Where
-Infinity
0

Vendor Risk Score

See how : automationdirect compares to other vendors in security performance

View Risk Score →
Severity
9.8
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

AutomationDirect C-more EA9 HMI contains a function with bounds checks that can be skipped, which could result in an attacker abusing the function to cause a denial-of-service condition or achieving remote code execution on the affected device.

Remedy

AutomationDirect recommends that users update C-MORE EA9 HMI software and firmware to V6.80 https://support.automationdirect.com/firmware/historydetail.php .
First published (updated )
Severity
10
AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H

The embedded web server lacks authentication and access controls, allowing unrestricted remote access. This could lead to configuration changes, operational disruption, or arbitrary code execution depending on the environment and exposed functionality.

First published (updated )
Severity
4.2
AV:L/AC:L/PR:H/UI:R/S:U/C:H/I:N/A:N

Cleartext storage of sensitive information was discovered in Click Programming Software version v3.60. The vulnerability can be exploited by a local user with access to the file system, while an administrator session is active, to steal credentials stored in clear text.

Remedy

AutomationDirect recommends that users update CLICK PLUS and firmware to V3.80. https://www.automationdirect.com/support/software-downloads If the update cannot be applied right away, the following compensating controls are recommended until the upgrade can be performed: * Network Isolation – Disconnect the CLICK PLUS PLC from external networks (e.g., the internet or corporate LAN) to reduce exposure. * Secure Communications – Use only trusted, dedicated internal networks or air-gapped systems for device communication. * Access Control – Restrict both physical and logical access to authorized personnel only. * Application Whitelisting – Configure whitelisting so that only trusted, pre-approved applications are allowed to run. Block any unauthorized software. * Endpoint Protection – Use antivirus or EDR tools and configure host-based firewalls to block unauthorized access attempts. * Logging & Monitoring – Enable and regularly review system logs to detect suspicious or unauthorized activity. * Backup & Recovery – Maintain secure, tested backups of the PLC and its configurations to minimize downtime in case of an incident. * Ongoing Risk Assessment – Continuously evaluate risks associated with running outdated firmware and adjust compensating measures accordingly.
First published (updated )
Severity
8.7
AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:L

A predictable seed in pseudo-random number generator vulnerability has been discovered in firmware version 3.60 of the Click Plus PLC. The vulnerability relies on the fact that the software implements a predictable seed for its pseudo-random number generator, which compromises the security of the generated private keys.

Remedy

AutomationDirect recommends that users update CLICK PLUS and firmware to V3.80. https://www.automationdirect.com/support/software-downloads If the update cannot be applied right away, the following compensating controls are recommended until the upgrade can be performed: * Network Isolation – Disconnect the CLICK PLUS PLC from external networks (e.g., the internet or corporate LAN) to reduce exposure. * Secure Communications – Use only trusted, dedicated internal networks or air-gapped systems for device communication. * Access Control – Restrict both physical and logical access to authorized personnel only. * Application Whitelisting – Configure whitelisting so that only trusted, pre-approved applications are allowed to run. Block any unauthorized software. * Endpoint Protection – Use antivirus or EDR tools and configure host-based firewalls to block unauthorized access attempts. * Logging & Monitoring – Enable and regularly review system logs to detect suspicious or unauthorized activity. * Backup & Recovery – Maintain secure, tested backups of the PLC and its configurations to minimize downtime in case of an incident. * Ongoing Risk Assessment – Continuously evaluate risks associated with running outdated firmware and adjust compensating measures accordingly.
First published (updated )
Severity
6.9
AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N

The use of a hard-coded cryptographic key was discovered in firmware version 3.60 of the Click Plus PLC. The vulnerability relies on the fact that the software contains a hard-coded AES key used to protect the initial messages of a new KOPS session.

Remedy

AutomationDirect recommends that users update CLICK PLUS and firmware to V3.80. https://www.automationdirect.com/support/software-downloads If the update cannot be applied right away, the following compensating controls are recommended until the upgrade can be performed: * Network Isolation – Disconnect the CLICK PLUS PLC from external networks (e.g., the internet or corporate LAN) to reduce exposure. * Secure Communications – Use only trusted, dedicated internal networks or air-gapped systems for device communication. * Access Control – Restrict both physical and logical access to authorized personnel only. * Application Whitelisting – Configure whitelisting so that only trusted, pre-approved applications are allowed to run. Block any unauthorized software. * Endpoint Protection – Use antivirus or EDR tools and configure host-based firewalls to block unauthorized access attempts. * Logging & Monitoring – Enable and regularly review system logs to detect suspicious or unauthorized activity. * Backup & Recovery – Maintain secure, tested backups of the PLC and its configurations to minimize downtime in case of an incident. * Ongoing Risk Assessment – Continuously evaluate risks associated with running outdated firmware and adjust compensating measures accordingly.
First published (updated )
Severity
7.6
AV:N/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:N

An authorization bypass vulnerability has been discovered in the Click Plus C2-03CPU2 device firmware version 3.60. Through the KOPR protocol utilized by the Remote PLC application, authenticated users with low-level access permissions can exploit this vulnerability to read and modify PLC variables beyond their intended authorization level.

