Where
AND
-Infinity
0
Severity
7.2
Malicious File Upload
CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H

A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions < V8.1 with WinCC V7.3 Upd 19), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd 11), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11), SIMATIC WinCC Professional (TIA Portal V13) (All versions), SIMATIC WinCC Professional (TIA Portal V14) (All versions < V14 SP1 Upd 9), SIMATIC WinCC Professional (TIA Portal V15) (All versions < V15.1 Upd 3), SIMATIC WinCC Runtime Professional V13 (All versions), SIMATIC WinCC Runtime Professional V14 (All versions < V14.1 Upd 8), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Upd 3), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 19), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 11), SIMATIC WinCC V7.5 (All versions < V7.5 Upd 3). The SIMATIC WinCC DataMonitor web application of the affected products allows to upload arbitrary ASPX code. The security vulnerability could be exploited by an authenticated attacker with network access to the WinCC DataMonitor application. No user interaction is required to exploit this vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the affected device. At the stage of publishing this security advisory no public exploitation is known.

First published (updated )
Severity
9.9
Path Traversal
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H

A vulnerability has been identified in SIMATIC PCS 7 V8.2 (All versions), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP3 UC04), SIMATIC PCS 7 V9.1 (All versions < V9.1 SP1), SIMATIC WinCC V15 and earlier (All versions < V15 SP1 Update 7), SIMATIC WinCC V16 (All versions < V16 Update 5), SIMATIC WinCC V17 (All versions < V17 Update 2), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Update 19), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 5). Legitimate file operations on the web server of the affected systems do not properly neutralize special elements within the pathname. An attacker could then cause the pathname to resolve to a location outside of the restricted directory on the server and read, write or delete unexpected critical files.

First published (updated )
Severity
5.5
CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N

A vulnerability has been identified in SIMATIC PCS 7 V8.2 (All versions), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP3 UC04), SIMATIC PCS 7 V9.1 (All versions < V9.1 SP1), SIMATIC WinCC V15 and earlier (All versions < V15 SP1 Update 7), SIMATIC WinCC V16 (All versions < V16 Update 5), SIMATIC WinCC V17 (All versions < V17 Update 2), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Update 19), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 5). The affected systems store sensitive information in log files. An attacker with access to the log files could publicly expose the information or reuse it to develop further attacks on the system.

First published (updated )
Severity
7.8
CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H

A vulnerability has been identified in SIMATIC PCS 7 V8.2 (All versions), SIMATIC PCS 7 V9.0 (All versions), SIMATIC PCS 7 V9.1 (All versions < V9.1 SP1), SIMATIC WinCC V15 and earlier (All versions < V15 SP1 Update 7), SIMATIC WinCC V16 (All versions < V16 Update 5), SIMATIC WinCC V17 (All versions < V17 Update 2), SIMATIC WinCC V17 (All versions <= V17 Update 4), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Update 19), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 6). The affected component stores the credentials of a local system account in a potentially publicly accessible project file using an outdated cipher algorithm. An attacker may use this to brute force the credentials and take over the system.

First published (updated )
Severity
8.8
Infoleak
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H

A vulnerability has been identified in SIMATIC PCS 7 V8.2 (All versions), SIMATIC PCS 7 V9.0 (All versions), SIMATIC PCS 7 V9.1 (All versions < V9.1 SP1), SIMATIC WinCC V15 and earlier (All versions < V15 SP1 Update 7), SIMATIC WinCC V16 (All versions < V16 Update 5), SIMATIC WinCC V17 (All versions < V17 Update 2), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Update 19), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 6). The password hash of a local user account in the remote server could be granted via public API to a user on the affected system. An authenticated attacker could brute force the password hash and use it to login to the server.

First published (updated )

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.
© 2026 SecAlerts Pty Ltd.