-Infinity
0
Severity
4.6
AV:P/AC:L/PR:H/UI:N/S:U/C:L/I:H/A:N

Vulnerability in GE Vernova Enervista UR Setup on Windows.This issue affects Enervista: 8.6 and previous versions.

Remedy

The EnerVista URPC installation software versions prior to 8.70, used an incorrect method of loading the DLL (dynamic Link Library) file by referencing it relative to the location of the installation folder. If the system in which the software is installed gets compromised, an attacker could exploit this weakness and replace the legitimate DLL with a malicious file. The EnerVista UR Setup software installation has been upgraded to address this vulnerability.
First published (updated )
Severity
2.9
AV:P/AC:L/PR:H/UI:N/S:U/C:N/I:L/A:L

A vulnerability in GE Vernova Enervista UR Setup on Windows allows File Manipulation.This issue affects Enervista: 8.6 and prior versions.

Remedy

We strongly recommend that users with impacted firmware versions update their UR devices to UR firmware version 8.70, released in November 2025, to resolve these vulnerabilities. We also recommend upgrading the EnerVista UR Setup configuration tool to version 8.70 or greater. Enervista UR Setup software is backward compatible, users can upgrade it to version 8.70, independently of upgrading their UR IED to FW v870.
First published (updated )
Severity
7.5
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

ProficySCADA for iOS 5.0.25920 contains a denial of service vulnerability that allows attackers to crash the application by manipulating the password input field. Attackers can overwrite the password field with 257 bytes of repeated characters to trigger an application crash and prevent successful authentication.

First published (updated )
Severity
9.3
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

Improper Authentication vulnerability in GE Vernova Smallworld on Windows, Linux allows Authentication Abuse.This issue affects Smallworld: 5.3.3 and prior versions for Linux, and 5.3.4. and prior versions for Windows.

Remedy

GE Vernova recommends that users upgrade to the appropriate non-affected version listed above in accordance with their use case and architecture as this is the most complete method to address the Vulnerability. Also, users are strongly advised to follow the SDG instructions. The complete SDG can be found in the Smallworld Documentation. To obtain the latest version of SWMFS, please contact your local support representative at Customer Center.
First published (updated )
Severity
5.3
Path Traversal
CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:L/VI:L/VA:L/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability in GE Vernova Smallworld on Windows, Linux allows File Manipulation.This issue affects Smallworld: 5.3.5. and previous versions.

Remedy

GE Vernova recommends that users upgrade to the appropriate non-affected version listed above in accordance with their use case and architecture, as this is the most complete method to address the Vulnerability. Also, users are strongly advised to follow the SDG instructions. The complete SDG can be found in the Smallworld Documentation. To obtain the latest version of SWMFS, please contact your local support representative at Customer Center.
First published (updated )
Severity
7.5
EPSS
0.02%
CVSS:4.0/AV:L/AC:H/AT:P/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:N/AU:X/R:X/V:X/RE:X/U:X

Improper Privilege Management vulnerability in GE Vernova S1 Agile Configuration Software on Windows allows Privilege Escalation.This issue affects S1 Agile Configuration Software: 3.1 and previous version.

Remedy

To resolve this issue and enhance security, during the S1 Agile application installation, we ensure only privileged users can access various folders used by the S1 Agile application. This ensures that S1 Agile files can not be edited or replaced by users without sufficient privileges on that computer. We would like to assert that this attack, if successful, can give “Administrator” privileges to the attacker on the computer, but the configured IEDs will not see any impact in their configuration or functionality. The RBAC (‘Role-Based Access Control’) on the IED remains unimpacted. We strongly recommend customers to upgrade to the latest software version available. Software version 3.1.1 is released for customer usage in January 2025.
First published (updated )
Severity
5.9
Path Traversal
CVSS:3.1/AV:A/AC:H/PR:L/UI:N/S:U/C:L/I:H/A:L

Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability in GE Vernova WorkstationST on Windows (EGD Configuration Server modules) allows Path Traversal.This issue affects WorkstationST: WorkstationST V07.10.10C and earlier.

First published (updated )
Severity
6.1
EPSS
0.01%
AV:A/AC:L/PR:H/UI:N/S:U/C:N/I:H/A:H

Insufficient Verification of Data Authenticity vulnerability in GE Vernova UR IED family devices allows an authenticated user to install a modified firmware. The firmware signature verification is enforced only on the client-side dedicated software Enervista UR Setup, allowing the integration check to be bypassed.

