-Infinity
0
Severity
10
Buffer Overflow
AV:N/AC:L/Au:N/C:C/I:C/A:C

PRLicenseMgr.exe in the Proficy Server License Manager in GE Intelligent Platforms Proficy Plant Applications 5.0 and earlier allows remote attackers to cause a denial of service (memory corruption) or possibly execute arbitrary code via a crafted TCP session on port 12401.

First published (updated )
Severity
10
Buffer Overflow
AV:N/AC:L/Au:N/C:C/I:C/A:C

The Data Archiver service in GE Intelligent Platforms Proficy Historian 4.5 and earlier allows remote attackers to cause a denial of service (memory corruption) or possibly execute arbitrary code via a crafted session on TCP port 14000 to (1) ihDataArchiver.exe or (2) ihDataArchiverx64.exe.

First published (updated )
Severity
10
Buffer Overflow
AV:N/AC:L/Au:N/C:C/I:C/A:C

PRRDS.exe in the Proficy Remote Data Service in GE Intelligent Platforms Proficy Plant Applications 5.0 and earlier allows remote attackers to cause a denial of service (memory corruption) or possibly execute arbitrary code via a crafted TCP session on port 12299.

First published (updated )
Severity
10
Input Validation
AV:N/AC:L/Au:N/C:C/I:C/A:C

rifsrvd.exe in the Remote Interface Service in GE Intelligent Platforms Proficy Real-Time Information Portal 2.6 through 3.5 SP1 allows remote attackers to cause a denial of service (memory corruption and service crash) or possibly execute arbitrary code via long input data, a different vulnerability than CVE-2012-3021 and CVE-2012-3026.

First published (updated )
Severity
10
Input Validation
AV:N/AC:L/Au:N/C:C/I:C/A:C

rifsrvd.exe in the Remote Interface Service in GE Intelligent Platforms Proficy Real-Time Information Portal 2.6 through 3.5 SP1 allows remote attackers to cause a denial of service (memory corruption and service crash) or possibly execute arbitrary code via long input data, a different vulnerability than CVE-2012-3010 and CVE-2012-3026.

First published (updated )
Severity
10
Input Validation
AV:N/AC:L/Au:N/C:C/I:C/A:C

rifsrvd.exe in the Remote Interface Service in GE Intelligent Platforms Proficy Real-Time Information Portal 2.6 through 3.5 SP1 allows remote attackers to cause a denial of service (memory corruption and service crash) or possibly execute arbitrary code via long input data, a different vulnerability than CVE-2012-3010 and CVE-2012-3021.

First published (updated )
Severity
10
Buffer Overflow
AV:N/AC:L/Au:N/C:C/I:C/A:C

Multiple stack-based buffer overflows in GE Intelligent Platforms Proficy Applications before 4.4.1 SIM 101 and 5.x before 5.0 SIM 43 allow remote attackers to cause a denial of service (daemon crash) or possibly execute arbitrary code via crafted TCP message traffic to (1) PRProficyMgr.exe in Proficy Server Manager, (2) PRGateway.exe in Proficy Server Gateway, (3) PRRDS.exe in Proficy Remote Data Service, or (4) PRLicenseMgr.exe in Proficy Server License Manager.

First published (updated )
Severity
10
AV:N/AC:L/Au:N/C:P/I:N/A:N

GE Multilink ML800, ML1200, ML1600, and ML2400 switches with firmware 4.2.1 and earlier and Multilink ML810, ML3000, and ML3100 switches with firmware 5.2.0 and earlier use the same RSA private key across different customers' installations, which makes it easier for remote attackers to obtain the cleartext content of network traffic by reading this key from a firmware image and then sniffing the network.

