Missing Authentication for Critical Function vulnerability in GE Vernova Enervista UR Setup application allows Authentication Bypass due to a missing SSH server authentication. Since the client connection is not authenticated, an attacker may perform a man-in-the-middle attack on the network.

First published (updated )
Severity
6.1
EPSS
0.01%
AV:A/AC:L/PR:H/UI:N/S:U/C:N/I:H/A:H

Insufficient Verification of Data Authenticity vulnerability in GE Vernova UR IED family devices allows an authenticated user to install a modified firmware. The firmware signature verification is enforced only on the client-side dedicated software Enervista UR Setup, allowing the integration check to be bypassed.

First published (updated )
Severity
8
EPSS
0.03%
AV:L/AC:L/PR:N/UI:N/S:U/C:L/I:H/A:H

CWE-282 "Improper Ownership Management" in GE Vernova EnerVista UR Setup allows Authentication Bypass.  The software's startup authentication can be disabled by altering a Windows registry setting that any user can modify.

First published (updated )
Severity
8
EPSS
0.02%
AV:L/AC:L/PR:N/UI:N/S:U/C:L/I:H/A:H

Use of Hard-coded Credentials vulnerability in GE Vernova EnerVista UR Setup allows Privilege Escalation. The local user database is encrypted using an hardcoded password retrievable by an attacker analyzing the application code.

First published (updated )
Severity
6.1
EPSS
0.03%
AV:A/AC:L/PR:N/UI:N/S:C/C:L/I:N/A:L

A CWE-15 "External Control of System or Configuration Setting" in GE Vernova UR IED family devices from version 7.0 up to 8.60 allows an attacker to provide input that establishes a TCP connection through a port forwarding. The lack of the IP address and port validation may allow the attacker to bypass firewall rules or to send malicious traffic in the network.

First published (updated )
Severity
9.8
Buffer Overflow, Input Validation, Use After Free
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

All versions of GE Digital CIMPLICITY that are not adhering to SDG guidance and accepting documents from untrusted sources are vulnerable to memory corruption issues due to insufficient input validation, including issues such as out-of-bounds reads and writes, use-after-free, stack-based buffer overflows, uninitialized pointers, and a heap-based buffer overflow. Successful exploitation could allow an attacker to execute arbitrary code.

First published (updated )
Severity
6.8
Input Validation
CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

A restricted desktop environment escape vulnerability exists in the Kiosk Mode functionality of affected devices. Specially crafted inputs can allow the user to escape the restricted environment, resulting in access to the underlying operating system. Affected devices include the following GE Ultrasound Products: Vivid products - all versions; LOGIQ - all versions not including LOGIQ 100 Pro; Voluson - all versions; Versana Essential - all versions; Invenia ABUS Scan station - all versions; Venue - all versions not including Venue 40 R1-3 and Venue 50 R4-5

First published (updated )
Severity
7.8
Input Validation
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

In GE PACSystems RX3i CPE305/310 version 9.20 and prior, RX3i CPE330 version 9.21 and prior, RX3i CPE 400 version 9.30 and prior, PACSystems RSTi-EP CPE 100 all versions, and PACSystems CPU320/CRU320 RXi all versions, the device does not properly validate input, which could allow a remote attacker to send specially crafted packets causing the device to become unavailable.

First published (updated )
Severity
9.8
Buffer Overflow
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

A Stack-based Buffer Overflow issue was discovered in GE D60 Line Distance Relay devices running firmware Version 7.11 and prior. Multiple stack-based buffer overflow vulnerabilities have been identified, which may allow remote code execution.

First published (updated )
Severity
9.8
Buffer Overflow
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

An Improper Restriction of Operations within the Bounds of a Memory Buffer issue was discovered in GE D60 Line Distance Relay devices running firmware Version 7.11 and prior. The SSH functions of the device are vulnerable to buffer overflow conditions that may allow a remote attacker to execute arbitrary code on the device.

