Where
-Infinity
0
Severity
9.8
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to bypass authentication on affected installations of Triangle MicroWorks SCADA Data Gateway. Authentication is not required to exploit this vulnerability. The specific flaw exists due to the lack of user authentication. The issue results from missing authentication in the default system configuration. An attacker can leverage this vulnerability to execute arbitrary code in the context of root.

1 / 2
Source: ZDI
First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to execute arbitrary code on affected installations of Triangle MicroWorks SCADA Data Gateway. Authentication is not required to exploit this vulnerability. The specific flaw exists within the handling of data set elements. The issue results from the lack of proper validation of user-supplied data, which can result in a type confusion condition. An attacker can leverage this vulnerability to execute code in the context of SYSTEM.

1 / 2
First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

This vulnerability allows remote attackers to execute arbitrary code on affected installations of Triangle Microworks SCADA Data Gateway. Authentication is not required to exploit this vulnerability. The specific flaw exists with the handling of opcodes for GETFILEINFO. The issue results from the lack of proper validation of the length of user-supplied data prior to copying it to a fixed-length stack-based buffer. An attacker can leverage this vulnerablity to execute code in the context of SYSTEM.

1 / 2
Source: ZDI
First published (updated )
Severity
9.8
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to execute arbitrary code on affected installations of Triangle Microworks SCADA Data Gateway. Authentication is not required to exploit this vulnerability. The specific flaw exists with the handling of opcodes for GETFILEINFO. The issue results from the lack of proper validation of the length of user-supplied data prior to copying it to a fixed-length stack-based buffer. An attacker can leverage this vulnerablity to execute code in the context of SYSTEM.

Advisory
ZDI-20-547
Severity
9.8
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to execute arbitrary code on affected installations of Triangle Microworks SCADA Data Gateway. Authentication is not required to exploit this vulnerability. The specific flaw exists with the handling of opcodes for GETFILEINFO. The issue results from the lack of proper validation of the length of user-supplied data prior to copying it to a fixed-length stack-based buffer. An attacker can leverage this vulnerablity to execute code in the context of SYSTEM.

Severity
9.8
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to execute arbitrary code on affected installations of Triangle MicroWorks SCADA Data Gateway. Authentication is not required to exploit this vulnerability. The specific flaw exists within the handling of data set elements. The issue results from the lack of proper validation of user-supplied data, which can result in a type confusion condition. An attacker can leverage this vulnerability to execute code in the context of SYSTEM.

Advisory
ZDI-20-549
Severity
9.8
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to execute arbitrary code on affected installations of Triangle MicroWorks SCADA Data Gateway. Authentication is not required to exploit this vulnerability. The specific flaw exists within the handling of data set elements. The issue results from the lack of proper validation of user-supplied data, which can result in a type confusion condition. An attacker can leverage this vulnerability to execute code in the context of SYSTEM.

Severity
9.8
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to bypass authentication on affected installations of Triangle MicroWorks SCADA Data Gateway. Authentication is not required to exploit this vulnerability.

1 / 2
First published (updated )
Advisory
ZDI-23-1025
Severity
9.8
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to bypass authentication on affected installations of Triangle MicroWorks SCADA Data Gateway. Authentication is not required to exploit this vulnerability.

1 / 2
First published (updated )
Severity
8.8
Path Traversal
AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to execute arbitrary code on affected installations of Triangle MicroWorks SCADA Data Gateway. Although authentication is required to exploit this vulnerability, the existing authentication mechanism can be bypassed. The specific flaw exists within the Restore Workspace feature. The issue results from the lack of proper validation of a user-supplied path prior to using it in file operations. An attacker can leverage this vulnerability to execute code in the context of SYSTEM.

1 / 2
Source: ZDI
First published (updated )
Severity
7.8
Path Traversal
AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to create arbitrary files on affected installations of Triangle MicroWorks SCADA Data Gateway. User interaction is required to exploit this vulnerability in that the target must visit a malicious page or open a malicious file. The specific flaw exists within the processing of workspace files. The issue results from the lack of proper validation of a user-supplied path prior to using it in file operations. An attacker can leverage this vulnerability to create files in the context of Administrator.

1 / 2
Source: ZDI
First published (updated )
Severity
7.8
AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to create arbitrary files on affected installations of Triangle MicroWorks SCADA Data Gateway. User interaction is required to exploit this vulnerability in that the target must visit a malicious page or open a malicious file.

1 / 2
First published (updated )
Advisory
ZDI-23-1027
Severity
7.8
AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to create arbitrary files on affected installations of Triangle MicroWorks SCADA Data Gateway. User interaction is required to exploit this vulnerability in that the target must visit a malicious page or open a malicious file.

1 / 2
First published (updated )
Severity
7.5
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

This vulnerability allows remote attackers to disclose sensitive information on affected installations of Triangle MicroWorks SCADA Data Gateway. Authentication is not required to exploit this vulnerability. The specific flaw exists within the TmwCrypto class. The issue results from the usage of a hard-coded cryptograhic key and the usage of a hard-coded certificate. An attacker can leverage this vulnerability to disclose sensitive information.

