 5580, GuardLogix 5580: Upgrade to v33.011 firmware CompactLogix 5370, Compact GuardLogix 5370, ControlLogix 5570, GuardLogix 5570: Upgrade to v34.011 firmware Please see Rockwell Automation’s security advisory PN1596 for more information. https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1135559
First published (updated )
Severity
8.6
Input Validation
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

An unauthorized user could use a specially crafted sequence of Ethernet/IP messages, combined with heavy traffic loading to cause a denial-of-service condition in Rockwell Automation Logix controllers resulting in a major non-recoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online and continue normal operation.

1 / 2
Source: MITRE
First published (updated )
Severity
8.7
EPSS
0.04%
Input Validation
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

CVE-2024-7515 IMPACT

A denial-of-service vulnerability exists in the affected products. A malformed PTP management packet can cause a major nonrecoverable fault in the controller.

Remedy

Upgrade to:  v36.011, v35.013, v34.014
First published (updated )
Severity
8.7
EPSS
0.04%
Input Validation
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

CVE-2024-7507 IMPACT

A denial-of-service vulnerability exists in the affected products. This vulnerability occurs when a malformed PCCC message is received, causing a fault in the controller.

Remedy

Upgrade to:  v36.011, v35.013, v34.014
First published (updated )
Severity
8.6
EPSS
0.04%
Input Validation
AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H

A specific malformed fragmented packet type (fragmented packets may be generated automatically by devices that send large amounts of data) can cause a major nonrecoverable fault (MNRF) Rockwell Automation's ControlLogix 5580, Guard Logix 5580, CompactLogix 5380, and 1756-EN4TR. If exploited, the affected product will become unavailable and require a manual restart to recover it. Additionally, an MNRF could result in a loss of view and/or control of connected devices.

Remedy

Affected Product         First Known in Firmware Revision         Corrected in Firmware Revision         ControlLogix® 5580         V35.011         V35.013, V36.011         GuardLogix 5580         V35.011         V35.013, V36.011         CompactLogix 5380         V35.011         V35.013, V36.011         1756-EN4TR         V5.001         V6.001     Users using the affected software and who are not able to upgrade to one of the corrected versions are encouraged to apply security best practices, where possible.   * Security Best Practices https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight  
First published (updated )
Severity
8.7
EPSS
0.04%
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

Due to a memory leak, a denial-of-service vulnerability exists in the Rockwell Automation affected products. A malicious actor could exploit this vulnerability by performing multiple actions on certain web pages of the product causing the affected products to become fully unavailable and require a power cycle to recover.

Remedy

Affected Product      First Known in firmware Revision         Corrected in Firmware Revision         CompactLogix 5380 controllers         v33.011 <                     * v33.015 and later for versions 33     * v34.011 and later               Compact GuardLogix® 5380 controllers         v33.011<         CompactLogix 5480 controllers         v33.011<         ControlLogix 5580 controllers         v33.011<         GuardLogix 5580 controllers         v33.011<         1756-EN4TR         v3.002         * 4.001 and later     Mitigations and Workarounds Customers using the affected versions are encouraged to upgrade to corrected firmware versions. We also strongly encourage customers to implement our suggested security best practices to minimize the risk of the vulnerability. * Security Best Practices https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight
First published (updated )
Severity
8.7
Input Validation
AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

CVE 2021-22681 https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.PN1550.html  and send a specially crafted CIP message to the device. If exploited, a threat actor could help prevent access to the legitimate user and end connections to connected devices including the workstation. To recover the controllers, a download is required which ends any process that the controller is running.

Remedy

AFFECTED PRODUCTS AND SOLUTION Affected Product First Known in firmware revisionCorrected in firmware revisionControlLogix® 5580V28.011V33.017, V34.014, V35.013, V36.011 and laterControlLogix® 5580 ProcessV33.011V33.017, V34.014, V35.013, V36.011 and laterGuardLogix 5580V31.011 V33.017, V34.014, V35.013, V36.011 and laterCompactLogix 5380V28.011 V33.017, V34.014, V35.013, V36.011 and laterCompact GuardLogix 5380 SIL 2V31.011V33.017, V34.014, V35.013, V36.011 and laterCompact GuardLogix 5380 SIL 3V32.013V33.017, V34.014, V35.013, V36.011 and laterCompactLogix 5480V32.011V33.017, V34.014, V35.013, V36.011 and laterFactoryTalk® Logix Echo V33.011V34.014, V35.013, V36.011 and later
First published (updated )
Severity
8.7
Input Validation
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

A denial-of-service vulnerability exists in the Rockwell Automation affected products when specially crafted packets are sent to the CIP Security Object. If exploited the device will become unavailable and require a factory reset to recover.