First published (updated )
Severity
8.3
EPSS
0.03%
AV:A/AC:L/PR:N/UI:N/S:U/C:L/I:H/A:H

Missing Authentication for Critical Function vulnerability in GE Vernova Enervista UR Setup application allows Authentication Bypass due to a missing SSH server authentication. Since the client connection is not authenticated, an attacker may perform a man-in-the-middle attack on the network.

First published (updated )
Severity
8
EPSS
0.02%
AV:L/AC:L/PR:N/UI:N/S:U/C:L/I:H/A:H

Use of Hard-coded Credentials vulnerability in GE Vernova EnerVista UR Setup allows Privilege Escalation. The local user database is encrypted using an hardcoded password retrievable by an attacker analyzing the application code.

First published (updated )
Severity
8
EPSS
0.03%
AV:L/AC:L/PR:N/UI:N/S:U/C:L/I:H/A:H

CWE-282 "Improper Ownership Management" in GE Vernova EnerVista UR Setup allows Authentication Bypass.  The software's startup authentication can be disabled by altering a Windows registry setting that any user can modify.

First published (updated )
Severity
6.1
EPSS
0.03%
AV:A/AC:L/PR:N/UI:N/S:C/C:L/I:N/A:L

A CWE-15 "External Control of System or Configuration Setting" in GE Vernova UR IED family devices from version 7.0 up to 8.60 allows an attacker to provide input that establishes a TCP connection through a port forwarding. The lack of the IP address and port validation may allow the attacker to bypass firewall rules or to send malicious traffic in the network.

First published (updated )
Severity
7.5
EPSS
0.06%
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

KEPServerEX does not properly validate certificates from clients which may allow unauthenticated users to connect.

Remedy

PTC has released and recommends users to update to the following versions: * KEPServerEX should upgrade to v6.15 or later * ThingWorx Kepware Server should upgrade to v6.15 or later * ThingWorx Industrial Connectivity should upgrade to ThingWorx Kepware Server v6.15 or later * OPC-Aggregator should upgrade to v6.15 or later * ThingWorx Kepware Edge: Upgrade to v1.8 or later Refer to secure configuration guide here https://www.ptc.com/en/support/refdoc/ThingWorx_Kepware_Server/6.15/ThingWorx%20Kepware%20Server%20Secure%20Deployment%20Guide If additional questions remain, please contact PTC Technical Support https://support.ptc.com/apps/case_logger_viewer/cs/auth/ssl/log For more information, see PTC's advisory https://www.ptc.com/en/support/article/CS405439 .
First published (updated )
Severity
9.1
EPSS
0.07%
Buffer Overflow
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H

KEPServerEX is vulnerable to a buffer overflow which may allow an attacker to crash the product being accessed or leak information.

Remedy

PTC has released and recommends users to update to the following versions: * KEPServerEX should upgrade to v6.15 or later * ThingWorx Kepware Server should upgrade to v6.15 or later * ThingWorx Industrial Connectivity should upgrade to ThingWorx Kepware Server v6.15 or later * OPC-Aggregator should upgrade to v6.15 or later * ThingWorx Kepware Edge: Upgrade to v1.8 or later Refer to secure configuration guide here https://www.ptc.com/en/support/refdoc/ThingWorx_Kepware_Server/6.15/ThingWorx%20Kepware%20Server%20Secure%20Deployment%20Guide If additional questions remain, please contact PTC Technical Support https://support.ptc.com/apps/case_logger_viewer/cs/auth/ssl/log For more information, see PTC's advisory https://www.ptc.com/en/support/article/CS405439 .
First published (updated )
Severity
7.3
CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H

General Electric MiCOM S1 Agile is vulnerable to an attacker achieving code execution by placing malicious DLL files in the directory of the application.

Remedy

General Electric has released an update that resolves this vulnerability. No action is required by the customer. For more information, see General Electric's Security Advisory https://www.gegridsolutions.com/app/viewfiles.aspx .
First published (updated )
Severity
7.8
CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H

GE CIMPLICITY 2023 is by a process control vulnerability, which could allow a local attacker to insert malicious configuration files in the expected web server execution path to escalate privileges and gain full control of the HMI software.

