See how rockwell automation compares to other vendors in security performance
A denial-of-service security issue exists in the affected product and version. The security issue stems from the controller repeatedly attempting to forward messages. The issue could result in a major nonrecoverable fault on the controller.
An open database issue exists in the affected product and version. The security issue stems from an over permissive Redis instance. This could result in an attacker on the intranet accessing sensitive data and potential alteration of data.
An authentication bypass security issue exists within FactoryTalk Historian Site Edition. By continually sending requests to the login endpoint, an attacker may obtain a valid authentication token.
A security issue exists within 1769 CompactLogix controllers due to the missing validation of sequence numbers and source IP addresses in the CIP protocol. This allows attacker to abuse the exposed Connection ID’s visible on the web interface to perform denial-of-service attacks, resulting in a minor fault.
A security issue was identified in Pavilion due to improper authorization enforcement in API endpoints. This vulnerability can allow an unauthorized actor to execute privileged operations, including user/role management and other administrative actions.
A denial-of-service issue exists in 5370/5570 controllers. This vulnerability could potentially allow a remote user to load an invalid project, causing the device to enter a major non-recoverable fault (MNRF).
A denial-of-service issue exists in 5380/5480/5580 controllers boot firmware lower than version 1.072. This vulnerability could potentially allow a malicious user to write invalid file data to the controller, causing the device to enter a major non-recoverable fault (MNRF).
A denial-of-service issue exists in 5380/5480/5580 controllers. This vulnerability could potentially allow a malicious user to write invalid file data to the controller, causing the device to enter a major non-recoverable fault (MNRF).
A security issue exists due to improper handling of malformed CIP packets during fuzzing. The controller enters a hard fault with solid red Fault LED and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF019. To recover, clear the fault.
A security issue was found in the IPv6 stack in the Micro850 and Micro870 controllers when the controllers received multiple malformed packets during fuzzing. The controllers will go into recoverable fault with fault code 0xFE60. To recover the controller, clear the fault.
A denial-of-service security issue exists within FactoryTalk® Historian Machine Edition. A network adjacent attacker who is authenticated could send crafted requests to the web interface, resulting in buffer overflow conditions that may cause the device to crash and become unresponsive.
A denial-of-service security issue exists in the affected product. The security issue stems from a crafted CIP packet being sent crashing the module. The device requires a restart to recover.
A privilege escalation security issue exists within FactoryTalk® Activation Manager. The security issue stems from custom actions in the installer that spawn visible console windows running with SYSTEM privileges during installation or repair operations. An authenticated attacker with Windows credentials could hijack these console windows to obtain a SYSTEM-level command prompt, allowing full access to all files, processes, and system resources.
A denial-of-service security issue exists within RSLinx® Classic. The security issue stems from improper handling of a malformed packet. A crafted CIP packet can cause the RSLinx® Classic service to crash, requiring a restart of the service to recover
A denial-of-service security issue exists in the affected Logix platforms listed in the table above. The security issue stems from improper validation of input length during CIP message processing. This can result in a major nonrecoverable fault (MNRF), requiring a power cycle to recover
A denial-of-service security issue exists within RSLinx® Classic. A crafted CIP packet targeting the Forward Close service can cause the RSLinx® Classic service to crash, requiring a restart of the service to recover.
A denial-of-service security issue exists within RSLinx® Classic. A crafted CIP packet with an oversized embedded message request can cause the RSLinx® Classic service to crash, requiring a restart of the service to recover.
A denial-of-service security issue exists within RSLinx® Classic. A crafted CIP packet can cause the RSLinx® Classic service to crash due to insufficient data length validation, requiring a restart of the service to recover.
A code execution security issue exists within Studio 5000 Logix Designer® due to an unquoted search path in the External Tools configuration. The executable paths specified in the external tools configuration file are not properly quoted, and because these paths contain spaces, the operating system may resolve them to unintended executables placed earlier in the search order. If exploited, an attacker could plant a malicious executable in a location within the search path, resulting in arbitrary code execution with the same permissions of the user running the application.
A path traversal security issue exists within Studio 5000 Logix Designer® due to improper limitation of file paths within ACD project files. The software does not sanitize or validate file names embedded in the ACD file structure during the project opening procedure, allowing path traversal sequences to escape the intended extraction directory. If exploited, an attacker could craft a malicious ACD project file that results in arbitrary files being written to attacker-controlled locations on the file system, potentially leading to code execution.
A remote code execution security issue exists within Studio 5000 Logix Designer® due to incorrect authorization on a configuration file. This can allow any authenticated user to modify the paths of external tools configured within the application. If exploited, an attacker could alter the configuration to point to a malicious executable, resulting in arbitrary code execution when any user interacts with the external tools functionality.
A security issue exists within Arena® Simulation due to a memory corruption vulnerability in the model.exe (Siman) component. The vulnerability stems from improper validation of user-supplied data, which can result in an out-of-bounds write. An attacker could leverage this vulnerability to execute arbitrary code in the context of the current process by convincing a user to open a malicious file.
A security issue exists within Arena® Simulation due to a memory corruption vulnerability in the siman.exe (Siman) component. The vulnerability stems from improper validation of user-supplied data, which can result in an out-of-bounds write. An attacker could leverage this vulnerability to execute arbitrary code in the context of the current process by convincing a user to open a malicious file.
A security issue exists within the 1715-AENTR EtherNet/IP Adapter. The affected product exposes a network-accessible debug port that does not enforce proper privilege controls, allowing unauthenticated remote access to intrusive command-line interface (CLI) commands. If exploited, a threat actor could read or delete files, stop tasks, modify memory, and change I/O states, potentially impacting the confidentiality, integrity, and availability of the device.
A security issue exists within FactoryTalk® Services Platform (FTSP), allowing an attacker to bypass JWT signature validation during Okta Web Authentication. The vulnerability stems from the application not verifying that the JWT algorithm is configured for RSA, enabling an attacker to set the algorithm to "none" and craft forged tokens. This could allow an authenticated low-privilege user to impersonate any authorized user on the FTSP server, resulting in unauthorized access to system configuration and the ability to grant permissions to other systems protected by FTSP.
A denial-of-service security issue exists across all the 1756-EN2, EN3, and ENBT communication module due to improper validation of CIP Implicit Connection packets. An attacker on the network can exploit this by sending crafted packets to continuously disrupt device connections, though device connections will recover immediately after.
A path traversal security issue exists within Rockwell Automation ThinManager® software due to improper limitation of file save operations within the API. An authenticated attacker could exploit this vulnerability to write arbitrary files to restricted system directories outside of the application's intended directory.
A Stored Cross-Site Scripting security issue exists within FactoryTalk® DataMosaix™ Private Cloud. The vulnerability stems from improper neutralization of user-supplied input within the Workflows configuration. An authenticated attacker with high privileges can inject malicious scripts that are permanently stored on the server. This vulnerability can result in the execution of malicious JavaScript when other users access the affected page, potentially allowing for account takeover, credential theft, or redirection to a malicious website.
A denial-of-service security issue exists in the affected products. The security issue stems from improper handling of exceptional conditions when processing crafted CIP packets sent to the adapter. A power cycle is required to recover the module and associated I/O.
A security issue exists within CompactLogix® 5380, ControlLogix® 5580, and EN4 communication modules related to CIP Security certificate revocation handling. The security issue stems from the controller failing to properly reject certificates signed by an intermediate certificate that has been revoked via a Certificate Revocation List (CRL). This could allow a network-based attacker to establish a connection using a certificate that should be untrusted, potentially bypassing CIP Security protections.