Where
-Infinity
0
Severity
10
Input Validation
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is en-abled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the receiving RTU500 CMU to reboot. The vulnerability is caused by the validation error in the length information carried in MBAP header in the HCI Modbus TCP function.

1 / 2
Source: MITRE

Remedy

Remediation available, see the advisory for details.
First published (updated )
Severity
10
OS Command Injection, Command Injection
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Versions of INEA ME RTU firmware prior to 3.36 are vulnerable to OS command injection, which could allow an attacker to remotely execute arbitrary code.

First published (updated )
Severity
9.9
OS Command Injection, Command Injection
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Versions of INEA ME RTU firmware 3.36b and prior are vulnerable to operating system (OS) command injection, which could allow remote code execution.

Remedy

INEA recommends users to upgrade ME RTU to firmware version 3.37 https://www.inea.si/en/telemetrija-in-m2m-produkti/mertu-en/ .
First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Versions of INEA ME RTU firmware 3.36b and prior do not require authentication to the "root" account on the host system of the device. This could allow an attacker to obtain admin-level access to the host system.

Remedy

INEA recommends users to upgrade ME RTU to firmware version 3.37 https://www.inea.si/en/telemetrija-in-m2m-produkti/mertu-en/ .
First published (updated )
Severity
8.7
AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

A vulnerability exists in RTU IEC 61850 client and server functionality that could impact the availability if renegotiation of an open IEC61850 TLS connection takes place in specific timing situations, when IEC61850 communication is active.

Precondition is that IEC61850 as client or server are configured using TLS on RTU500 device. It affects the CMU the IEC61850 stack is configured on.

First published (updated )
Severity
6.9
EPSS
0.17%
Null Pointer Dereference
CVSS:4.0/AV:A/AC:L/AT:N/PR:L/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

IEC 60870-5-104 used in bidirectional mode in RTU500 is vulnerable for a NULL pointer dereferencing, if a specially crafted sequence of messages is sent for a certain time, causing Denial of Service impact. Product is only affected if IEC 60870-5-104 functionality in bidirectional mode (BCI) is configured.

First published (updated )
Severity
5.9
Null Pointer Dereference
AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H

RTU500 has a vulnerability, where high-load scenarios, such as sending GI requests at short intervals, may cause a NULL pointer dereference in the last entry of the enhanced message queue. This can cause a BCIIEC104 fatal write error, resulting in connection interruption and restart, and ultimately a denial of service for bidirectional IEC 60870-5-104 communication.

First published (updated )

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.