Remedy

​GE Digital recommends users apply the following mitigations: * ​Update CIMPLICITY to v2023 SIM 1 https://digitalsupport.ge.com/s/article/CIMPLICITY-2023-SIM-1  (login is required) ​Please refer to GE Digital’s security bulletin https://digitalsupport.ge.com/s/article/GE-Digital-CIMPLICITY-Privilege-Escalation-Vulnerability  (login is required) for more information.
First published (updated )
Severity
9.8
Buffer Overflow, Input Validation, Use After Free
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

All versions of GE Digital CIMPLICITY that are not adhering to SDG guidance and accepting documents from untrusted sources are vulnerable to memory corruption issues due to insufficient input validation, including issues such as out-of-bounds reads and writes, use-after-free, stack-based buffer overflows, uninitialized pointers, and a heap-based buffer overflow. Successful exploitation could allow an attacker to execute arbitrary code.

First published (updated )
Severity
7.8
CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H

ToolboxST prior to version 7.10 is affected by a deserialization vulnerability. An attacker with local access to an HMI or who has conducted a social engineering attack on an authorized operator could execute code in a Toolbox user's context through the deserialization of an untrusted configuration file. Two CVSS scores have been provided to capture the differences between the two aforementioned attack vectors.

Customers are advised to update to ToolboxST 7.10 which can be found in ControlST 7.10. If unable to update at this time customers should ensure they are following the guidance laid out in GE Gas Power's Secure Deployment Guide (GEH-6839). Customers should ensure they are not running ToolboxST as an Administrative user.

Remedy

Update to ToolboxST version >=7.10 (available in ControlST >=7.10)
First published (updated )
Severity
9.8
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

This vulnerability allows remote attackers to execute arbitrary code on affected installations of Kepware KEPServerEX 6.11.718.0. Authentication is not required to exploit this vulnerability. The specific flaw exists within the handling of text encoding conversions. The issue results from the lack of proper validation of the length of user-supplied data prior to copying it to a stack-based buffer. An attacker can leverage this vulnerability to execute code in the context of SYSTEM. Was ZDI-CAN-18411.

1 / 2
First published (updated )
Severity
9.1
Buffer Overflow
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H

This vulnerability allows remote attackers to execute arbitrary code on affected installations of Kepware KEPServerEX 6.11.718.0. Authentication is not required to exploit this vulnerability. The specific flaw exists within the handling of text encoding conversions. The issue results from the lack of proper validation of the length of user-supplied data prior to copying it to a heap-based buffer. An attacker can leverage this vulnerability to execute code in the context of SYSTEM. Was ZDI-CAN-16486.

1 / 2
First published (updated )
Severity
9.8
Code Injection
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

GE Digital Proficy iFIX 2022, GE Digital Proficy iFIX v6.1, and GE Digital Proficy iFIX v6.5 are vulnerable to code injection, which may allow an attacker to insert malicious configuration files in the expected web server execution path and gain full control of the HMI software.

1 / 2
Source: MITRE

Remedy

GE Digital recommends that users upgrade to Proficy iFIX 2023. GE Digital recommends that any users choosing not to upgrade at this time apply the Simulation Drivers (SIMs) provided below to their earlier GE Digital Proficy iFIX versions (login required): * iFIX 2023 - select “Download Software Updates”: * iFIX 2022 SIM https://digitalsupport.ge.com/s/article/iFIX2022-WebSecurity-001   * iFIX v6.1 SIM https://digitalsupport.ge.com/s/article/iFIX61-WebSecurity-001   * iFIX v6.5 SIM https://digitalsupport.ge.com/s/article/iFIX65-WebSecurity-001  
First published (updated )
Severity
9.8
Integer Overflow
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

The affected products are vulnerable to an integer overflow or wraparound, which could  allow an attacker to crash the server and remotely execute arbitrary code.

1 / 2
Source: MITRE

Remedy

PTC has released the following resolutions: Update the impacted product to the latest version: ·         ThingWorx Edge C-SDK: 3.0.0 or later. ·         ThingWorx Edge MicroServer (EMS): v5.4.11 or later. ·         .NET-SDK: v5.8.5 or later. For Kepware products, the vulnerability is mitigated if the ThingWorx Interface is not enabled. To use the ThingWorx Interface without the vulnerability, update to the latest version of the product: ·         Kepware KEPServerEX: v6.13 or later. ·         ThingWorx Kepware Server (formerly ThingWorx Industrial Connectivity): v6.13 or later. ·         ThingWorx Kepware Edge: v1.6 or later. The following products should be upgraded as indicated or in accordance with the applicable organization’s recommendations if the ThingWorx Interface is in use: ·         Rockwell Automation KEPServer Enterprise: v6.13 or later. ·         GE Digital Industrial Gateway Server: v7.613 or later. For more information see PTC’s Customer Support Article .
First published (updated )
Severity
9.8
Out-of-bounds Read
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

The affected products are vulnerable to an improper validation of array index, which could allow an attacker to crash the server and remotely execute arbitrary code.

