Where
AND
-Infinity
0
Severity
7.2
CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H

AVEVA System Platform versions 2017 through 2020 R2 P01 does not verify, or incorrectly verifies, the cryptographic signature for data.

Remedy

AVEVA recommends organizations evaluate the impact of these vulnerabilities based on their operational environment, architecture, and product implementation. AutoBuild service is intended to be used only on the GR Node of System Platform during configuration. If the AutoBuild service is enabled on any Runtime nodes, it should be disabled. Furthermore, if the AutoBuild functionality is not used on the GR Node, the AutoBuild service can be disabled on the GR Node as an alternative mitigation that does not require patching. AVEVA recommends users who need to continually use the AutoBuild functionality and cannot disable it in System Platform Versions 2017 through 2020 R2 P01 (inclusive) are affected by the vulnerabilities and should first upgrade to one of the System Platform versions listed below, then apply the corresponding security update: System Platform 2020 R2 P01, 2020 R2, 2020: Apply AVEVA Communication Drivers Pack 2020 R2.1 System Platform 2017 U3 SP1 P01: First apply AVEVA Communication Drivers Pack 2020 R2 AVEVA notes that Activated Licensing is required to apply AVEVA Communication Drivers Pack 2020 R2 on top of System Platform 2017 U3 SP1 P01. For information on AVEVA license compatibility, please contact AVEVA Customer Support. Then apply AVEVA Communication Drivers Pack 2020 R2.1 Please see AVEVA’s security bulletin AVEVA-2021-002 for more information.
First published (updated )
Severity
7.2
CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H

AVEVA System Platform versions 2017 through 2020 R2 P01 does not properly verify that the source of data or communication is valid.

Remedy

AVEVA recommends organizations evaluate the impact of these vulnerabilities based on their operational environment, architecture, and product implementation. AutoBuild service is intended to be used only on the GR Node of System Platform during configuration. If the AutoBuild service is enabled on any Runtime nodes, it should be disabled. Furthermore, if the AutoBuild functionality is not used on the GR Node, the AutoBuild service can be disabled on the GR Node as an alternative mitigation that does not require patching. AVEVA recommends users who need to continually use the AutoBuild functionality and cannot disable it in System Platform Versions 2017 through 2020 R2 P01 (inclusive) are affected by the vulnerabilities and should first upgrade to one of the System Platform versions listed below, then apply the corresponding security update: System Platform 2020 R2 P01, 2020 R2, 2020: Apply AVEVA Communication Drivers Pack 2020 R2.1 System Platform 2017 U3 SP1 P01: First apply AVEVA Communication Drivers Pack 2020 R2 AVEVA notes that Activated Licensing is required to apply AVEVA Communication Drivers Pack 2020 R2 on top of System Platform 2017 U3 SP1 P01. For information on AVEVA license compatibility, please contact AVEVA Customer Support. Then apply AVEVA Communication Drivers Pack 2020 R2.1 Please see AVEVA’s security bulletin AVEVA-2021-002 for more information.
First published (updated )
Severity
7.2
Path Traversal
CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H

AVEVA System Platform versions 2017 through 2020 R2 P01 uses external input to construct a pathname that is intended to identify a file or directory that is located underneath a restricted parent directory, but the software does not properly neutralize special elements within the pathname that can cause the pathname to resolve to a location that is outside of the restricted directory.

