Where
-Infinity
0
Severity
9.8
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

The Web-GUI on WAGO Series 750-88x (750-330, 750-352, 750-829, 750-831, 750-852, 750-880, 750-881, 750-882, 750-884, 750-885, 750-889) and Series 750-87x (750-830, 750-849, 750-871, 750-872, 750-873) devices has undocumented service access.

First published (updated )
Severity
9.1
Path Traversal
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N

On WAGO PFC200 devices in different firmware versions with special crafted packets an authorised attacker with network access to the device can access the file system with higher privileges.

Remedy

WAGO recommends all effected users with CODESYS 2.3 Runtime PLCs to update to the firmware versions listed at https://cert.vde.com/en-us/advisories/vde-2021-014 in the solution paragraph.
First published (updated )
Severity
9.1
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:H

Improper Authentication vulnerability in WAGO 750-8XX series with FW version <= FW07 allows an attacker to change some special parameters without authentication. This issue affects: WAGO 750-852, WAGO 750-880/xxx-xxx, WAGO 750-881, WAGO 750-831/xxx-xxx, WAGO 750-882, WAGO 750-885/xxx-xxx, WAGO 750-889 in versions FW07 and below.

Remedy

Upgrade devices to the latest standard firmware (> FW07).
First published (updated )
Severity
7.5
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Older firmware versions (FW1 up to FW10) of the WAGO PLC family 750-88x and 750-352 are vulnerable for a special denial of service attack.

Remedy

Update the device to the latest FW version.
First published (updated )
Severity
7.5
Buffer Overflow
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Crafted web server requests may cause a heap-based buffer overflow and could therefore trigger a denial-of- service condition due to a crash in the CODESYS V2 web server prior to V1.1.9.22.

Remedy

CODESYS GmbH has released version V1.1.9.22 of the CODESYS V2 web server to solve the noted vulnerability issues. This version of the CODESYS V2 web server is also part of the CODESYS Development System setup version V2.3.9.68.
First published (updated )
Severity
7.5
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

On WAGO PFC200 devices in different firmware versions with special crafted packets an attacker with network access to the device could cause a denial of service for the login service of the runtime.

Remedy

WAGO recommends all effected users with CODESYS 2.3 Runtime PLCs to update to the firmware versions listed at https://cert.vde.com/en-us/advisories/vde-2021-014 in the solution paragraph.
First published (updated )
Severity
6.5
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H

A crafted request may cause a read access to an uninitialized pointer in CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56, resulting in a denial-of-service condition.

Remedy

CODESYS GmbH has released the following product versions to solve the noted vulnerability issue for the affected CODESYS products: * CODESYS Runtime Toolkit 32 bit full version V2.4.7.56 * CODESYS PLCWinNT version V2.4.7.56. This will also be part of the CODESYS Development System setup version V2.3.9.68.
First published (updated )
Severity
5.3
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L

Wago 750 Series PLCs with firmware version 10 and prior include a remote attack may take advantage of an improper implementation of the 3 way handshake during a TCP connection affecting the communications with commission and service tools. Specially crafted packets may also be sent to Port 2455/TCP/IP, used in Codesys management software, which may result in a denial-of-service condition of communications with commissioning and service tools.

First published (updated )
Severity
4.9
Input Validation
CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:N/A:H

Multiple WAGO devices in multiple versions may allow an authenticated remote attacker with high privileges to DoS the device by sending a specifically crafted packet to the CODESYS V2 runtime.

First published (updated )
Severity
4.9
Input Validation
CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:N/A:H

Multiple WAGO devices in multiple versions may allow an authenticated remote attacker with high privileges to DoS the device by sending a malformed packet.

First published (updated )

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.
© 2026 SecAlerts Pty Ltd.