-Infinity
0
Severity
10
AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H

A remote unauthenticated attacker may use default certificates to generate JWT Tokens and gain full access to the tool and all connected devices.

First published (updated )
Severity
10
AV:N/AC:L/Au:N/C:C/I:C/A:C

The Linux Console on the WAGO I/O System 758 model 758-870, 758-874, 758-875, and 758-876 Industrial PC (IPC) devices has a default password of wago for the (1) root and (2) admin accounts, (3) a default password of user for the user account, and (4) a default password of guest for the guest account, which makes it easier for remote attackers to obtain login access via a TELNET session, a different vulnerability than CVE-2012-3013.

First published (updated )
Severity
10
AV:N/AC:L/Au:N/C:C/I:C/A:C

WAGO I/O System 758 model 758-870, 758-874, 758-875, and 758-876 Industrial PC (IPC) devices have default passwords for unspecified Web Based Management accounts, which makes it easier for remote attackers to obtain administrative access via a TCP session.

First published (updated )
Severity
10
Buffer Overflow
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

An exploitable stack buffer overflow vulnerability exists in the command line utility getcouplerdetails of WAGO PFC200 Firmware versions 03.01.07(13) and 03.00.39(12), and WAGO PFC100 Firmware version 03.00.39(12). A specially crafted set of packets sent to the iocheckd service "I/O-Check" can cause a stack buffer overflow in the sub-process getcouplerdetails, resulting in code execution. An attacker can send unauthenticated packets to trigger this vulnerability.

First published (updated )
Severity
10
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

WAGO IO 750-849 01.01.27 and WAGO IO 750-881 01.02.05 do not contain privilege separation.

First published (updated )
Severity
10
OS Command Injection
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

The reported vulnerability allows an attacker who has network access to the device to execute code with specially crafted packets in WAGO Series PFC 100 (750-81xx/xxx-xxx), Series PFC 200 (750-82xx/xxx-xxx), Series Wago Touch Panel 600 Standard Line (762-4xxx), Series Wago Touch Panel 600 Advanced Line (762-5xxx), Series Wago Touch Panel 600 Marine Line (762-6xxx) with firmware versions <=FW10.

Remedy

The I/O-Check service protocol is only needed during installation and commissioning, not during normal operations. It is highly recommended to disable the I/O-Check service after commissioning. This is the easiest and securest way to protect your device from the listed vulnerabilities. Regardless to the action described above, the vulnerability has been fixed in FW11, released in December 2017.
First published (updated )
Severity
10
Buffer Overflow
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

An exploitable heap buffer overflow vulnerability exists in the iocheckd service ''I/O-Chec'' functionality of WAGO PFC 200 Firmware version 03.01.07(13) and 03.00.39(12), and WAGO PFC100 Firmware version 03.00.39(12). A specially crafted set of packets can cause a heap buffer overflow, potentially resulting in code execution. An attacker can send unauthenticated packets to trigger this vulnerability.

First published (updated )
Severity
10
Buffer Overflow
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

An exploitable stack buffer overflow vulnerability exists in the iocheckd service ''I/O-Check'' functionality of WAGO PFC200 Firmware version 03.01.07(13), WAGO PFC200 Firmware version 03.00.39(12) and WAGO PFC100 Firmware version 03.00.39(12). A specially crafted set of packets can cause a stack buffer overflow, resulting in code execution. An attacker can send unauthenticated packets to trigger this vulnerability.

First published (updated )
Severity
10
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

In multiple managed switches by WAGO in different versions without authorization and with specially crafted packets it is possible to create users.

Remedy

The Web-Based Management is only needed during installation and commissioning, not during normal operations. It is recommended to disable the web server after commissioning. The Command Line Interface (CLI) is an alternative for commissioning the device. This is the easiest and securest way to protect your device from the listed vulnerabilities. Regardless of the action described above, the vulnerabilities are fixed with following firmware releases: Item number [FW version] 0852-0303 (HW < 3)* [V1.2.5.S0] Detailed information about the hardware version is described in the installation guide. 0852-0303 (HW >=3)* [V1.2.3.S1] Detailed information about the hardware version is described in the installation guide. 0852-1305 [V1.1.8.S0] 0852-1505 [V1.1.7.S0] 0852-1305/000-001 [V1.1.4.S0] 0852-1505/000-001 [V1.1.4.S0]
First published (updated )
Severity
10
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

WAGO 852-303 before FW06, 852-1305 before FW06, and 852-1505 before FW03 devices contain hardcoded private keys for the SSH daemon. The fingerprint of the SSH host key from the corresponding SSH daemon matches the embedded private key.

First published (updated )
Severity
10
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

WAGO 852-303 before FW06, 852-1305 before FW06, and 852-1505 before FW03 devices contain hardcoded users and passwords that can be used to login via SSH and TELNET.