Remedy

AutomationDirect recommends that users update CLICK PLUS and firmware to V3.80. https://www.automationdirect.com/support/software-downloads If the update cannot be applied right away, the following compensating controls are recommended until the upgrade can be performed: * Network Isolation – Disconnect the CLICK PLUS PLC from external networks (e.g., the internet or corporate LAN) to reduce exposure. * Secure Communications – Use only trusted, dedicated internal networks or air-gapped systems for device communication. * Access Control – Restrict both physical and logical access to authorized personnel only. * Application Whitelisting – Configure whitelisting so that only trusted, pre-approved applications are allowed to run. Block any unauthorized software. * Endpoint Protection – Use antivirus or EDR tools and configure host-based firewalls to block unauthorized access attempts. * Logging & Monitoring – Enable and regularly review system logs to detect suspicious or unauthorized activity. * Backup & Recovery – Maintain secure, tested backups of the PLC and its configurations to minimize downtime in case of an incident. * Ongoing Risk Assessment – Continuously evaluate risks associated with running outdated firmware and adjust compensating measures accordingly.
First published (updated )
Severity
8.2
AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H

An improper resource shutdown or release vulnerability has been identified in the Click Plus C2-03CPU-2 device running firmware version 3.60. The vulnerability allows an unauthenticated attacker to perform a denial-of-service attack by exhausting all available device sessions of the Click Programming Software.

Remedy

AutomationDirect recommends that users update CLICK PLUS and firmware to V3.80. https://www.automationdirect.com/support/software-downloads If the update cannot be applied right away, the following compensating controls are recommended until the upgrade can be performed: * Network Isolation – Disconnect the CLICK PLUS PLC from external networks (e.g., the internet or corporate LAN) to reduce exposure. * Secure Communications – Use only trusted, dedicated internal networks or air-gapped systems for device communication. * Access Control – Restrict both physical and logical access to authorized personnel only. * Application Whitelisting – Configure whitelisting so that only trusted, pre-approved applications are allowed to run. Block any unauthorized software. * Endpoint Protection – Use antivirus or EDR tools and configure host-based firewalls to block unauthorized access attempts. * Logging & Monitoring – Enable and regularly review system logs to detect suspicious or unauthorized activity. * Backup & Recovery – Maintain secure, tested backups of the PLC and its configurations to minimize downtime in case of an incident. * Ongoing Risk Assessment – Continuously evaluate risks associated with running outdated firmware and adjust compensating measures accordingly.
First published (updated )
Severity
8.2
AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H

An improper resource shutdown or release vulnerability has been identified in the Click Plus C2-03CPU-2 device running firmware version 3.60. The vulnerability allows an unauthenticated attacker to perform a denial-of-service attack by exhausting all available device sessions in the Remote PLC application.

Remedy

AutomationDirect recommends that users update CLICK PLUS and firmware to V3.80. https://www.automationdirect.com/support/software-downloads If the update cannot be applied right away, the following compensating controls are recommended until the upgrade can be performed: * Network Isolation – Disconnect the CLICK PLUS PLC from external networks (e.g., the internet or corporate LAN) to reduce exposure. * Secure Communications – Use only trusted, dedicated internal networks or air-gapped systems for device communication. * Access Control – Restrict both physical and logical access to authorized personnel only. * Application Whitelisting – Configure whitelisting so that only trusted, pre-approved applications are allowed to run. Block any unauthorized software. * Endpoint Protection – Use antivirus or EDR tools and configure host-based firewalls to block unauthorized access attempts. * Logging & Monitoring – Enable and regularly review system logs to detect suspicious or unauthorized activity. * Backup & Recovery – Maintain secure, tested backups of the PLC and its configurations to minimize downtime in case of an incident. * Ongoing Risk Assessment – Continuously evaluate risks associated with running outdated firmware and adjust compensating measures accordingly.
First published (updated )
Severity
8.7
AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:L

The use of a broken or risky cryptographic algorithm was discovered in firmware version 3.60 of the Click Plus PLC. The vulnerability relies on the fact that the software uses an insecure implementation of the RSA encryption algorithm.