First published (updated )
Severity
7.5
Path Traversal
AV:N/AC:L/Au:N/C:P/I:P/A:P

Directory traversal vulnerability in gefebt.exe in the WebView CimWeb components in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY through 8.2 SIM 24, and Proficy Process Systems with CIMPLICITY, allows remote attackers to execute arbitrary code via a crafted HTTP request, aka ZDI-CAN-1622.

First published (updated )
Severity
7.5
Path Traversal
AV:N/AC:L/Au:N/C:P/I:P/A:P

Directory traversal vulnerability in CimWebServer.exe (aka the WebView component) in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY before 8.2 SIM 24, and Proficy Process Systems with CIMPLICITY, allows remote attackers to execute arbitrary code via a crafted message to TCP port 10212, aka ZDI-CAN-1623.

1 / 2
First published (updated )
Severity
5.3
AV:N/AC:L/Au:N/C:N/I:P/A:N

SSH 1.2.25, 1.2.23, and other versions, when used in in CBC (Cipher Block Chaining) or CFB (Cipher Feedback 64 bits) modes, allows remote attackers to insert arbitrary data into an existing stream between an SSH client and server by using a known plaintext attack and computing a valid CRC-32 checksum for the packet, aka the "SSH insertion attack."

First published (updated )
Severity
7.5
Infoleak, Weak Encryption
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

A flaw was found in the way the DES/3DES cipher was used as part of the TLS/SSL protocol. A man-in-the-middle attacker could use this flaw to recover some plaintext data by capturing large amounts of encrypted traffic between TLS/SSL server and client if the communication used a DES/3DES based ciphersuite.

1 / 5

Remedy

1.SSL/TLS configurations should prefer AES over DES. Versions of OpenSSL shipped with Red Hat Enterprise Linux 6 and 7 already do so. In the version of OpenSSL shipped with Red Hat Enterprise Linux 5, 3DES is listed below the AES-256 cipher and above the AES-128 cipher, therefore AES-256 based ciphersuite should not be disabled on the server. 2. Servers using OpenSSL, should not disable AES-128 and AES-256 ciphersuites. Versions of Apache shipped with Red Hat Enterprise Linux use the default cipher string, in which AES is preferred over DES/3DES based ciphersuites. For JBoss Middleware, and Java mitigations, please review this knowledge base article: https://access.redhat.com/articles/2598471 This can be mitigated on OpenShift Container Platform (OCP) by disabling the vulnerable TLS cipher suite in the applicable component. TLS configuration options for OCP are described here: https://access.redhat.com/articles/5348961
First published (updated )
Severity
5.9
Weak Encryption
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

A new attack was discovered against TLS that allows an attacker to recover a limited amount of plaintext from a TLS connection when RC4 encryption is used. The attacks arise from statistical flaws in the keystream generated by the RC4 algorithm which become apparent in TLS ciphertexts when the same plaintext is repeatedly encrypted at a fixed location across many TLS sessions.

Reference:

http://www.isg.rhul.ac.uk/tls/ http://blog.cryptographyengineering.com/2013/03/attack-of-week-rc4-is-kind-of-broken-in.html

1 / 2
First published (updated )
Severity
6.7
CVSS:3.1/AV:L/AC:H/PR:H/UI:N/S:C/C:H/I:L/A:L

An issue was discovered in General Electric (GE) Proficy HMI/SCADA iFIX Version 5.8 SIM 13 and prior versions, Proficy HMI/SCADA CIMPLICITY Version 9.0 and prior versions, and Proficy Historian Version 6.0 and prior versions. An attacker may be able to retrieve user passwords if he or she has access to an authenticated session.

First published (updated )
Severity
4.6
AV:P/AC:L/PR:H/UI:N/S:U/C:L/I:H/A:N

Vulnerability in GE Vernova Enervista UR Setup on Windows.This issue affects Enervista: 8.6 and previous versions.