First published (updated )
Severity
9.8
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

An unauthenticated remote attacker can abuse unsafe sscanf calls within the checkcookie() function to write arbitrary data into fixed-size stack buffers which leads to full device compromise.

First published (updated )
Severity
9.8
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

An unauthenticated remote attacker can abuse unsafe sscanf calls within the checkaccount() function to write arbitrary data into fixed-size stack buffers which leads to full device compromise.

First published (updated )
Severity
9.8
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

WAGO 750-8212 PFC200 G2 2ETH RS firmware contains a privilege escalation vulnerability that allows attackers to manipulate user session cookies. Attackers can modify the cookie's 'name' and 'roles' parameters to elevate from ordinary user to administrative privileges without authentication.

First published (updated )
Severity
9.8
Buffer Overflow
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

An exploitable heap buffer overflow vulnerability exists in the iocheckd service "I/O-Check" functionality of WAGO PFC200 Firmware versions 03.01.07(13) and 03.00.39(12), and WAGO PFC100 Firmware version 03.00.39(12). A specially crafted set of packets can cause a heap buffer overflow, potentially resulting in code execution. An attacker can send unauthenticated packets to trigger this vulnerability.

First published (updated )
Severity
9.8
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

WAGO IO 750-849 01.01.27 and 01.02.05, WAGO IO 750-881, and WAGO IO 758-870 have weak credential management.

First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H

This vulnerability allows an attacker who has access to the WBM to read and write settings-parameters of the device by sending specifically constructed requests without authentication on multiple WAGO PLCs in firmware versions up to FW07.

Remedy

Update the device to the latest FW version.
First published (updated )
Severity
9.8
Buffer Overflow
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

eap.c in pppd in ppp 2.4.2 through 2.4.8 has an rhostname buffer overflow in the eaprequest and eapresponse functions.

1 / 3
First published (updated )
Severity
9.8
Buffer Overflow
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

An exploitable heap buffer overflow vulnerability exists in the iocheckd service I/O-Check functionality of WAGO PFC200 Firmware version 03.01.07(13), WAGO PFC200 Firmware version 03.00.39(12), and WAGO PFC100 Firmware version 03.00.39(12). A specially crafted set of packets can cause a heap buffer overflow, potentially resulting in code execution. An attacker can send unauthenticated packets to trigger this vulnerability.

First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

CODESYS V2 Web-Server before 1.1.9.20 has an Out-of-bounds Write.

First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

CODESYS V2 Web-Server before 1.1.9.20 has an Improperly Implemented Security Check.

First published (updated )
Severity
9.8
Buffer Overflow
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

CODESYS V2 runtime system SP before 2.4.7.55 has a Stack-based Buffer Overflow.

First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

CODESYS V2 Web-Server before 1.1.9.20 has Improper Access Control.

First published (updated )
Severity
9.8
Buffer Overflow
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

CODESYS V2 Web-Server before 1.1.9.20 has a Stack-based Buffer Overflow.

First published (updated )
Severity
9.8
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

The Web-GUI on WAGO Series 750-88x (750-330, 750-352, 750-829, 750-831, 750-852, 750-880, 750-881, 750-882, 750-884, 750-885, 750-889) and Series 750-87x (750-830, 750-849, 750-871, 750-872, 750-873) devices has undocumented service access.

First published (updated )
Severity
9.8
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

An Improper Authentication issue was discovered in WAGO PFC200 Series 3S CoDeSys Runtime versions 2.3.X and 2.4.X. An attacker can execute different unauthenticated remote operations because of the CoDeSys Runtime application, which is available via network by default on Port 2455. An attacker could execute some unauthenticated commands such as reading, writing, or deleting arbitrary files, or manipulate the PLC application during runtime by sending specially-crafted TCP packets to Port 2455.

First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

In WAGO I/O-Check Service in multiple products an attacker can send a specially crafted packet containing OS commands to crash the diagnostic tool and write memory.

1 / 2
First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

In CODESYS V3 products in all versions prior V3.5.16.0 containing the CmpUserMgr, the CODESYS Control runtime system stores the online communication passwords using a weak hashing algorithm. This can be used by a local attacker with low privileges to gain full control of the device.

First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

The configuration backend allows an unauthenticated user to write arbitrary data with root privileges to the storage, which could lead to unauthenticated remote code execution and full system compromise.

First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

The configuration backend of the web-based management can be used by unauthenticated users, although only authenticated users should be able to use the API. The vulnerability allows an unauthenticated attacker to read and set several device parameters that can lead to full compromise of the device.

First published (updated )

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.
© 2026 SecAlerts Pty Ltd.
ABN: 70 645 966 203, ACN: 645 966 203