Remedy

AutomationDirect recommends that users update CLICK PLUS and firmware to V3.80. https://www.automationdirect.com/support/software-downloads If the update cannot be applied right away, the following compensating controls are recommended until the upgrade can be performed: * Network Isolation – Disconnect the CLICK PLUS PLC from external networks (e.g., the internet or corporate LAN) to reduce exposure. * Secure Communications – Use only trusted, dedicated internal networks or air-gapped systems for device communication. * Access Control – Restrict both physical and logical access to authorized personnel only. * Application Whitelisting – Configure whitelisting so that only trusted, pre-approved applications are allowed to run. Block any unauthorized software. * Endpoint Protection – Use antivirus or EDR tools and configure host-based firewalls to block unauthorized access attempts. * Logging & Monitoring – Enable and regularly review system logs to detect suspicious or unauthorized activity. * Backup & Recovery – Maintain secure, tested backups of the PLC and its configurations to minimize downtime in case of an incident. * Ongoing Risk Assessment – Continuously evaluate risks associated with running outdated firmware and adjust compensating measures accordingly.
First published (updated )
Severity
8.8
Path Traversal
AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H

A relative path traversal (ZipSlip) vulnerability was discovered in Productivity Suite software version

4.4.1.19. The vulnerability allows an attacker who can tamper with a productivity project to execute arbitrary code on the machine where the project is opened.

Remedy

AutomationDirect recommends that users do the following: * Update the Productivity Suite programming software to version 4.5.0.x or higher. * Update the firmware of Productivity PLCs to the latest version. https://www.automationdirect.com/support/software-downloads * Although automation networks and systems come equipped with built-in password protection mechanisms, this represents a fraction of the security measures needed to safeguard these systems. * It is imperative that automation control system networks integrate data protection and security measures that match, if not exceed, the robustness of conventional business computer systems. * AutomationDirect advises users of PLCs, HMI products, and SCADA systems to conduct a thorough network security analysis to ascertain the appropriate level of security necessary for their specific application.
First published (updated )
Severity
8.2
Path Traversal
AV:N/AC:H/PR:N/UI:N/S:C/C:H/I:N/A:N

A relative path traversal vulnerability was discovered in Productivity Suite software version

4.4.1.19.

The vulnerability allows an unauthenticated remote attacker to interact with the ProductivityService PLC simulator and read arbitrary files on the target machine.

Remedy

AutomationDirect recommends that users do the following: * Update the Productivity Suite programming software to version 4.5.0.x or higher. * Update the firmware of Productivity PLCs to the latest version. https://www.automationdirect.com/support/software-downloads * Although automation networks and systems come equipped with built-in password protection mechanisms, this represents a fraction of the security measures needed to safeguard these systems. * It is imperative that automation control system networks integrate data protection and security measures that match, if not exceed, the robustness of conventional business computer systems. * AutomationDirect advises users of PLCs, HMI products, and SCADA systems to conduct a thorough network security analysis to ascertain the appropriate level of security necessary for their specific application.
First published (updated )
Severity
10
AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H

A binding to an unrestricted IP address vulnerability was discovered in Productivity Suite software version v4.4.1.19. The vulnerability allows an unauthenticated remote attacker to interact with the ProductivityService PLC simulator and read, write, or delete arbitrary files and folders on the target machine

Remedy

AutomationDirect recommends that users do the following: * Update the Productivity Suite programming software to version 4.5.0.x or higher. * Update the firmware of Productivity PLCs to the latest version. https://www.automationdirect.com/support/software-downloads * Although automation networks and systems come equipped with built-in password protection mechanisms, this represents a fraction of the security measures needed to safeguard these systems. * It is imperative that automation control system networks integrate data protection and security measures that match, if not exceed, the robustness of conventional business computer systems. * AutomationDirect advises users of PLCs, HMI products, and SCADA systems to conduct a thorough network security analysis to ascertain the appropriate level of security necessary for their specific application.
First published (updated )
Severity
8.3
Path Traversal
AV:N/AC:H/PR:N/UI:N/S:C/C:N/I:L/A:H

A relative path traversal vulnerability was discovered in Productivity Suite software version

4.4.1.19.

The vulnerability allows an unauthenticated remote attacker to interact with the ProductivityService PLC simulator and write files with arbitrary data on the target machine.

Remedy

AutomationDirect recommends that users do the following: * Update the Productivity Suite programming software to version 4.5.0.x or higher. * Update the firmware of Productivity PLCs to the latest version. https://www.automationdirect.com/support/software-downloads * Although automation networks and systems come equipped with built-in password protection mechanisms, this represents a fraction of the security measures needed to safeguard these systems. * It is imperative that automation control system networks integrate data protection and security measures that match, if not exceed, the robustness of conventional business computer systems. * AutomationDirect advises users of PLCs, HMI products, and SCADA systems to conduct a thorough network security analysis to ascertain the appropriate level of security necessary for their specific application.
First published (updated )
Severity
7.1
AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:H

An incorrect permission assignment for a critical resource vulnerability was discovered in Productivity Suite software version 4.4.1.19. The vulnerability allows an attacker with low-privileged credentials to change their role, gaining full control access to the project.