Remedy

PTC has released the following resolutions: Update the impacted product to the latest version: ·         ThingWorx Edge C-SDK: 3.0.0 or later. ·         ThingWorx Edge MicroServer (EMS): v5.4.11 or later. ·         .NET-SDK: v5.8.5 or later. For Kepware products, the vulnerability is mitigated if the ThingWorx Interface is not enabled. To use the ThingWorx Interface without the vulnerability, update to the latest version of the product: ·         Kepware KEPServerEX: v6.13 or later. ·         ThingWorx Kepware Server (formerly ThingWorx Industrial Connectivity): v6.13 or later. ·         ThingWorx Kepware Edge: v1.6 or later. The following products should be upgraded as indicated or in accordance with the applicable organization’s recommendations if the ThingWorx Interface is in use: ·         Rockwell Automation KEPServer Enterprise: v6.13 or later. ·         GE Digital Industrial Gateway Server: v7.613 or later. For more information see PTC’s Customer Support Article .
First published (updated )
Severity
7.5
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

An unauthorized user with network access and the decryption key could decrypt sensitive data, such as usernames and passwords.

1 / 2
Source: MITRE

Remedy

GE Digital released Proficy Historian 2023 https://www.ge.com/digital/applications/proficy-historian  to mitigate these vulnerabilities.  SIMs have also been released for all affected versions.Users can find out more about the vulnerabilities, how to obtain, and install the updates by visiting this notification document from GE Digital https://digitalsupport.ge.com/s/article/GE-Digital-Product-Security-Advisory-GED-23-01 .  
First published (updated )
Severity
8.1
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:H

An unauthorized user could possibly delete any file on the system.

1 / 2
Source: MITRE

Remedy

GE Digital released Proficy Historian 2023 https://www.ge.com/digital/applications/proficy-historian  to mitigate these vulnerabilities.  SIMs have also been released for all affected versions.Users can find out more about the vulnerabilities, how to obtain, and install the updates by visiting this notification document from GE Digital https://digitalsupport.ge.com/s/article/GE-Digital-Product-Security-Advisory-GED-23-01 .  
First published (updated )
Severity
7.5
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N

An unauthorized user could be able to read any file on the system, potentially exposing sensitive information.

1 / 2
Source: MITRE

Remedy

GE Digital released Proficy Historian 2023 https://www.ge.com/digital/applications/proficy-historian  to mitigate these vulnerabilities.  SIMs have also been released for all affected versions.Users can find out more about the vulnerabilities, how to obtain, and install the updates by visiting this notification document from GE Digital https://digitalsupport.ge.com/s/article/GE-Digital-Product-Security-Advisory-GED-23-01 .  
First published (updated )
Severity
7.5
Malicious File Upload
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:N

An unauthorized user could alter or write files with full control over the path and content of the file.

1 / 2
Source: MITRE

Remedy

GE Digital released Proficy Historian 2023 https://www.ge.com/digital/applications/proficy-historian  to mitigate these vulnerabilities.  SIMs have also been released for all affected versions.Users can find out more about the vulnerabilities, how to obtain, and install the updates by visiting this notification document from GE Digital https://digitalsupport.ge.com/s/article/GE-Digital-Product-Security-Advisory-GED-23-01 .  
First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Even if the authentication fails for local service authentication, the requested command could still execute regardless of authentication status.

First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

An issue was discovered on GE Grid Solutions MS3000 devices before 3.7.6.25p03.2.2.17p04.7p0. The debug port accessible via TCP (a qconn service) lacks access control.

First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

An issue was discovered in FC46-WebBridge on GE Grid Solutions MS3000 devices before 3.7.6.25p03.2.2.17p04.7p0. Direct access to the API is possible on TCP port 8888 via programs located in the cgi-bin folder without any authentication.

First published (updated )

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.