Where
-Infinity
0
Severity
8.7
Integer Overflow
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

The OPC UA implementations (ANSI C and C++) in affected products contain an integer overflow vulnerability that could cause the application to run into an infinite loop during certificate validation. This could allow an unauthenticated remote attacker to create a denial of service condition by sending a specially crafted certificate.

First published (updated )
Severity
7.5
CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:N/A:H

Affected devices don't process correctly certain special crafted packets sent to port 102/tcp, which could allow an attacker to cause a denial of service in the device.

First published (updated )
Severity
7.5
Input Validation
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Affected devices don't process correctly certain special crafted packets sent to port 102/tcp, which could allow an attacker to cause a denial of service in the device.

First published (updated )
Severity
7.5
Input Validation
CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:L/A:H

Affected devices don't process correctly certain special crafted packets sent to port 102/tcp, which could allow an attacker to cause a denial of service in the device.

First published (updated )
Severity
7.5
Input Validation
CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:N/A:H

Affected devices don't process correctly certain special crafted packets sent to port 102/tcp, which could allow an attacker to cause a denial of service in the device.

First published (updated )
Severity
6.5
CSRF
CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N

The login endpoint /FormLogin in affected web services does not apply proper origin checking. This could allow authenticated remote attackers to track the activities of other users via a login cross-site request forgery attack.

First published (updated )
Severity
7.5
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

A vulnerability has been identified in SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packets over port 102/tcp. A restart of the affected device is needed to restore normal operations.

First published (updated )
Severity
7.5
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V21.9), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 Ready4Linux (All versions), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.5.0), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.9.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions < V21.9), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions < V4.0), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packet over port 102/tcp. A restart of the affected device is needed to restore normal operations.

First published (updated )
Severity
7.5
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

A vulnerability has been identified in SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packets over port 102/tcp. A restart of the affected device is needed to restore normal operations.

First published (updated )
Severity
7.5
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N

A vulnerability has been identified in SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (V4.5.0). Affected devices fail to authenticate against configured passwords when provisioned using TIA Portal V13. This could allow an attacker using TIA Portal V13 or later versions to bypass authentication and download arbitrary programs to the PLC. The vulnerability does not occur when TIA Portal V13 SP1 or any later version was used to provision the device.

First published (updated )
Severity
7.5
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

A vulnerability has been identified in SIMATIC ET 200pro IM154-8 PN/DP CPU (All versions < V3.X.17), SIMATIC ET 200pro IM154-8F PN/DP CPU (All versions < V3.X.17), SIMATIC ET 200pro IM154-8FX PN/DP CPU (All versions < V3.X.17), SIMATIC ET 200S IM151-8 PN/DP CPU (All versions < V3.X.17), SIMATIC ET 200S IM151-8F PN/DP CPU (All versions < V3.X.17), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.1), SIMATIC S7-300 CPU 314C-2 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 315-2 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 315F-2 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 315T-3 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 317-2 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 317F-2 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 317T-3 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 317TF-3 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 319-3 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 319F-3 PN/DP (All versions < V3.X.17), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants) (All versions), SIMATIC WinAC RTX 2010 (All versions), SIMATIC WinAC RTX F 2010 (All versions), SIPLUS ET 200S IM151-8 PN/DP CPU (All versions < V3.X.17), SIPLUS ET 200S IM151-8F PN/DP CPU (All versions < V3.X.17), SIPLUS S7-300 CPU 314C-2 PN/DP (All versions < V3.X.17), SIPLUS S7-300 CPU 315-2 PN/DP (All versions < V3.X.17), SIPLUS S7-300 CPU 315F-2 PN/DP (All versions < V3.X.17), SIPLUS S7-300 CPU 317-2 PN/DP (All versions < V3.X.17), SIPLUS S7-300 CPU 317F-2 PN/DP (All versions < V3.X.17). Affected devices contain a vulnerability that could cause a denial of service condition of the web server by sending specially crafted HTTP requests to ports 80/tcp and 443/tcp. Beyond the web service, no other functions or interfaces are affected by the denial of service condition.

1 / 2
Source: MITRE
First published (updated )
Severity
7.5
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

