Where
-Infinity
0
Severity
9.8
OS Command Injection, Command Injection
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') vulnerability in Johnson Controls Frick Controls Quantum HD allows OS Command Injection. Insufficient validation of input in certain parameters may permit unexpected actions, which could impact the security of the device before authentication occurs.This issue affects Frick Controls Quantum HD version 10.22 and prior.

Remedy

a. Quantum HD version 10.22 through Version 11 is a previous product platform and is End Of support platform and should be upgraded to new platform with Quantum HD Unity version 12 and above. The update procedure can be found here:  https://www.johnsoncontrols.com/trust-center/cybersecurity/security-advisories
First published (updated )
Severity
9.8
Code Injection
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

Improper Control of Generation of Code ('Code Injection') vulnerability in Johnson Controls Frick Controls Quantum HD allows Code Injection. Insufficient validation of input in certain parameters may permit unexpected actions, which could impact the security of the device before authentication occurs.This issue affects Frick Controls Quantum HD version 10.22 and prior.

Remedy

a. Quantum HD version 10.22 through Version 11 is a previous product platform and is End Of support platform and should be upgraded to new platform with Quantum HD Unity version 12 and above. The update procedure can be found here:  https://frickcontrolsblob.file.core.windows.net/frickweb1/Quantum-HD-Unity/Quantum_HD_Unity_Software... https://frickcontrolsblob.file.core.windows.net/frickweb1/Quantum-HD-Unity/Quantum_HD_Unity_Software_Update_Procedure.pdf b. After the upgrade to version 12 is completed, ensure full alignment with hardening guide and apply all relevant security configurations. d. For more detailed mitigation instructions, please see Johnson Controls Product Security Advisory JCI-PSA-2026-05 at the following location
First published (updated )
Severity
9.8
Code Injection
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

Improper Control of Generation of Code ('Code Injection') vulnerability in Johnson Controls Frick Controls Quantum HD allows Code Injection. Insufficient validation of input in certain parameters may permit unexpected actions, which could impact the security of the device before authentication occurs.This issue affects Frick Controls Quantum HD version 10.22 and prior.

Remedy

a. Quantum HD version 10.22 through Version 11 is a previous product platform and is End Of support platform and should be upgraded to new platform with Quantum HD Unity version 12 and above.  The update procedure can be found here:  https://www.johnsoncontrols.com/trust-center/cybersecurity/security-advisories
First published (updated )
Severity
9.8
Code Injection
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

Unauthenticated Remote Code Execution i.e Improper Control of Generation of Code ('Code Injection') vulnerability in Johnson Controls Frick Controls Quantum HD allows Code Injection. Insufficient validation of input in certain parameters may permit unexpected actions, which could impact the security of the device before authentication occurs.This issue affects Frick Controls Quantum HD version 10.22 and prior.

Remedy

a. Quantum HD version 10.22 through Version 11 is a previous product platform and is End Of support platform and should be upgraded to new platform with Quantum HD Unity version 12 and above. The update procedure can be found here: https://www.johnsoncontrols.com/trust-center/cybersecurity/security-advisories
First published (updated )
Severity
9.8
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

Unauthenticated Remote Code Execution and Information Disclosure due to Local File Inclusion (LFI) vulnerability in Johnson Controls Frick Controls Quantum HD allow an unauthenticated attacker to execute arbitrary code on the affected device, leading to full system compromise. This issue affects Frick Controls Quantum HD: Frick Controls Quantum HD version 10.22 and prior.

Remedy

a. Quantum HD version 10.22 through Version 11 is a previous product platform and is End Of support platform and should be upgraded to new platform with Quantum HD Unity version 12 and above. The update procedure can be found here: https://www.johnsoncontrols.com/trust-center/cybersecurity/security-advisories
First published (updated )
Severity
9.5
Command Injection
CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

Johnson Controls Metasys component listed below have Improper Neutralization of Special Elements used in a Command (Command Injection) Vulnerability . Successful exploitation of this vulnerability could allow remote SQL execution This issue affects

Metasys: Application and Data Server (ADS) installed with SQL Express deployed as part of the Metasys 14.1 and prior installation,  Extended Application and Data Server (ADX) installed with SQL Express deployed as part of the Metasys 14.1 installation,  LCS8500 or NAE8500 installed with SQL Express deployed as part of the Metasys installation Releases 12.0 through 14.1,  System Configuration Tool (SCT) installed with SQL Express deployed as part of the SCT installation 17.1 and prior,  Controller Configuration Tool (CCT) installed with SQL Express deployed as part of the CCT installation 17.0 and prior.

