See how rockwell automation compares to other vendors in security performance
Studio 5000 Logix Designer 30.01.00 contains an unquoted service path vulnerability in the FactoryTalk Activation Service that allows local users to potentially execute code with elevated privileges. Attackers can exploit the unquoted path in C:\Program Files (x86)\Rockwell Software\FactoryTalk Activation\ to inject malicious code that would execute with LocalSystem permissions.
A security issue exists within the 1715-AENTR EtherNet/IP Adapter. The affected product exposes a network-accessible debug port that does not enforce proper privilege controls, allowing unauthenticated remote access to intrusive command-line interface (CLI) commands. If exploited, a threat actor could read or delete files, stop tasks, modify memory, and change I/O states, potentially impacting the confidentiality, integrity, and availability of the device.
A security issue exists within Arena® Simulation due to a memory corruption vulnerability in the siman.exe (Siman) component. The vulnerability stems from improper validation of user-supplied data, which can result in an out-of-bounds write. An attacker could leverage this vulnerability to execute arbitrary code in the context of the current process by convincing a user to open a malicious file.
A security issue exists within Arena® Simulation due to a memory corruption vulnerability in the model.exe (Siman) component. The vulnerability stems from improper validation of user-supplied data, which can result in an out-of-bounds write. An attacker could leverage this vulnerability to execute arbitrary code in the context of the current process by convincing a user to open a malicious file.
A security issue exists within FactoryTalk® Services Platform (FTSP), allowing an attacker to bypass JWT signature validation during Okta Web Authentication. The vulnerability stems from the application not verifying that the JWT algorithm is configured for RSA, enabling an attacker to set the algorithm to "none" and craft forged tokens. This could allow an authenticated low-privilege user to impersonate any authorized user on the FTSP server, resulting in unauthorized access to system configuration and the ability to grant permissions to other systems protected by FTSP.
A path traversal security issue exists within Rockwell Automation ThinManager® software due to improper limitation of file save operations within the API. An authenticated attacker could exploit this vulnerability to write arbitrary files to restricted system directories outside of the application's intended directory.
A Stored Cross-Site Scripting security issue exists within FactoryTalk® DataMosaix™ Private Cloud. The vulnerability stems from improper neutralization of user-supplied input within the Workflows configuration. An authenticated attacker with high privileges can inject malicious scripts that are permanently stored on the server. This vulnerability can result in the execution of malicious JavaScript when other users access the affected page, potentially allowing for account takeover, credential theft, or redirection to a malicious website.
A code execution security issue exists within Studio 5000 Logix Designer® due to an unquoted search path in the External Tools configuration. The executable paths specified in the external tools configuration file are not properly quoted, and because these paths contain spaces, the operating system may resolve them to unintended executables placed earlier in the search order. If exploited, an attacker could plant a malicious executable in a location within the search path, resulting in arbitrary code execution with the same permissions of the user running the application.
A path traversal security issue exists within Studio 5000 Logix Designer® due to improper limitation of file paths within ACD project files. The software does not sanitize or validate file names embedded in the ACD file structure during the project opening procedure, allowing path traversal sequences to escape the intended extraction directory. If exploited, an attacker could craft a malicious ACD project file that results in arbitrary files being written to attacker-controlled locations on the file system, potentially leading to code execution.
A remote code execution security issue exists within Studio 5000 Logix Designer® due to incorrect authorization on a configuration file. This can allow any authenticated user to modify the paths of external tools configured within the application. If exploited, an attacker could alter the configuration to point to a malicious executable, resulting in arbitrary code execution when any user interacts with the external tools functionality.
A denial-of-service security issue exists in the affected products. The security issue stems from improper handling of exceptional conditions when processing crafted CIP packets sent to the adapter. A power cycle is required to recover the module and associated I/O.
A security issue exists within CompactLogix® 5380, ControlLogix® 5580, and EN4 communication modules related to CIP Security certificate revocation handling. The security issue stems from the controller failing to properly reject certificates signed by an intermediate certificate that has been revoked via a Certificate Revocation List (CRL). This could allow a network-based attacker to establish a connection using a certificate that should be untrusted, potentially bypassing CIP Security protections.
