Where
-Infinity
0
Severity
8.1
AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H

Due to inadequate code logic, a previously unauthenticated threat actor could potentially obtain a local Windows OS user token through the FactoryTalk® Services Platform web service and then use the token to log in into FactoryTalk® Services Platform . This vulnerability can only be exploited if the authorized user did not previously log in into the FactoryTalk® Services Platform web service.

Remedy

* Install the respective FactoryTalk Services Version https://compatibility.rockwellautomation.com/Pages/MultiProductCompareSelections.aspx  that remediates the issue. * QA43240 - Recommended Security Guidelines from Rockwell Automation https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012
First published (updated )
Severity
8.8
Input Validation
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

In Rockwell Automation FactoryTalk Services Platform, all versions, the redundancy host service (RdcyHost.exe) does not validate supplied identifiers, which could allow an unauthenticated, adjacent attacker to execute remote COM objects with elevated privileges.

First published (updated )
Severity
6.9
AV:L/AC:M/Au:N/C:C/I:C/A:C

Untrusted search path vulnerability in the Clean Utility application in Rockwell Automation FactoryTalk Services Platform before 2.71.00 and FactoryTalk View Studio 8.00.00 and earlier allows local users to gain privileges via a Trojan horse DLL in an unspecified directory.

First published (updated )
Severity
7.8
Integer Overflow
AV:N/AC:L/Au:N/C:N/I:N/A:C

Integer overflow in RNADiagnostics.dll in Rockwell Automation FactoryTalk Services Platform (FTSP) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 allows remote attackers to cause a denial of service (service outage or RNADiagReceiver.exe daemon crash) via UDP data that specifies a large integer value.

First published (updated )
Severity
8.8
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H

Rockwell Automation FactoryTalk Services Platform v6.11 and earlier, if FactoryTalk Security is enabled and deployed contains a vulnerability that may allow a remote, authenticated attacker to bypass FactoryTalk Security policies based on the computer name. If successfully exploited, this may allow an attacker to have the same privileges as if they were logged on to the client machine.

Remedy

Rockwell Automation encourages those using the affected software to update to FactoryTalk Services Platform v6.20 or later to address the associated risk. Please see the Rockwell Automation publication regarding this issue for more information.
First published (updated )
Severity
10
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H

In Rockwell Automation FactoryTalk Services Platform Versions 6.10.00 and 6.11.00, there is an issue with the implementation of the SHA-256 hashing algorithm with FactoryTalk Services Platform that prevents the user password from being hashed properly.

First published (updated )
Severity
8.4
XEE
CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:H

A local, authenticated attacker could use an XML External Entity (XXE) attack to exploit weakly configured XML files to access local or remote content. A successful exploit could potentially cause a denial-of-service condition and allow the attacker to arbitrarily read any local file via system-level services.

First published (updated )

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.
© 2026 SecAlerts Pty Ltd.
ABN: 70 645 966 203, ACN: 645 966 203