A vulnerability has been identified in SIMATIC S7-400 CPU 414-3 PN/DP V7, SIMATIC S7-400 CPU 414F-3 PN/DP V7, SIMATIC S7-400 CPU 416-3 PN/DP V7, SIMATIC S7-400 CPU 416F-3 PN/DP V7, Development/Evaluation Kits for PROFINET IO: DK Standard Ethernet Controller, Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200, Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200P, SIMATIC CFU PA, SIMATIC ET 200pro IM154-8 PN/DP CPU, SIMATIC ET 200pro IM154-8F PN/DP CPU, SIMATIC ET 200pro IM154-8FX PN/DP CPU, SIMATIC ET 200S IM151-8 PN/DP CPU, SIMATIC ET 200S IM151-8F PN/DP CPU, SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants), SIMATIC ET200AL, SIMATIC ET200ecoPN, 16DI, DC24V, 8xM12, SIMATIC ET200ecoPN, 16DO DC24V/1,3A, 8xM12, SIMATIC ET200ecoPN, 4AO U/I 4xM12, SIMATIC ET200ecoPN, 8 DIO, DC24V/1,3A, 8xM12, SIMATIC ET200ecoPN, 8 DO, DC24V/2A, 8xM12, SIMATIC ET200ecoPN, 8AI RTD/TC 8xM12, SIMATIC ET200ecoPN, 8AI; 4 U/I; 4 RTD/TC 8xM12, SIMATIC ET200ecoPN, 8DI, DC24V, 4xM12, SIMATIC ET200ecoPN, 8DI, DC24V, 8xM12, SIMATIC ET200ecoPN, 8DO, DC24V/0,5A, 4xM12, SIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 4xM12, SIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 8xM12, SIMATIC ET200ecoPN: IO-Link Master, SIMATIC ET200M (incl. SIPLUS variants), SIMATIC ET200MP IM155-5 PN BA (incl. SIPLUS variants), SIMATIC ET200MP IM155-5 PN HF (incl. SIPLUS variants), SIMATIC ET200MP IM155-5 PN ST (incl. SIPLUS variants), SIMATIC ET200pro, SIMATIC ET200S (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN BA (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN HA (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN HF (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN HS (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN ST (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN/2 HF (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN/3 HF (incl. SIPLUS variants), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (incl. SIPLUS variants), SIMATIC HMI Comfort Panels 4" - 22" (incl. SIPLUS variants), SIMATIC HMI KTP Mobile Panels, SIMATIC PN/PN Coupler, SIMATIC PROFINET Driver, SIMATIC S7-1200 CPU family (incl. SIPLUS variants), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants), SIMATIC S7-1500 Software Controller, SIMATIC S7-300 CPU 314C-2 PN/DP, SIMATIC S7-300 CPU 315-2 PN/DP, SIMATIC S7-300 CPU 315F-2 PN/DP, SIMATIC S7-300 CPU 315T-3 PN/DP, SIMATIC S7-300 CPU 317-2 PN/DP, SIMATIC S7-300 CPU 317F-2 PN/DP, SIMATIC S7-300 CPU 317T-3 PN/DP, SIMATIC S7-300 CPU 317TF-3 PN/DP, SIMATIC S7-300 CPU 319-3 PN/DP, SIMATIC S7-300 CPU 319F-3 PN/DP, SIMATIC S7-400 CPU 412-2 PN V7, SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants), SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants), SIMATIC TDC CP51M1, SIMATIC TDC CPU555, SIMATIC WinAC RTX 2010, SIMATIC WinAC RTX F 2010, SINAMICS DCM, SINAMICS DCP, SINAMICS G110M V4.7 PN Control Unit, SINAMICS G120 V4.7 PN Control Unit (incl. SIPLUS variants), SINAMICS G130 V4.7 Control Unit, SINAMICS G150 Control Unit, SINAMICS GH150 V4.7 Control Unit, SINAMICS GL150 V4.7 Control Unit, SINAMICS GM150 V4.7 Control Unit, SINAMICS S110 Control Unit, SINAMICS S120 V4.7 Control Unit (incl. SIPLUS variants), SINAMICS S150 Control Unit, SINAMICS SL150 V4.7 Control Unit, SINAMICS SM120 V4.7 Control Unit, SINUMERIK 828D, SINUMERIK 840D sl, SIPLUS ET 200S IM151-8 PN/DP CPU, SIPLUS ET 200S IM151-8F PN/DP CPU, SIPLUS NET PN/PN Coupler, SIPLUS S7-300 CPU 314C-2 PN/DP, SIPLUS S7-300 CPU 315-2 PN/DP, SIPLUS S7-300 CPU 315F-2 PN/DP, SIPLUS S7-300 CPU 317-2 PN/DP, SIPLUS S7-300 CPU 317F-2 PN/DP, SIPLUS S7-400 CPU 414-3 PN/DP V7, SIPLUS S7-400 CPU 416-3 PN/DP V7. Affected devices improperly handle large amounts of specially crafted UDP packets. This could allow an unauthenticated remote attacker to trigger a denial of service condition.

1 / 2
First published (updated )
Severity
7.8
AV:N/AC:L/Au:N/C:N/I:N/A:C

Siemens SIMATIC S7-1200 PLCs 2.x and 3.x allow remote attackers to cause a denial of service (defect-mode transition and control outage) via crafted packets to UDP port 161 (aka the SNMP port).

First published (updated )
Severity
7.8
AV:N/AC:L/Au:N/C:N/I:N/A:C

Siemens SIMATIC S7-1200 PLCs 2.x and 3.x allow remote attackers to cause a denial of service (defect-mode transition and control outage) via crafted packets to TCP port 102 (aka the ISO-TSAP port).

First published (updated )
Severity
4.3
XSS
AV:N/AC:M/Au:N/C:N/I:P/A:N

Cross-site scripting (XSS) vulnerability in the web server on Siemens SIMATIC S7-1200 PLCs 2.x through 3.0.1 allows remote attackers to inject arbitrary web script or HTML via a crafted URI.

First published (updated )
Severity
4.3
AV:N/AC:M/Au:N/C:P/I:N/A:N

The Siemens SIMATIC S7-1200 2.x PLC does not properly protect the private key of the SIMATIC CONTROLLER Certification Authority certificate, which allows remote attackers to spoof the S7-1200 web server by using this key to create a forged certificate.

First published (updated )

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.