A denial-of-service security issue exists in the affected product and version. The security issue stems from improper handling of network storm traffic, which can interrupt communication, cause device faults, and affect open TCP and UDP ports. A power cycle is required to recover the device to its normal state.
A security issue exists within 1732E ArmorBlock® I/O, where an unauthenticated attacker can change the device's webserver password without valid credentials. This could result in admin account takeover or unauthorized modification of device configuration.
A security issue exists within the Studio 5000 Logix Designer add-on profile (AOP) for the ArmorStart Classic distributed motor controller, resulting in denial-of-service. This vulnerability is possible due to the input of invalid values into Component Object Model (COM) methods.
A security issue exists within the Rockwell Automation Driver Package x64 Microsoft Installer File (MSI) repair functionality, installed with FTLinx. Authenticated attackers with valid Windows Users credentials can initiate a repair and hijack the resulting console window for vbpinstall.exe. This allows the launching of a command prompt running with SYSTEM-level privileges, allowing full access to all files, processes, and system resources.
An authentication bypass security issue exists within FactoryTalk View Machine Edition Web Browser ActiveX control. Exploitation of this vulnerability allows unauthorized access to the PanelView Plus 7 Series B, including access to the file system, retrieval of diagnostic information, event logs, and more.
A denial-of-service security issue in the affected product. The security issue stems from a fault occurring when a crafted CIP unconnected explicit message is sent. This can result in a major non-recoverable fault.
A path traversal security issue exists within FactoryTalk View Machine Edition, allowing unauthenticated attackers on the same network as the device to delete any file within the panels operating system. Exploitation of this vulnerability is dependent on the knowledge of filenames to be deleted.
A security issue was discovered within FactoryTalk® ViewPoint, allowing unauthenticated attackers to achieve XXE. Certain SOAP requests can be abused to perform XXE, resulting in a temporary denial-of-service.
A security issue exists within the x86 Microsoft Installer File (MSI), installed with FTLinx. Authenticated attackers with valid Windows user credentials can initiate a repair and hijack the resulting console window. This allows the launching of a command prompt running with SYSTEM-level privileges, allowing full access to all files, processes, and system resources.
A cross-site request forgery security issue exists in the product and version listed. The vulnerability stems from missing CSRF checks on the impacted form. This allows for unintended configuration modification if an attacker can convince a logged in admin to visit a crafted link.
A Stored Cross-Site Scripting security issue exists in the affected product that could potentially allow a malicious user to view and modify sensitive data or make the webpage unavailable. The vulnerability stems from missing special character filtering and encoding. Successful exploitation requires an attacker to be able to update configuration fields behind admin login.
Multiple Broken Authentication security issues exist in the affected product. The security issues are due to missing authentication checks on critical functions. These could result in potential denial-of-service, admin account takeover, or NAT rule modifications. Devices would no longer be able to communicate through NATR as a result of denial-of-service or NAT rule modifications. NAT rule modification could also result in device communication to incorrect endpoints. Admin account takeover could allow modification of configuration and require physical access to restore.
A denial-of-service security issue exists in the affected product and version. The security issue is caused through CIP communication using crafted payloads. The security issue could result in no CIP communication with 1715 EtherNet/IP Adapter.A restart is required to recover.
A denial-of-service security issue exists in the affected product and version. The security issue stems from a high number of requests sent to the web server. This could result in a web server crash however; this does not impact I/O control or communication . A power cycle is required to recover and utilize the webpage.
Rockwell Automation Arena® suffers from a stack-based buffer overflow vulnerability. The specific flaw exists within the parsing of DOE files. Local attackers are able to exploit this issue to potentially execute arbitrary code on affected installations of Arena®. Exploiting the vulnerability requires opening a malicious DOE file.
A security issue exists due to improper handling of malformed CIP packets during fuzzing. The controller enters a hard fault with solid red Fault LED and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF019. To recover, clear the fault.
A security issue was found in the IPv6 stack in the Micro850 and Micro870 controllers when the controllers received multiple malformed packets during fuzzing. The controllers will go into recoverable fault with fault code 0xFE60. To recover the controller, clear the fault.
An authentication bypass security issue exists within FactoryTalk Historian Site Edition. By continually sending requests to the login endpoint, an attacker may obtain a valid authentication token.