Remedy

The EnerVista URPC installation software versions prior to 8.70, used an incorrect method of loading the DLL (dynamic Link Library) file by referencing it relative to the location of the installation folder. If the system in which the software is installed gets compromised, an attacker could exploit this weakness and replace the legitimate DLL with a malicious file. The EnerVista UR Setup software installation has been upgraded to address this vulnerability.
First published (updated )
Severity
2.9
AV:P/AC:L/PR:H/UI:N/S:U/C:N/I:L/A:L

A vulnerability in GE Vernova Enervista UR Setup on Windows allows File Manipulation.This issue affects Enervista: 8.6 and prior versions.

Remedy

We strongly recommend that users with impacted firmware versions update their UR devices to UR firmware version 8.70, released in November 2025, to resolve these vulnerabilities. We also recommend upgrading the EnerVista UR Setup configuration tool to version 8.70 or greater. Enervista UR Setup software is backward compatible, users can upgrade it to version 8.70, independently of upgrading their UR IED to FW v870.
First published (updated )
Severity
7.5
EPSS
0.06%
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

KEPServerEX does not properly validate certificates from clients which may allow unauthenticated users to connect.

Remedy

PTC has released and recommends users to update to the following versions: * KEPServerEX should upgrade to v6.15 or later * ThingWorx Kepware Server should upgrade to v6.15 or later * ThingWorx Industrial Connectivity should upgrade to ThingWorx Kepware Server v6.15 or later * OPC-Aggregator should upgrade to v6.15 or later * ThingWorx Kepware Edge: Upgrade to v1.8 or later Refer to secure configuration guide here https://www.ptc.com/en/support/refdoc/ThingWorx_Kepware_Server/6.15/ThingWorx%20Kepware%20Server%20Secure%20Deployment%20Guide If additional questions remain, please contact PTC Technical Support https://support.ptc.com/apps/case_logger_viewer/cs/auth/ssl/log For more information, see PTC's advisory https://www.ptc.com/en/support/article/CS405439 .
First published (updated )
Severity
7.5
AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

ProficySCADA for iOS 5.0.25920 contains a denial of service vulnerability that allows attackers to crash the application by manipulating the password input field. Attackers can overwrite the password field with 257 bytes of repeated characters to trigger an application crash and prevent successful authentication.

First published (updated )
Severity
5.3
Path Traversal
CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:L/VI:L/VA:L/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability in GE Vernova Smallworld on Windows, Linux allows File Manipulation.This issue affects Smallworld: 5.3.5. and previous versions.

Remedy

GE Vernova recommends that users upgrade to the appropriate non-affected version listed above in accordance with their use case and architecture, as this is the most complete method to address the Vulnerability. Also, users are strongly advised to follow the SDG instructions. The complete SDG can be found in the Smallworld Documentation. To obtain the latest version of SWMFS, please contact your local support representative at Customer Center.
First published (updated )
Severity
9.3
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

Improper Authentication vulnerability in GE Vernova Smallworld on Windows, Linux allows Authentication Abuse.This issue affects Smallworld: 5.3.3 and prior versions for Linux, and 5.3.4. and prior versions for Windows.

Remedy

GE Vernova recommends that users upgrade to the appropriate non-affected version listed above in accordance with their use case and architecture as this is the most complete method to address the Vulnerability. Also, users are strongly advised to follow the SDG instructions. The complete SDG can be found in the Smallworld Documentation. To obtain the latest version of SWMFS, please contact your local support representative at Customer Center.
First published (updated )
Severity
10
AV:N/AC:L/Au:N/C:P/I:N/A:N

GE Multilink ML800, ML1200, ML1600, and ML2400 switches with firmware 4.2.1 and earlier and Multilink ML810, ML3000, and ML3100 switches with firmware 5.2.0 and earlier use the same RSA private key across different customers' installations, which makes it easier for remote attackers to obtain the cleartext content of network traffic by reading this key from a firmware image and then sniffing the network.