Remedy

GE recommends users update switch firmware to the latest published version to resolve these vulnerabilities. The new firmware will enable new keys to be calculated and exchanged, resolve the slow data transfer and potential denial of service, and prevent the identified cross-site scripting vulnerabilities. The latest firmware is Version 5.3.2 for the ML800, ML1200, ML1600 and ML2400 and Version 5.3.2-3K for the ML810, ML3000, and ML3100. This firmware is available through the “Resources/Software” link in the product web sites at http://www.gedigitalenergy.com . This firmware is also available through the EnerVista Launchpad device management tool. GE recommends updating the switch over a serial connection to prevent an attacker from capturing the new key. Please refer to the GE advisory for specific information on how to install the firmware and change RSA key. The GE advisory is available at: https://www.gedigitalenergy.com/products/support/multilink/MLSB0415.pdf
First published (updated )
Severity
10
Path Traversal
AV:N/AC:L/Au:N/C:C/I:C/A:C

Absolute path traversal vulnerability in the download feature in FileDownloadServlet in GE Digital Energy MDS PulseNET and MDS PulseNET Enterprise before 3.1.5 allows remote attackers to read or delete arbitrary files via a full pathname.

First published (updated )
Severity
10
Buffer Overflow
AV:N/AC:L/Au:N/C:C/I:C/A:C

Stack-based buffer overflow in the Data Archiver service in GE Intelligent Platforms Proficy Historian before 3.5 SIM 17 and 4.x before 4.0 SIM 12 allows remote attackers to cause a denial of service (daemon crash) or possibly execute arbitrary code via crafted TCP message traffic.

First published (updated )
Severity
10
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H

General Electric (GE) Bently Nevada 3500/22M USB with firmware before 5.0 and Bently Nevada 3500/22M Serial have open ports, which makes it easier for remote attackers to obtain privileged access via unspecified vectors.

First published (updated )
Severity
10
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

General Electric (GE) Multilink ML800, ML1200, ML1600, and ML2400 switches with firmware before 5.5.0 and ML810, ML3000, and ML3100 switches with firmware before 5.5.0k have hardcoded credentials, which allows remote attackers to modify configuration settings via the web interface.

First published (updated )
Severity
10
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

GE Infinia/Infinia with Hawkeye 4 medical imaging systems all current versions are affected these devices use default or hard-coded credentials. Successful exploitation of this vulnerability may allow a remote attacker to bypass authentication and gain access to the affected devices.

First published (updated )
Severity
10
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Certain General Electric Renewable Energy products have a hidden feature for unauthenticated remote access to the device configuration shell. This affects iNET and iNET II before 8.3.0.

First published (updated )
Severity
9.8
CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H

The software contains a hard-coded password that could allow an attacker to take control of the merging unit using these hard-coded credentials on the MU320E (all firmware versions prior to v04A00.1).

First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

The software contains a hard-coded password it uses for its own inbound authentication or for outbound communication to external components on the Reason DR60 (all firmware versions prior to 02A04.1).

First published (updated )
Severity
9.8
Weak Encryption
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

A Weak Cryptography for Passwords issue was discovered in General Electric (GE) Multilin SR 750 Feeder Protection Relay, firmware versions prior to Version 7.47; SR 760 Feeder Protection Relay, firmware versions prior to Version 7.47; SR 469 Motor Protection Relay, firmware versions prior to Version 5.23; SR 489 Generator Protection Relay, firmware versions prior to Version 4.06; SR 745 Transformer Protection Relay, firmware versions prior to Version 5.23; SR 369 Motor Protection Relay, all firmware versions; Multilin Universal Relay, firmware Version 6.0 and prior versions; and Multilin URplus (D90, C90, B95), all versions. Ciphertext versions of user passwords were created with a non-random initialization vector leaving them susceptible to dictionary attacks. Ciphertext of user passwords can be obtained from the front LCD panel of affected products and through issued Modbus commands.

First published (updated )
Severity
9.8
Buffer Overflow
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

KEPServerEX: v6.0 to v6.9, ThingWorx Kepware Server: v6.8 and v6.9, ThingWorx Industrial Connectivity: All versions, OPC-Aggregator: All versions, Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server: v7.68.804 and v7.66, Software Toolbox TOP Server: All 6.x versions are vulnerable to a stack-based buffer overflow. Opening a specifically crafted OPC UA message could allow an attacker to crash the server and remotely execute code.

First published (updated )
Severity
9.8
AV:N/AC:L/Au:N/C:P/I:N/A:N

GE Fanuc Proficy Real-Time Information Portal 2.6 and earlier uses HTTP Basic Authentication, which transmits usernames and passwords in base64-encoded cleartext and allows remote attackers to steal the passwords and gain privileges.

