Input Validation
CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:N/A:H

Multiple WAGO devices in multiple versions may allow an authenticated remote attacker with high privileges to DoS the device by sending a specifically crafted packet to the CODESYS V2 runtime.

First published (updated )
Severity
4.9
Input Validation
CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:N/A:H

Multiple WAGO devices in multiple versions may allow an authenticated remote attacker with high privileges to DoS the device by sending a malformed packet.

First published (updated )
Severity
6.5
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H

A crafted request may cause a read access to an uninitialized pointer in CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56, resulting in a denial-of-service condition.

Remedy

CODESYS GmbH has released the following product versions to solve the noted vulnerability issue for the affected CODESYS products: * CODESYS Runtime Toolkit 32 bit full version V2.4.7.56 * CODESYS PLCWinNT version V2.4.7.56. This will also be part of the CODESYS Development System setup version V2.3.9.68.
First published (updated )
Severity
7.5
Buffer Overflow
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Crafted web server requests may cause a heap-based buffer overflow and could therefore trigger a denial-of- service condition due to a crash in the CODESYS V2 web server prior to V1.1.9.22.

Remedy

CODESYS GmbH has released version V1.1.9.22 of the CODESYS V2 web server to solve the noted vulnerability issues. This version of the CODESYS V2 web server is also part of the CODESYS Development System setup version V2.3.9.68.
First published (updated )
Severity
7.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Missing Release of Resource after Effective Lifetime vulnerability in OpenSSL implementation of WAGO 750-831/xxx-xxx, 750-880/xxx-xxx, 750-881, 750-889 in versions FW4 up to FW15 allows an unauthenticated attacker to cause DoS on the device.

Remedy

Update the device to the latest FW version ( >FW15 ).
First published (updated )
Severity
5.3
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L

Wago 750 Series PLCs with firmware version 10 and prior include a remote attack may take advantage of an improper implementation of the 3 way handshake during a TCP connection affecting the communications with commission and service tools. Specially crafted packets may also be sent to Port 2455/TCP/IP, used in Codesys management software, which may result in a denial-of-service condition of communications with commissioning and service tools.

First published (updated )
Severity
7.5
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Older firmware versions (FW1 up to FW10) of the WAGO PLC family 750-88x and 750-352 are vulnerable for a special denial of service attack.

Remedy

Update the device to the latest FW version.
First published (updated )

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.