Remedy

GE recommends users update switch firmware to the latest published version to resolve these vulnerabilities. The new firmware will enable new keys to be calculated and exchanged, resolve the slow data transfer and potential denial of service, and prevent the identified cross-site scripting vulnerabilities. The latest firmware is Version 5.3.2 for the ML800, ML1200, ML1600 and ML2400 and Version 5.3.2-3K for the ML810, ML3000, and ML3100. This firmware is available through the “Resources/Software” link in the product web sites at http://www.gedigitalenergy.com . This firmware is also available through the EnerVista Launchpad device management tool. GE recommends updating the switch over a serial connection to prevent an attacker from capturing the new key. Please refer to the GE advisory for specific information on how to install the firmware and change RSA key. The GE advisory is available at: https://www.gedigitalenergy.com/products/support/multilink/MLSB0415.pdf
First published (updated )
Severity
7.8
AV:N/AC:L/Au:N/C:N/I:N/A:C

GE Multilink ML800, ML1200, ML1600, and ML2400 switches with firmware 4.2.1 and earlier and Multilink ML810, ML3000, and ML3100 switches with firmware 5.2.0 and earlier allow remote attackers to cause a denial of service (resource consumption or reboot) via crafted packets.

Remedy

GE recommends users update switch firmware to the latest published version to resolve these vulnerabilities. The new firmware will enable new keys to be calculated and exchanged, resolve the slow data transfer and potential denial of service, and prevent the identified cross-site scripting vulnerabilities. The latest firmware is Version 5.3.2 for the ML800, ML1200, ML1600 and ML2400 and Version 5.3.2-3K for the ML810, ML3000, and ML3100. This firmware is available through the “Resources/Software” link in the product web sites at http://www.gedigitalenergy.com . This firmware is also available through the EnerVista Launchpad device management tool. GE recommends updating the switch over a serial connection to prevent an attacker from capturing the new key. Please refer to the GE advisory for specific information on how to install the firmware and change RSA key. The GE advisory is available at: https://www.gedigitalenergy.com/products/support/multilink/MLSB0415.pdf
First published (updated )
Severity
6.8
XSS
CVSS:3.0/AV:N/AC:L/PR:L/UI:R/S:C/C:L/I:L/A:N

Cross-site scripting (XSS) vulnerability in GE Multilink ML810/3000/3100 series switch 5.2.0 and earlier, and GE Multilink ML800/1200/1600/2400 4.2.1 and earlier.

Remedy

GE recommends users update switch firmware to the latest published version to resolve these vulnerabilities. The new firmware will enable new keys to be calculated and exchanged, resolve the slow data transfer and potential denial of service, and prevent the identified cross-site scripting vulnerabilities. The latest firmware is Version 5.3.2 for the ML800, ML1200, ML1600 and ML2400 and Version 5.3.2-3K for the ML810, ML3000, and ML3100. This firmware is available through the “Resources/Software” link in the product web sites at http://www.gedigitalenergy.com . This firmware is also available through the EnerVista Launchpad device management tool. GE recommends updating the switch over a serial connection to prevent an attacker from capturing the new key. Please refer to the GE advisory for specific information on how to install the firmware and change RSA key. The GE advisory is available at: https://www.gedigitalenergy.com/products/support/multilink/MLSB0415.pdf
First published (updated )
Severity
6.4
AV:N/AC:L/Au:N/C:P/I:N/A:N

The 17046 Ethernet card before 94450214LFMT100SEM-L.R3-CL for the GE Digital Energy Hydran M2 does not properly generate random values for TCP Initial Sequence Numbers (ISNs), which makes it easier for remote attackers to spoof packets by predicting these values.

