Where
-Infinity
0
Severity
9.3
Code Injection
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

A denial-of-service and possible remote code execution vulnerability exists in the Rockwell Automation Power Monitor 1000. The vulnerability results in corruption of the heap memory which may compromise the integrity of the system, potentially allowing for remote code execution or a denial-of-service attack.

Remedy

Affected Products Affected firmware revision Corrected in firmware revision PM1k 1408-BC3A-485 <4.020 4.020 PM1k 1408-BC3A-ENT <4.020 4.020 PM1k 1408-TS3A-485 <4.020 4.020 PM1k 1408-TS3A-ENT <4.020 4.020 PM1k 1408-EM3A-485 <4.020 4.020 PM1k 1408-EM3A-ENT <4.020 4.020 PM1k 1408-TR1A-485 <4.020 4.020 PM1k 1408-TR2A-485 <4.020 4.020 PM1k 1408-EM1A-485 <4.020 4.020 PM1k 1408-EM2A-485 <4.020 4.020 PM1k 1408-TR1A-ENT <4.020 4.020 PM1k 1408-TR2A-ENT <4.020 4.020 PM1k 1408-EM1A-ENT <4.020 4.020 PM1k 1408-EM2A-ENT <4.020 4.020 Mitigations and Workarounds Users using the affected software, who are not able to upgrade to one of the corrected versions, are encouraged to apply security best practices, where possible.   ·       Security Best Practices https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight
First published (updated )
Severity
9.3
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

A denial-of-service vulnerability exists in the Rockwell Automation Power Monitor 1000. The vulnerability results in a buffer-overflow, potentially causing denial-of-service.

Remedy

Affected Products Affected firmware revision Corrected in firmware revision PM1k 1408-BC3A-485 <4.020 4.020 PM1k 1408-BC3A-ENT <4.020 4.020 PM1k 1408-TS3A-485 <4.020 4.020 PM1k 1408-TS3A-ENT <4.020 4.020 PM1k 1408-EM3A-485 <4.020 4.020 PM1k 1408-EM3A-ENT <4.020 4.020 PM1k 1408-TR1A-485 <4.020 4.020 PM1k 1408-TR2A-485 <4.020 4.020 PM1k 1408-EM1A-485 <4.020 4.020 PM1k 1408-EM2A-485 <4.020 4.020 PM1k 1408-TR1A-ENT <4.020 4.020 PM1k 1408-TR2A-ENT <4.020 4.020 PM1k 1408-EM1A-ENT <4.020 4.020 PM1k 1408-EM2A-ENT <4.020 4.020 Mitigations and Workarounds Users using the affected software, who are not able to upgrade to one of the corrected versions, are encouraged to apply security best practices, where possible.   ·       Security Best Practices https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight
First published (updated )
Severity
9.3
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

A device takeover vulnerability exists in the Rockwell Automation Power Monitor 1000. This vulnerability allows configuration of a new Policyholder user without any authentication via API. Policyholder user is the most privileged user that can perform edit operations, creating admin users and performing factory reset.

Remedy

Affected Products Affected firmware revision Corrected in firmware revision PM1k 1408-BC3A-485 <4.020 4.020 PM1k 1408-BC3A-ENT <4.020 4.020 PM1k 1408-TS3A-485 <4.020 4.020 PM1k 1408-TS3A-ENT <4.020 4.020 PM1k 1408-EM3A-485 <4.020 4.020 PM1k 1408-EM3A-ENT <4.020 4.020 PM1k 1408-TR1A-485 <4.020 4.020 PM1k 1408-TR2A-485 <4.020 4.020 PM1k 1408-EM1A-485 <4.020 4.020 PM1k 1408-EM2A-485 <4.020 4.020 PM1k 1408-TR1A-ENT <4.020 4.020 PM1k 1408-TR2A-ENT <4.020 4.020 PM1k 1408-EM1A-ENT <4.020 4.020 PM1k 1408-EM2A-ENT <4.020 4.020 Mitigations and Workarounds Users using the affected software, who are not able to upgrade to one of the corrected versions, are encouraged to apply security best practices, where possible.   ·       Security Best Practices https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight
First published (updated )
Severity
8.8
XSS
AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H

The Rockwell Automation PowerMonitor 1000 contains stored cross-site scripting vulnerabilities within the web page of the product.  The vulnerable pages do not require privileges to access and can be injected with code by an attacker which could be used to leverage an attack on an authenticated user resulting in remote code execution and potentially the complete loss of confidentiality, integrity, and availability of the product.

Remedy

* Customers should upgrade to V4.019 https://compatibility.rockwellautomation.com/Pages/MultiProductCompareSelections.aspx  which mitigates this issue
First published (updated )
Severity
6.1
XSS
CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N

Rockwell Automation Allen-Bradley PowerMonitor 1000 all versions. A remote attacker could inject arbitrary code into a targeted userâ??s web browser to gain access to the affected device.

1 / 2
First published (updated )
Severity
8.1
CVSS:3.0/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H

An issue was discovered in Rockwell Automation Allen-Bradley PowerMonitor 1000. An unauthenticated user can add/edit/remove administrators because access control is implemented on the client side via a disabled attribute for a BUTTON element.

First published (updated )

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.
© 2026 SecAlerts Pty Ltd.
ABN: 70 645 966 203, ACN: 645 966 203