Remedy

a. Follow the Johnson Controls hardening guide steps to ensure your Metasys installation is on a segmented network, not exposed to untrusted networks such as the internet b. Download and execute the Metasys patch for GIV-165989 from the License Portal https://software.jci.com/licenseportal/ . Login credentials are required c. Close incoming TCP port 1433 d. For more detailed mitigation instructions, please see Johnson Controls Product Security Advisory JCI-PSA-2026-02 at the following location: https://www.johnsoncontrols.com/cyber-solutions/security-advisories
First published (updated )
Severity
8.8
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

The iSTAR door controllers running firmware prior to version 6.6.B, does not support authenticated communications with ICU, which may allow an attacker to gain unauthorized access

Remedy

• Replace the iSTAR Pro, Edge and eX door controllers with a current generation iSTAR door controller (such as iSTAR Ultra G2) which supports authentication and prevents the ICU from making configuration changes. • Ensure your iSTAR Ultra and Ultra LT door controllers are running firmware 6.6.B or greater.
First published (updated )
Severity
8.7
CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

Deserialization of untrusted data vulnerability in Johnson Control victor on Windows, Johnson Controls CCure 9000, and Johnson Controls Victor Application Server allows capec-586.

This issue affects victor: before 8.0; CCure 9000: before 3.2; Victor Application Server: before 4.1.

First published (updated )
Severity
8.4
CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:L/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

An Uncontrolled Search Path Element vulnerability in JohnsonControls AC2000 on Windows allows Leveraging/Manipulating Configuration File Search Paths.

This issue affects AC2000: from 10.6 before release 10, from 11.0 before release 9, from 12 before release 3.

First published (updated )
Severity
7.7
CVSS:4.0/AV:N/AC:L/AT:P/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

Under certain circumstances the Software House C?CURE 9000 installer will utilize weak credentials.

1 / 2
Source: NVD

Remedy

Update Software House C●CURE 9000 to at least version 2.90
First published (updated )
Severity
7.2
CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:L/VI:H/VA:L/SC:L/SI:L/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

Due to Nonce reuse, attackers can perform reply attack or decrypt captured packets.

Remedy

a. Update IQ Panel 4’s to version 4.6.1/4.6.1i b. Devices that support PowerG+ should use PowerG v53.05 or later. c. During the installation or enrollment of PowerG+ devices, enter the PIN code in the PIN Code field on the sensor enrollment screen. For additional security, Johnson Controls recommends only authorized company personnel or integrators be present during the pairing process d. Replace all End-of-Life Products (IQ Panel 2, IQ Panel 2+, IQ Hub) with the latest IQ Panel 4 using firmware version 4.6.1 or greater
First published (updated )
Severity
7.2
Weak RNG
CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:L/VI:H/VA:L/SC:L/SI:L/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

Use of a weak pseudo-random number generator, which may allow an attacker to read or inject encrypted PowerG packets.

Remedy

a. Update IQ Panel 4’s to version 4.6.1/4.6.1i b. Devices that support PowerG+ should use PowerG v53.05 or later. c. During the installation or enrollment of PowerG+ devices, enter the PIN code in the PIN Code field on the sensor enrollment screen. For additional security, Johnson Controls recommends only authorized company personnel or integrators be present during the pairing process d. Replace all End-of-Life Products (IQ Panel 2, IQ Panel 2+, IQ Hub) with the latest IQ Panel 4 using firmware version 4.6.1 or greater
First published (updated )
Severity
7.2
CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:L/VI:H/VA:L/SC:L/SI:L/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

Authentication issue that does not verify the source of a packet which could allow an attacker to create a denial-of-service condition or modify the configuration of the device.

Remedy

a. Update IQ Panel 4’s to version 4.6.1/4.6.1i b. Devices that support PowerG+ should use PowerG v53.05 or later. c. During the installation or enrollment of PowerG+ devices, enter the PIN code in the PIN Code field on the sensor enrollment screen. For additional security, Johnson Controls recommends only authorized company personnel or integrators be present during the pairing process d. Replace all End-of-Life Products (IQ Panel 2, IQ Panel 2+, IQ Hub) with the latest IQ Panel 4 using firmware version 4.6.1 or greater
First published (updated )
Severity
7.2
SSRF
CVSS:4.0/AV:N/AC:L/AT:P/PR:H/UI:N/VC:H/VI:L/VA:L/SC:H/SI:H/SA:L/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

Victor SSRF vulnerability in Johnson Controls CCure 9000 and victor application server allows Server Side Request Forgery.