Remedy

Affected Family         First Known in Software/Firmware Version         Corrected in Software/Firmware Version         CompactLogix 5380               v.32 .011         v33.017, v34.014, v35.013, v36.011 and later         CompactLogix 5380 Process         v.33.011         v33.017, v34.014, v35.013, v36.011 and later         Compact GuardLogix 5380 SIL 2         v.32.013         v33.017, v34.014, v35.013, v36.011 and later         Compact GuardLogix 5380 SIL 3         v.32.011         v33.017, v34.014, v35.013, v36.011 and later         CompactLogix 5480         v.32.011         v33.017, v34.014, v35.013, v36.011 and later         ControlLogix® 5580         v.32.011         v33.017, v34.014, v35.013, v36.011 and later         ControlLogix® 5580 Process         v.33.011         v33.017, v34.014, v35.013, v36.011 and later         GuardLogix 5580         v.32.011         v33.017, v34.014, v35.013, v36.011 and later         1756-EN4         v2.001         v6.001 and later       Mitigations and Workarounds Customers who are unable to upgrade to the corrected software versions are encouraged to apply the following risk mitigations. * Users who do not wish to use CIP security can disable the feature per device. See "Disable CIP Security" in Chapter 2 of "CIP Security with Rockwell Automation Products" (publication SECURE-AT001) For information on how to mitigate Security Risks on industrial automation control systems, we encourage customers to implement our suggested security best practices https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight  to minimize the risk of the vulnerability. Customers can use Stakeholder-Specific Vulnerability Categorization https://www.cisa.gov/stakeholder-specific-vulnerability-categorization-ssvc  to generate more environment-specific prioritization.
First published (updated )
Severity
7.7
Code Injection
CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H

Rockwell Automation Studio 5000 Logix Designer (all versions) are vulnerable when an attacker who achieves administrator access on a workstation running Studio 5000 Logix Designer could inject controller code undetectable to a user.

First published (updated )
Severity
10
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

An attacker with the ability to modify a user program may change user program code on some ControlLogix, CompactLogix, and GuardLogix Control systems. Studio 5000 Logix Designer writes user-readable program code to a separate location than the executed compiled code, allowing an attacker to change one and not the other.

Remedy

The following mitigations should be applied for ControlLogix 5560, ControlLogix 5570, ControlLogix 5580 series, GuardLogix 5570, GuardLogix 5580, GuardLogix 5380, CompactLogix, CompactLogix 5380 devices: Risk Mitigation A: Recompile and download user program code (i.e., acd). Put controller mode switch into Run position. If keeping controller mode switch in Run is impractical, use the following mitigation: Recompile and download user program code (i.e., acd). Monitor controller change log for any unexpected modifications or anomalous activity. Utilize the Controller Log feature. Utilize Change Detection in the Logix Designer Application. If available, use the functionality in FactoryTalk AssetCenter software to detect changes. Risk Mitigation B: Implement CIP Security to help prevent unauthorized connections when properly deployed. Supported controllers and communications modules include: ControlLogix 5580 processors using on-board EtherNet/IP port. GuardLogix 5580 processors using on-board EtherNet/IP port. ControlLogix 5580 processors operating in High Availability (HA) configurations using 1756-EN4TR ControlLogix 5560, ControlLogix 5570, ControlLogix 5580, GuardLogix 5570 and GuardLogix 5580 can use a 1756-EN4TR ControlLogix EtherNet/IP module. If using a 1756-EN2T, then replace with a 1756-EN4TR CompactLogix 5380 using on-board EtherNet/IP port. CompactLogix GuardLogix 5380 using on-board EtherNet/IP port. The following mitigations should be applied for 1768 CompactLogix, 1769 CompactLogix, CompactLogix 5370, and CompactLogix 5480 devices: Recompile and download user program code (i.e., acd). Put controller mode switch into Run position. If keeping controller mode switch in Run is impractical, then use the following mitigation: Recompile and download user program code (i.e., acd). Monitor controller change log for any unexpected modifications or anomalous activity. Use the Controller Log feature. Use Change Detection in the Logix Designer application. If available, use the functionality in FactoryTalk AssetCenter to detect changes.
First published (updated )

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.