Remedy

AutomationDirect recommends that users do the following: * Update the Productivity Suite programming software to version 4.5.0.x or higher. * Update the firmware of Productivity PLCs to the latest version. https://www.automationdirect.com/support/software-downloads * Although automation networks and systems come equipped with built-in password protection mechanisms, this represents a fraction of the security measures needed to safeguard these systems. * It is imperative that automation control system networks integrate data protection and security measures that match, if not exceed, the robustness of conventional business computer systems. * AutomationDirect advises users of PLCs, HMI products, and SCADA systems to conduct a thorough network security analysis to ascertain the appropriate level of security necessary for their specific application.
First published (updated )
Severity
8.3
Path Traversal
AV:N/AC:H/PR:N/UI:N/S:C/C:N/I:L/A:H

A relative path traversal vulnerability was discovered in Productivity Suite software version 4.4.1.19. The vulnerability allows an unauthenticated remote attacker to interact with the ProductivityService PLC simulator and delete arbitrary files on the target machine.

Remedy

AutomationDirect recommends that users do the following: * Update the Productivity Suite programming software to version 4.5.0.x or higher. * Update the firmware of Productivity PLCs to the latest version. https://www.automationdirect.com/support/software-downloads * Although automation networks and systems come equipped with built-in password protection mechanisms, this represents a fraction of the security measures needed to safeguard these systems. * It is imperative that automation control system networks integrate data protection and security measures that match, if not exceed, the robustness of conventional business computer systems. * AutomationDirect advises users of PLCs, HMI products, and SCADA systems to conduct a thorough network security analysis to ascertain the appropriate level of security necessary for their specific application.
First published (updated )
Severity
6.3
Path Traversal
AV:N/AC:H/PR:N/UI:N/S:C/C:N/I:L/A:N

A relative path traversal vulnerability was discovered in Productivity Suite software version 4.4.1.19. The vulnerability allows an unauthenticated remote attacker to interact with the ProductivityService PLC simulator and create arbitrary directories on the target machine.

Remedy

AutomationDirect recommends that users do the following: * Update the Productivity Suite programming software to version 4.5.0.x or higher. * Update the firmware of Productivity PLCs to the latest version. https://www.automationdirect.com/support/software-downloads * Although automation networks and systems come equipped with built-in password protection mechanisms, this represents a fraction of the security measures needed to safeguard these systems. * It is imperative that automation control system networks integrate data protection and security measures that match, if not exceed, the robustness of conventional business computer systems. * AutomationDirect advises users of PLCs, HMI products, and SCADA systems to conduct a thorough network security analysis to ascertain the appropriate level of security necessary for their specific application.
First published (updated )
Severity
6.3
Path Traversal
AV:N/AC:H/PR:N/UI:N/S:C/C:N/I:L/A:N

A relative path traversal vulnerability was discovered in Productivity Suite software version 4.4.1.19. The vulnerability allows an unauthenticated remote attacker to interact with the ProductivityService PLC simulator and delete arbitrary directories on the target machine.

Remedy

AutomationDirect recommends that users do the following: * Update the Productivity Suite programming software to version 4.5.0.x or higher. * Update the firmware of Productivity PLCs to the latest version. https://www.automationdirect.com/support/software-downloads * Although automation networks and systems come equipped with built-in password protection mechanisms, this represents a fraction of the security measures needed to safeguard these systems. * It is imperative that automation control system networks integrate data protection and security measures that match, if not exceed, the robustness of conventional business computer systems. * AutomationDirect advises users of PLCs, HMI products, and SCADA systems to conduct a thorough network security analysis to ascertain the appropriate level of security necessary for their specific application.
First published (updated )
Severity
7.3
AV:L/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H

A weak password recovery mechanism for forgotten password vulnerability was discovered in Productivity Suite software version v4.4.1.19. The vulnerability allows an attacker to decrypt an encrypted project by answering just one recovery question.

Remedy

AutomationDirect recommends that users do the following: * Update the Productivity Suite programming software to version 4.5.0.x or higher. * Update the firmware of Productivity PLCs to the latest version. https://www.automationdirect.com/support/software-downloads * Although automation networks and systems come equipped with built-in password protection mechanisms, this represents a fraction of the security measures needed to safeguard these systems. * It is imperative that automation control system networks integrate data protection and security measures that match, if not exceed, the robustness of conventional business computer systems. * AutomationDirect advises users of PLCs, HMI products, and SCADA systems to conduct a thorough network security analysis to ascertain the appropriate level of security necessary for their specific application.
First published (updated )

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.