1 / 2
Source: ZDI
First published (updated )
Severity
7.5
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

This vulnerability allows remote attackers to disclose sensitive information on affected installations of Triangle MicroWorks SCADA Data Gateway. Authentication is not required to exploit this vulnerability. The specific flaw exists with the handling of data set descriptors. The issue results from the lack of proper validation of user-supplied data which can result in a read past the end of an allocated structure. An attacker can leverage this in conjunction with other vulnerabilities to execute code in the context of SYSTEM.

1 / 2
Source: ZDI
First published (updated )
Severity
7.5
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

This vulnerability allows remote attackers to disclose sensitive information on affected installations of Triangle MicroWorks SCADA Data Gateway. Authentication is not required to exploit this vulnerability.

1 / 2
First published (updated )
Advisory
ZDI-23-1033
Severity
7.5
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

This vulnerability allows remote attackers to disclose sensitive information on affected installations of Triangle MicroWorks SCADA Data Gateway. Authentication is not required to exploit this vulnerability.

1 / 2
First published (updated )
Severity
7.2
AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to execute code on affected installations of Triangle MicroWorks SCADA Data Gateway. Although authentication is required to exploit this vulnerability, the existing authentication mechanism can be bypassed. The specific flaw exists within the configuration of the GTWWebMonitorService service. The path to the service executable contains spaces not surrounded by quotations. An attacker can leverage this vulnerability to execute arbitrary code in the context of root.

1 / 2
Source: ZDI
First published (updated )
Severity
7.2
Path Traversal
AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to create arbitrary files on affected installations of Triangle MicroWorks SCADA Data Gateway. Although authentication is required to exploit this vulnerability, the existing authentication mechanism can be bypassed. The specific flaw exists within the creation of event logs. The issue results from the lack of proper validation of a user-supplied path prior to using it in file operations. An attacker can leverage this in conjunction with other vulnerabilities to execute code in the context of root.

1 / 2
Source: ZDI
First published (updated )
Severity
7.2
Malicious File Upload
AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to execute arbitrary code on affected installations of Triangle MicroWorks SCADA Data Gateway. Although authentication is required to exploit this vulnerability, the existing authentication mechanism can be bypassed. The specific flaw exists within the trusted certification feature. The issue lies in the handling of the OpcUaSecurityCertificateAuthorityTrustDir variable, which allows an arbitrary file write with attacker-controlled data. An attacker can leverage this vulnerability to execute code in the context of SYSTEM.

1 / 2
Source: ZDI
First published (updated )
Severity
7.2
AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to execute arbitrary code on affected installations of Triangle MicroWorks SCADA Data Gateway. Authentication is required to exploit this vulnerability. The specific flaw exists within the handling of DbasSectorFileToExecuteOnReset parameter. The issue results from an exposed dangerous function. An attacker can leverage this vulnerability to execute code in the context of SYSTEM.

1 / 2
Source: ZDI
First published (updated )
Severity
7.2
AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to execute arbitrary code on affected installations of Triangle MicroWorks SCADA Data Gateway. Although authentication is required to exploit this vulnerability, the existing authentication mechanism can be bypassed.

1 / 2
First published (updated )
Advisory
ZDI-23-450
Severity
7.2
AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to execute arbitrary code on affected installations of Triangle MicroWorks SCADA Data Gateway. Although authentication is required to exploit this vulnerability, the existing authentication mechanism can be bypassed.

1 / 2
First published (updated )
Severity
7.2
AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to execute arbitrary code on affected installations of Triangle MicroWorks SCADA Data Gateway. Although authentication is required to exploit this vulnerability, the existing authentication mechanism can be bypassed.

1 / 2
First published (updated )
Advisory
ZDI-23-1031
Severity
7.2
AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to execute arbitrary code on affected installations of Triangle MicroWorks SCADA Data Gateway. Authentication is required to exploit this vulnerability.

1 / 2
First published (updated )
Severity
7.2
AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to execute arbitrary code on affected installations of Triangle MicroWorks SCADA Data Gateway. Although authentication is required to exploit this vulnerability, the existing authentication mechanism can be bypassed.

1 / 2
First published (updated )
Severity
7.2
AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to execute arbitrary code on affected installations of Triangle MicroWorks SCADA Data Gateway. Authentication is required to exploit this vulnerability.

1 / 2
First published (updated )
Advisory
ZDI-23-1036
Severity
7.2
AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to execute code on affected installations of Triangle MicroWorks SCADA Data Gateway. Although authentication is required to exploit this vulnerability, the existing authentication mechanism can be bypassed.

1 / 2
First published (updated )
Advisory
ZDI-23-1032
Severity
7.2
AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to execute code on affected installations of Triangle MicroWorks SCADA Data Gateway. Although authentication is required to exploit this vulnerability, the existing authentication mechanism can be bypassed.

1 / 2
First published (updated )
Severity
7.2
AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to create arbitrary files on affected installations of Triangle MicroWorks SCADA Data Gateway. Although authentication is required to exploit this vulnerability, the existing authentication mechanism can be bypassed.

1 / 2
First published (updated )
Advisory
ZDI-23-1028

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.
© 2026 SecAlerts Pty Ltd.
ABN: 70 645 966 203, ACN: 645 966 203