See how ge compares to other vendors in security performance
Vulnerability in GE Vernova Enervista UR Setup on Windows.This issue affects Enervista: 8.6 and previous versions.
A vulnerability in GE Vernova Enervista UR Setup on Windows allows File Manipulation.This issue affects Enervista: 8.6 and prior versions.
ProficySCADA for iOS 5.0.25920 contains a denial of service vulnerability that allows attackers to crash the application by manipulating the password input field. Attackers can overwrite the password field with 257 bytes of repeated characters to trigger an application crash and prevent successful authentication.
Improper Authentication vulnerability in GE Vernova Smallworld on Windows, Linux allows Authentication Abuse.This issue affects Smallworld: 5.3.3 and prior versions for Linux, and 5.3.4. and prior versions for Windows.
Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability in GE Vernova Smallworld on Windows, Linux allows File Manipulation.This issue affects Smallworld: 5.3.5. and previous versions.
Improper Privilege Management vulnerability in GE Vernova S1 Agile Configuration Software on Windows allows Privilege Escalation.This issue affects S1 Agile Configuration Software: 3.1 and previous version.
Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability in GE Vernova WorkstationST on Windows (EGD Configuration Server modules) allows Path Traversal.This issue affects WorkstationST: WorkstationST V07.10.10C and earlier.
Insufficient Verification of Data Authenticity vulnerability in GE Vernova UR IED family devices allows an authenticated user to install a modified firmware. The firmware signature verification is enforced only on the client-side dedicated software Enervista UR Setup, allowing the integration check to be bypassed.
Missing Authentication for Critical Function vulnerability in GE Vernova Enervista UR Setup application allows Authentication Bypass due to a missing SSH server authentication. Since the client connection is not authenticated, an attacker may perform a man-in-the-middle attack on the network.
Use of Hard-coded Credentials vulnerability in GE Vernova EnerVista UR Setup allows Privilege Escalation. The local user database is encrypted using an hardcoded password retrievable by an attacker analyzing the application code.
CWE-282 "Improper Ownership Management" in GE Vernova EnerVista UR Setup allows Authentication Bypass. The software's startup authentication can be disabled by altering a Windows registry setting that any user can modify.
A CWE-15 "External Control of System or Configuration Setting" in GE Vernova UR IED family devices from version 7.0 up to 8.60 allows an attacker to provide input that establishes a TCP connection through a port forwarding. The lack of the IP address and port validation may allow the attacker to bypass firewall rules or to send malicious traffic in the network.
KEPServerEX does not properly validate certificates from clients which may allow unauthenticated users to connect.
KEPServerEX is vulnerable to a buffer overflow which may allow an attacker to crash the product being accessed or leak information.
General Electric MiCOM S1 Agile is vulnerable to an attacker achieving code execution by placing malicious DLL files in the directory of the application.
GE CIMPLICITY 2023 is by a process control vulnerability, which could allow a local attacker to insert malicious configuration files in the expected web server execution path to escalate privileges and gain full control of the HMI software.
All versions of GE Digital CIMPLICITY that are not adhering to SDG guidance and accepting documents from untrusted sources are vulnerable to memory corruption issues due to insufficient input validation, including issues such as out-of-bounds reads and writes, use-after-free, stack-based buffer overflows, uninitialized pointers, and a heap-based buffer overflow. Successful exploitation could allow an attacker to execute arbitrary code.
ToolboxST prior to version 7.10 is affected by a deserialization vulnerability. An attacker with local access to an HMI or who has conducted a social engineering attack on an authorized operator could execute code in a Toolbox user's context through the deserialization of an untrusted configuration file. Two CVSS scores have been provided to capture the differences between the two aforementioned attack vectors.
Customers are advised to update to ToolboxST 7.10 which can be found in ControlST 7.10. If unable to update at this time customers should ensure they are following the guidance laid out in GE Gas Power's Secure Deployment Guide (GEH-6839). Customers should ensure they are not running ToolboxST as an Administrative user.
This vulnerability allows remote attackers to execute arbitrary code on affected installations of Kepware KEPServerEX 6.11.718.0. Authentication is not required to exploit this vulnerability. The specific flaw exists within the handling of text encoding conversions. The issue results from the lack of proper validation of the length of user-supplied data prior to copying it to a stack-based buffer. An attacker can leverage this vulnerability to execute code in the context of SYSTEM. Was ZDI-CAN-18411.
This vulnerability allows remote attackers to execute arbitrary code on affected installations of Kepware KEPServerEX 6.11.718.0. Authentication is not required to exploit this vulnerability. The specific flaw exists within the handling of text encoding conversions. The issue results from the lack of proper validation of the length of user-supplied data prior to copying it to a heap-based buffer. An attacker can leverage this vulnerability to execute code in the context of SYSTEM. Was ZDI-CAN-16486.
GE Digital Proficy iFIX 2022, GE Digital Proficy iFIX v6.1, and GE Digital Proficy iFIX v6.5 are vulnerable to code injection, which may allow an attacker to insert malicious configuration files in the expected web server execution path and gain full control of the HMI software.
The affected products are vulnerable to an integer overflow or wraparound, which could allow an attacker to crash the server and remotely execute arbitrary code.
The affected products are vulnerable to an improper validation of array index, which could allow an attacker to crash the server and remotely execute arbitrary code.
An unauthorized user with network access and the decryption key could decrypt sensitive data, such as usernames and passwords.
An unauthorized user could possibly delete any file on the system.
An unauthorized user could be able to read any file on the system, potentially exposing sensitive information.
An unauthorized user could alter or write files with full control over the path and content of the file.
Even if the authentication fails for local service authentication, the requested command could still execute regardless of authentication status.
An issue was discovered on GE Grid Solutions MS3000 devices before 3.7.6.25p03.2.2.17p04.7p0. The debug port accessible via TCP (a qconn service) lacks access control.
An issue was discovered in FC46-WebBridge on GE Grid Solutions MS3000 devices before 3.7.6.25p03.2.2.17p04.7p0. Direct access to the API is possible on TCP port 8888 via programs located in the cgi-bin folder without any authentication.