Remedy

AVEVA recommends organizations evaluate the impact of these vulnerabilities based on their operational environment, architecture, and product implementation. AutoBuild service is intended to be used only on the GR Node of System Platform during configuration. If the AutoBuild service is enabled on any Runtime nodes, it should be disabled. Furthermore, if the AutoBuild functionality is not used on the GR Node, the AutoBuild service can be disabled on the GR Node as an alternative mitigation that does not require patching. AVEVA recommends users who need to continually use the AutoBuild functionality and cannot disable it in System Platform Versions 2017 through 2020 R2 P01 (inclusive) are affected by the vulnerabilities and should first upgrade to one of the System Platform versions listed below, then apply the corresponding security update: System Platform 2020 R2 P01, 2020 R2, 2020: Apply AVEVA Communication Drivers Pack 2020 R2.1 System Platform 2017 U3 SP1 P01: First apply AVEVA Communication Drivers Pack 2020 R2 AVEVA notes that Activated Licensing is required to apply AVEVA Communication Drivers Pack 2020 R2 on top of System Platform 2017 U3 SP1 P01. For information on AVEVA license compatibility, please contact AVEVA Customer Support. Then apply AVEVA Communication Drivers Pack 2020 R2.1 Please see AVEVA’s security bulletin AVEVA-2021-002 for more information.
First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

AVEVA System Platform versions 2017 through 2020 R2 P01 does not perform any authentication for functionality that requires a provable user identity.

Remedy

AVEVA recommends organizations evaluate the impact of these vulnerabilities based on their operational environment, architecture, and product implementation. AutoBuild service is intended to be used only on the GR Node of System Platform during configuration. If the AutoBuild service is enabled on any Runtime nodes, it should be disabled. Furthermore, if the AutoBuild functionality is not used on the GR Node, the AutoBuild service can be disabled on the GR Node as an alternative mitigation that does not require patching. AVEVA recommends users who need to continually use the AutoBuild functionality and cannot disable it in System Platform Versions 2017 through 2020 R2 P01 (inclusive) are affected by the vulnerabilities and should first upgrade to one of the System Platform versions listed below, then apply the corresponding security update: System Platform 2020 R2 P01, 2020 R2, 2020: Apply AVEVA Communication Drivers Pack 2020 R2.1 System Platform 2017 U3 SP1 P01: First apply AVEVA Communication Drivers Pack 2020 R2 AVEVA notes that Activated Licensing is required to apply AVEVA Communication Drivers Pack 2020 R2 on top of System Platform 2017 U3 SP1 P01. For information on AVEVA license compatibility, please contact AVEVA Customer Support. Then apply AVEVA Communication Drivers Pack 2020 R2.1 Please see AVEVA’s security bulletin AVEVA-2021-002 for more information.
First published (updated )
Severity
7.5
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

An exception is thrown from a function in AVEVA System Platform versions 2017 through 2020 R2 P01, but it is not caught, which may cause a denial-of-service condition.

Remedy

AVEVA recommends organizations evaluate the impact of these vulnerabilities based on their operational environment, architecture, and product implementation. AutoBuild service is intended to be used only on the GR Node of System Platform during configuration. If the AutoBuild service is enabled on any Runtime nodes, it should be disabled. Furthermore, if the AutoBuild functionality is not used on the GR Node, the AutoBuild service can be disabled on the GR Node as an alternative mitigation that does not require patching. AVEVA recommends users who need to continually use the AutoBuild functionality and cannot disable it in System Platform Versions 2017 through 2020 R2 P01 (inclusive) are affected by the vulnerabilities and should first upgrade to one of the System Platform versions listed below, then apply the corresponding security update: System Platform 2020 R2 P01, 2020 R2, 2020: Apply AVEVA Communication Drivers Pack 2020 R2.1 System Platform 2017 U3 SP1 P01: First apply AVEVA Communication Drivers Pack 2020 R2 AVEVA notes that Activated Licensing is required to apply AVEVA Communication Drivers Pack 2020 R2 on top of System Platform 2017 U3 SP1 P01. For information on AVEVA license compatibility, please contact AVEVA Customer Support. Then apply AVEVA Communication Drivers Pack 2020 R2.1 Please see AVEVA’s security bulletin AVEVA-2021-002 for more information.
First published (updated )
Severity
8.8
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H

AVEVA Wonderware System Platform 2017 Update 2 and prior uses an ArchestrA network user account for authentication of system processes and inter-node communications. A user with low privileges could make use of an API to obtain the credentials for this account.

First published (updated )

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.