This issue affects CCure 9000 and victor application server: from 2.9 through 3.0.

First published (updated )
Severity
7.1
Buffer Overflow
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:P/VC:N/VI:L/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

Johnson Controls iSTAR Configuration Utility (ICU) has Stack-based Buffer Overflow vulnerability. This issue affects iSTAR Configuration Utility (ICU) version 6.9.7 and prior. Successful exploitation of this vulnerability could result in failure within the operating system of the machine hosting the ICU tool.

Remedy

Update the ICU to version 6.9.8
First published (updated )
Severity
7.1
CVSS:4.0/AV:N/AC:H/AT:P/PR:H/UI:N/VC:H/VI:L/VA:L/SC:H/SI:L/SA:L/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

Cwe-269 vulnerability in Johnson Controls victor Web on Windows allows capec-233.

This issue affects victor Web: before 7.1.

First published (updated )
Severity
7
CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:H/VI:L/VA:N/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

Use of hard-coded cryptographic key vulnerability in Johnson Controls Airwall allows : Cryptanalytic Attack.

This issue affects Airwall: before 4.1.

First published (updated )
Severity
6.1
XSS
CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:U/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

Improper neutralization of input during web page generation ('cross-site scripting') vulnerability in Johnson Controls Metasys 14 and Johnson Controls Metasys 15 allows Cross Site Scripting.

This issue affects Metasys 14: before 14.1.5; Metasys 15: before 15.0.1.

First published (updated )
Severity
4.8
XSS
CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:P/VC:L/VI:N/VA:N/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

Improper neutralization of input during web page generation ('cross-site scripting') vulnerability in Johnson Controls FM Systems Employee allows Stored XSS.

This issue affects FM Systems Employee: before 2025.3.1.

First published (updated )
Severity
3.1
Infoleak
AV:A/AC:H/PR:N/UI:N/S:U/C:L/I:N/A:N

Under certain circumstances, when the controller is in factory reset mode waiting for initial setup, it will broadcast its MAC address, serial number, and firmware version. Once configured, the controller will no longer broadcast this information.

Remedy

Update Kantech door controllers as follows: * Update Kantech KT1 Door Controller to at least version 3.10.12 * Update Kantech KT2 Door Controller to at least version 3.10.12 * Update Kantech KT400 Door Controller to at least version 3.03
First published (updated )
Severity
7.5
CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N

Sensitive Cookie Without 'HttpOnly' Flag vulnerability in Johnson Controls System Configuration Tool (SCT) version 14 prior to 14.2.3 and version 15 prior to 15.0.3 could allow access to the cookie.

Remedy

Update SCT version 14 with patch 14.2.3

Remedy

Update SCT version 15 with patch 15.0.3

Remedy

Contact your local Johnson Controls office or Authorized Building Control Specialists (ABCS).
First published (updated )
Severity
7.5
CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N

Sensitive Cookie in HTTPS Session Without 'Secure' Attribute vulnerability in Johnson Controls System Configuration Tool (SCT) version 14 prior to 14.2.3 and version 15 prior to 15.0.3 could allow access to the cookie.

Remedy

Update SCT version 14 with patch 14.2.3

Remedy

Update SCT version 15 with patch 15.0.3

Remedy

Contact your local Johnson Controls office or Authorized Building Control Specialists (ABCS).
First published (updated )
Severity
8.8
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H

Successful exploitation of this vulnerability could give an authenticated Facility Explorer SNC Series Supervisory Controller (F4-SNC) user an unintended level of access to the controller’s file system, allowing them to access or modify system files by sending specifically crafted web messages to the F4-SNC.

Remedy

Apply a patch to the Facility Explorer SNC Series Supervisory Controllers (F4-SNC).
First published (updated )
Severity
7.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

Under some circumstances an Insufficiently Protected Credentials vulnerability in Johnson Controls Metasys ADS/ADX/OAS 10 versions prior to 10.1.6 and 11 versions prior to 11.0.3 allows API calls to expose credentials in plain text.

Remedy

Update all Metasys ADS/ADX/OAS 10 versions with patch 10.1.6.

Remedy

Update all Metasys ADS/ADX/OAS 11 versions with patch 11.0.3.
First published (updated )

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.
© 2026 SecAlerts Pty Ltd.
ABN: 70 645 966 203, ACN: 645 966 203