First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

GE Grid Solutions Reason RT Clocks, RT430, RT431, and RT434, all firmware versions prior to 08A05. The device’s vulnerability in the web application could allow multiple unauthenticated attacks that could cause serious impact. The vulnerability may allow an unauthenticated attacker to execute arbitrary commands and send a request to a specific URL that could cause the device to become unresponsive. The unauthenticated attacker may change the password of the 'configuration' user account, allowing the attacker to modify the configuration of the device via the web interface using the new password. This vulnerability may also allow an unauthenticated attacker to bypass the authentication required to configure the device and reboot the system.

First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

GE Communicator, all versions prior to 4.0.517, contains two backdoor accounts with hardcoded credentials, which may allow control over the database. This service is inaccessible to attackers if Windows default firewall settings are used by the end user.

First published (updated )
Severity
9.8
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Java remote method invocation (RMI) input port in GE MDS PulseNET and MDS PulseNET Enterprise version 3.2.1 and prior may be exploited to allow unauthenticated users to launch applications and support remote code execution through web services.

First published (updated )
Severity
9.8
Buffer Overflow, Input Validation, Use After Free
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

All versions of GE Digital CIMPLICITY that are not adhering to SDG guidance and accepting documents from untrusted sources are vulnerable to memory corruption issues due to insufficient input validation, including issues such as out-of-bounds reads and writes, use-after-free, stack-based buffer overflows, uninitialized pointers, and a heap-based buffer overflow. Successful exploitation could allow an attacker to execute arbitrary code.

First published (updated )
Severity
9.8
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

GE GEMNet License server (EchoServer) all current versions are affected these devices use default or hard-coded credentials. Successful exploitation of this vulnerability may allow a remote attacker to bypass authentication and gain access to the affected devices.

First published (updated )
Severity
9.8
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

GE Centricity PACS RA1000, diagnostic image analysis, all current versions are affected these devices use default or hard-coded credentials. Successful exploitation of this vulnerability may allow a remote attacker to bypass authentication and gain access to the affected devices.

First published (updated )
Severity
9.8
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

GE Xeleris versions 1.0,1.1,2.1,3.0,3.1, medical imaging systems, all current versions are affected, these devices use default or hard-coded credentials. Successful exploitation of this vulnerability may allow a remote attacker to bypass authentication and gain access to the affected devices.

First published (updated )
Severity
9.8
Buffer Overflow
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

A Stack-based Buffer Overflow issue was discovered in GE D60 Line Distance Relay devices running firmware Version 7.11 and prior. Multiple stack-based buffer overflow vulnerabilities have been identified, which may allow remote code execution.

First published (updated )
Severity
9.8
Buffer Overflow
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

An Improper Restriction of Operations within the Bounds of a Memory Buffer issue was discovered in GE D60 Line Distance Relay devices running firmware Version 7.11 and prior. The SSH functions of the device are vulnerable to buffer overflow conditions that may allow a remote attacker to execute arbitrary code on the device.

First published (updated )
Severity
9.8
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

The affected product is vulnerable due to cleartext transmission of credentials seen in the CIMPLICITY network, which can be easily spoofed and used to log in to make operational changes to the system.

Remedy

Users are advised to refer to the Secure Deployment Guide on how to configure communication encryption. Users are encouraged to review the CIMPLICITY Windows Hardening Guide and Recommendations for further IPSEC configuration guidance found in the section titled “Appendix A IPSEC Configuration.” Users are encouraged to contact a GE representative to obtain the latest versions of CIMPLICITY.
First published (updated )
Severity
9.8
Malicious File Upload
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

GE UR IED firmware versions prior to version 8.1x supports upgrading firmware using UR Setup configuration tool – Enervista UR Setup. This UR Setup tool validates the authenticity and integrity of firmware file before uploading the UR IED. An illegitimate user could upgrade firmware without appropriate privileges. The weakness is assessed, and mitigation is implemented in firmware Version 8.10.

Remedy

GE strongly recommends users with impacted firmware versions update their UR devices to UR firmware Version 8.10, or greater to resolve these vulnerabilities. GE provides additional mitigations and information about these vulnerabilities in GE Publication Number: GES-2021-004 (login required).
First published (updated )

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.
© 2026 SecAlerts Pty Ltd.
ABN: 70 645 966 203, ACN: 645 966 203