See how eaton compares to other vendors in security performance
Eaton easySoft improperly validates TLS certificates presented by easyE4 devices. A network-adjacent attacker could exploit this weakness to perform a man-in-the-middle attack and potentially intercept or modify communications between easySoft and easyE4.
Eaton easyE4 uses an insufficiently strong password policy. An attacker who obtains a password hash, including through CVE-2026-41020, could perform an offline password-guessing attack and potentially recover user credentials.
Eaton easyE4 uses a static nonce during authentication, which could allow an unauthenticated attacker with access to captured authentication traffic to replay a valid authentication exchange and gain unauthorized access to the device.
Improper input validation in one of the session management interface of Eaton's Tripp Lite series PADM firmware could allow an authenticated user to elevate privileges resulting in unrestricted access to the device.
Improper input validation in one of the session management interface of Eaton's Tripp Lite Series PADM firmware could allow an authenticated administrator to execute arbitrary commands within a restricted environment.
Improper input validation in the authentication component of Eaton's Tripp Lite series PADM firmware could allow an unauthenticated remote attacker to bypass authentication and gain a privileged user access to the device.
Eaton Intelligent Power Protector (IPP) is affected by insecure library loading in its executable, which could lead to arbitrary code execution by an attacker with access to the software package. This security issue has been fixed in the latest version of Eaton IPP software which is available on the Eaton download center.
A security misconfiguration was identified in Eaton Intelligent Power Protector (IPP), where an HTTP response header was set with an insecure attribute, potentially exposing users to web‑based attacks. This security issue has been fixed in the latest version of Eaton IPP software which is available on the Eaton download centre.
Eaton Intelligent Power Protector (IPP) uses an insecure cookie configuration, which could allow a network‑based attacker to intercept the cookie and exploit it through a man‑in‑the‑middle attack. This security issue has been fixed in the latest version of Eaton IPP software which is available on the Eaton download centre.
Eaton Intelligent Power Protector (IPP) software allows repeated authentication attempts against the web interface login page due to insufficient rate‑limiting controls. This security issue has been fixed in the latest version of Eaton IPP which is available on the Eaton download centre.
Due to improper input validation in one of the Eaton Intelligent Power Protector (IPP) XML, it is possible for an attacker with admin privileges and access to the local system to inject malicious code resulting in arbitrary command execution. This security issue has been fixed in the latest version of Eaton IPP software which is available on the Eaton download centre.
The encryption mechanism used in Eaton's EasySoft project file was insecure and susceptible to brute force attacks, an attacker with access to this file and the local host machine could potentially read the sensitive information stored and tamper with the project file. This security issue has been fixed in the latest version of Eaton EasySoft which is available on the Eaton download centre.
The server identity check mechanism for firmware upgrade performed via command shell is insecurely implemented potentially allowing an attacker to perform a Man-in-the-middle attack. This security issue has been fixed in the latest firmware version of Eaton
Network M3
which is available on the Eaton download center.
Due to insecure library loading in the Eaton UPS Companion software executable, an attacker with access to the software package
could perform arbitrary code execution . This security issue has been fixed in the latest version of EUC which is available on the Eaton download center.
Improper quotation in search paths in the Eaton UPS Companion software installer could lead to arbitrary code execution of an attacker with the access to the
file system. This security issue has been fixed in the latest version of EUC which is available on the Eaton download center.
Improper authentication of library files in the Eaton UPS Companion software installer could lead to arbitrary code execution of an attacker with the access to the software package. This security issue has been fixed in the latest version of EUC which is available on the Eaton download center.
Improper input validation at one of the endpoints of Eaton xComfort ECI's
web interface, could lead into an attacker with network access to the device executing privileged user commands. As cybersecurity standards continue to evolve and to meet our requirements today, Eaton has decided to discontinue the product. Upon retirement or end of support, there will be no new security updates, non-security updates, or paid assisted support options, or online technical content updates.
Improper input sanitization in the file archives upload functionality of Eaton Galileo software allows traversing paths which could lead into an attacker with local access to execute unauthorized code or commands. This security issue has been fixed in the latest version of Galileo which is available on the Eaton download center.
The privileged user could log in without sufficient credentials after enabling an application protocol. This security issue has been fixed in the latest script patch latest version of of Eaton BLSS (7.3.0.SCP004).
Arbitrary code execution is possible due to improper validation of the file upload functionality in Eaton BLSS. This security issue has been fixed in the latest script patch latest version of of Eaton BLSS (7.3.0.SCP004).
Improper authentication of library files in the Eaton IPP software installer could lead to arbitrary code execution of an attacker with the access to the software package.
This security issue has been fixed in the latest version of IPP which is available on the Eaton download center.
An attacker with authenticated and privileged access could modify the contents of a non-sensitive file by traversing the path in the limited shell of the CLI. This security issue has been fixed in the latest version of NMC G2 which is available on the Eaton download center.
The server identity check mechanism for firmware upgrade performed via command shell is insecurely implemented potentially allowing an attacker to perform a Man-in-the-middle attack. This security issue has been fixed in the latest firmware version of Eaton G4 PDU which is available on the Eaton download center.
In Eaton X303 3.5.16 - X303 3.5.17 Build 712, an attacker with network access to a XC-303 PLC can login as root over SSH. The root password is hardcoded in the firmware. NOTE: This vulnerability appears in versions that are no longer supported by Eaton.
Eaton Intelligent Power Manager (IPM) prior to 1.70 is vulnerable to stored Cross site scripting. The vulnerability exists due to insufficient validation of input from certain resources by the IPM software. The attacker would need access to the local Subnet and an administrator interaction to compromise the system
The Eaton Foreseer software provides multiple customizable input fields for the users to configure parameters in the tool like alarms, reports, etc. Some of these input fields were not checking the length and bounds of the entered value. The exploit of this security flaw by a bad actor may result in excessive memory consumption or integer overflow.
The Eaton Foreseer software provides the feasibility for the user to configure external servers for multiple purposes such as network management, user management, etc. The software uses encryption to store these configurations securely on the host machine. However, the keys used for this encryption were insecurely stored, which could be abused to possibly change or remove the server configuration.
The Eaton Foreseer software provides users the capability to customize the dashboard in WebView pages. However, the input fields for this feature in the Eaton Foreseer software lacked proper input sanitization on the server-side, which could lead to injection and execution of malicious scripts when abused by bad actors.
Eaton easySoft software is used to program easy controllers and displays for configuring, programming and defining parameters for all the intelligent relays. This software has a password protection functionality to secure the project file from unauthorized access. This password was being stored insecurely and could be retrieved by skilled adversaries.
Eaton easyE4 PLC offers a device password protection functionality to facilitate a secure connection and prevent unauthorized access. It was observed that the device password was stored with a weak encoding algorithm in the easyE4 program file when exported to SD card (.PRG file ending).