Remedy

GE Digital Energy has released a new version of the Ethernet option, which resolves the identified vulnerability in newly released Hydran M2 devices. The update changes the sequence algorithm, which makes it improbable that a TCP sequence attack could succeed. The version of Ethernet card that implements this improvement is 94450214LFMT100SEM-L.R3-CL.
First published (updated )
Severity
6.9
Buffer Overflow
AV:L/AC:M/Au:N/C:C/I:C/A:C

The (1) CimView and (2) CimEdit components in GE Proficy HMI/SCADA-CIMPLICITY 8.2 and earlier allow remote attackers to gain privileges via a crafted CIMPLICITY screen (aka .CIM) file.

Remedy

GE recommends that asset owners apply product updates to Proficy HMI/SCADA–CIMPLICITY Versions 8.1 and 8.2. The following product updates address the memory access violation vulnerability: Proficy HMI/SCADA – CIMPLICITY 8.1 SIM 29 (DN4219) available at:  http://support.ge-ip.com/support/index?page=dwchannel&id=DN4219 Proficy HMI/SCADA–CIMPLICITY 8.2 SIM 26 (DN4197) available at:  http://support.ge-ip.com/support/index?page=dwchannel&id=DN4197
First published (updated )
Severity
7.5
EPSS
0.02%
CVSS:4.0/AV:L/AC:H/AT:P/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:N/AU:X/R:X/V:X/RE:X/U:X

Improper Privilege Management vulnerability in GE Vernova S1 Agile Configuration Software on Windows allows Privilege Escalation.This issue affects S1 Agile Configuration Software: 3.1 and previous version.

Remedy

To resolve this issue and enhance security, during the S1 Agile application installation, we ensure only privileged users can access various folders used by the S1 Agile application. This ensures that S1 Agile files can not be edited or replaced by users without sufficient privileges on that computer. We would like to assert that this attack, if successful, can give “Administrator” privileges to the attacker on the computer, but the configured IEDs will not see any impact in their configuration or functionality. The RBAC (‘Role-Based Access Control’) on the IED remains unimpacted. We strongly recommend customers to upgrade to the latest software version available. Software version 3.1.1 is released for customer usage in January 2025.
First published (updated )
Severity
5.9
Path Traversal
CVSS:3.1/AV:A/AC:H/PR:L/UI:N/S:U/C:L/I:H/A:L

Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability in GE Vernova WorkstationST on Windows (EGD Configuration Server modules) allows Path Traversal.This issue affects WorkstationST: WorkstationST V07.10.10C and earlier.

First published (updated )
Severity
7.8
CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H

Exploitation of this vulnerability may result in local privilege escalation and code execution. GE maintains exploitation of this vulnerability is only possible if the attacker has login access to a machine actively running CIMPLICITY, the CIMPLICITY server is not already running a project, and the server is licensed for multiple projects.

Remedy

GE Digital recommends users upgrade all instances of the affected software to GE Digital’s Proficy CIMPLICITY, released January 2022 (Upgrade) and follow the instructions in the Secure Deployment Guide to restrict which CIMPLICITY projects are allowed to run. The upgrade contains what GE believes are mitigation measures to help ensure the vulnerability cannot be exploited. Users are encouraged to contact a GE Digital representative for the latest versions of the update. For users who choose to not implement the upgrade, GE Digital recommends applying the instructions in CIMPLICITY’s Secure Deployment Guide to ensure access to the CIMPLICITY machines and directories are properly controlled via access control limits.
First published (updated )

Contact

SecAlerts Pty Ltd.
132 Wickham Terrace
Fortitude Valley,
QLD 4006, Australia
info@secalerts.co
By using SecAlerts services, you agree to our services end-user license agreement. This website is safeguarded by reCAPTCHA and governed by the Google Privacy Policy and Terms of Service. All names, logos, and brands of products are owned by their respective owners, and any usage of these names, logos, and brands for identification purposes only does not imply endorsement. If you possess any content that requires removal, please get in touch with us.
© 2026 SecAlerts Pty Ltd.
ABN: 70 645 966 203, ACN: 645 966 203