Where
-Infinity
0
Severity
8.6
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H

A malformed Class 3 common industrial protocol message with a cached connection can cause a denial-of-service condition in Rockwell Automation Logix Controllers, resulting in a major nonrecoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online.

Remedy

Rockwell Automation recommends users update to the latest firmware version to mitigate this vulnerability. Users are directed towards the risk mitigation provided below and are encouraged (where possible) to combine these with the general security guidelines below to employ multiple strategies simultaneously. Users should go to Rockwell Automation's Product Compatibility & Download Center to download the latest firmware. CompactLogix 5380, Compact GuardLogix 5380, CompactLogix 5480, ControlLogix 5580, GuardLogix 5580: Upgrade to v33.011 firmware CompactLogix 5370, Compact GuardLogix 5370, ControlLogix 5570, GuardLogix 5570: Upgrade to v34.011 firmware Please see Rockwell Automation’s security advisory PN1596 for more information. https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1135559
First published (updated )
Severity
8.6
Input Validation, Path Traversal
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H

The connection establishment algorithm found in Rockwell Automation CompactLogix 5370 and ControlLogix 5570 versions 33 and prior does not sufficiently manage its control flow during execution, creating an infinite loop. This may allow an attacker to send specially crafted CIP packet requests to a controller, which may cause denial-of-service conditions in communications with other products.

Remedy

Rockwell Automation recommends affected users apply firmware v33.011 or later. For more information see the Rockwell Automation advisory (login required).
First published (updated )
Severity
8.6
Input Validation
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

A vulnerability exists in the Rockwell Automation controllers that allows a malformed CIP request to cause a major non-recoverable fault (MNRF) and a denial-of-service condition (DOS).

First published (updated )
Severity
10
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

An attacker with the ability to modify a user program may change user program code on some ControlLogix, CompactLogix, and GuardLogix Control systems. Studio 5000 Logix Designer writes user-readable program code to a separate location than the executed compiled code, allowing an attacker to change one and not the other.

Remedy

The following mitigations should be applied for ControlLogix 5560, ControlLogix 5570, ControlLogix 5580 series, GuardLogix 5570, GuardLogix 5580, GuardLogix 5380, CompactLogix, CompactLogix 5380 devices: Risk Mitigation A: Recompile and download user program code (i.e., acd). Put controller mode switch into Run position. If keeping controller mode switch in Run is impractical, use the following mitigation: Recompile and download user program code (i.e., acd). Monitor controller change log for any unexpected modifications or anomalous activity. Utilize the Controller Log feature. Utilize Change Detection in the Logix Designer Application. If available, use the functionality in FactoryTalk AssetCenter software to detect changes. Risk Mitigation B: Implement CIP Security to help prevent unauthorized connections when properly deployed. Supported controllers and communications modules include: ControlLogix 5580 processors using on-board EtherNet/IP port. GuardLogix 5580 processors using on-board EtherNet/IP port. ControlLogix 5580 processors operating in High Availability (HA) configurations using 1756-EN4TR ControlLogix 5560, ControlLogix 5570, ControlLogix 5580, GuardLogix 5570 and GuardLogix 5580 can use a 1756-EN4TR ControlLogix EtherNet/IP module. If using a 1756-EN2T, then replace with a 1756-EN4TR CompactLogix 5380 using on-board EtherNet/IP port. CompactLogix GuardLogix 5380 using on-board EtherNet/IP port. The following mitigations should be applied for 1768 CompactLogix, 1769 CompactLogix, CompactLogix 5370, and CompactLogix 5480 devices: Recompile and download user program code (i.e., acd). Put controller mode switch into Run position. If keeping controller mode switch in Run is impractical, then use the following mitigation: Recompile and download user program code (i.e., acd). Monitor controller change log for any unexpected modifications or anomalous activity. Use the Controller Log feature. Use Change Detection in the Logix Designer application. If available, use the functionality in FactoryTalk AssetCenter to detect changes.
First published (updated )

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.