The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.
Buffer overflow in the BaseRunner ActiveX control in the Ademco ATNBaseLoader100 Module (ATNBaseLoader100.dll) 5.4.0.6, when Internet Explorer 6 is used, allows remote attackers to execute arbitrary code via a long argument to the (1) Send485CMD method, and possibly the (2) SetLoginID, (3) AddSite, (4) SetScreen, and (5) SetVideoServer methods.
Directory traversal vulnerability in the FTP server on Honeywell Excel Web XL1000C50 52 I/O, XL1000C100 104 I/O, XL1000C500 300 I/O, XL1000C1000 600 I/O, XL1000C50U 52 I/O UUKL, XL1000C100U 104 I/O UUKL, XL1000C500U 300 I/O UUKL, and XL1000C1000U 600 I/O UUKL controllers before 2.04.01 allows remote attackers to read files under the web root, and consequently obtain administrative login access, via a crafted pathname.
Multiple stack-based buffer overflow vulnerabilities were found in Honeywell Experion PKS all versions prior to R400.6, all versions prior to R410.6, and all versions prior to R430.2 modules that could lead to possible remote code execution, dynamic memory corruption, or denial of service. Honeywell strongly encourages and recommends all customers running unsupported versions of EKPS prior to R400 to upgrade to a supported version.
Honeywell Experion PKS C200, C200E, C300, and ACE controllers are vulnerable to unrestricted file uploads, which may allow an attacker to remotely execute arbitrary code and cause a denial-of-service condition.
Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') vulnerability in Honeywell MB-Secure allows Privilege Abuse. This issue affects MB-Secure: from V11.04 before V12.53 and MB-Secure PRO from V01.06 before V03.09.Honeywell also recommends updating to the most recent version of this product.
Improper Input Validation vulnerability in Honeywell PM43 on 32 bit, ARM (Printer web page modules) allows Command Injection.This issue affects PM43 versions prior to P10.19.050004. Update to the latest available firmware version of the respective printers to version MR19.5 (e.g. P10.19.050006).
LenelS2 NetBox access control and event monitoring system was discovered to contain Hardcoded Credentials in versions prior to and including 5.6.1 which allows an attacker to bypass authentication requirements.
LenelS2 NetBox access control and event monitoring system was discovered to contain an unauthenticated RCE in versions prior to and including 5.6.1, which allows an attacker to execute malicious commands with elevated permissions.
The following versions of MAXPRO VMS and NVR, MAXPRO VMS:HNMSWVMS prior to Version VMS560 Build 595 T2-Patch, HNMSWVMSLT prior to Version VMS560 Build 595 T2-Patch, MAXPRO NVR: MAXPRO NVR XE prior to Version NVR 5.6 Build 595 T2-Patch, MAXPRO NVR SE prior to Version NVR 5.6 Build 595 T2-Patch, MAXPRO NVR PE prior to Version NVR 5.6 Build 595 T2-Patch, and MPNVRSWXX prior to Version NVR 5.6 Build 595 T2-Patch are vulnerable to an unsafe deserialization of untrusted data. An attacker may be able to remotely modify deserialized data without authentication using a specially crafted web request, resulting in remote code execution.
An arbitrary memory write vulnerability exists in the dualonsrv.exe module in Honeywell Experion PKS R40x before R400.6, R41x before R410.6, and R43x before R430.2, that could lead to possible remote code execution or denial of service. Honeywell strongly encourages and recommends all customers running unsupported versions of EKPS prior to R400 to upgrade to a supported version.
Multiple heap-based buffer overflow vulnerabilities exist in Honeywell Experion PKS all versions prior to R400.6, all versions prior to R410.6, and all versions prior to R430.2 modules, which could lead to possible remote code execution or denial of service. Honeywell strongly encourages and recommends all customers running unsupported versions of EKPS prior to R400 to upgrade to a supported version.
An issue was discovered in Honeywell XL Web II controller XL1000C500 XLWebExe-2-01-00 and prior, and XLWeb 500 XLWebExe-1-02-08 and prior. Any user is able to disclose a password by accessing a specific URL, because of Plaintext Storage of a Password.
An issue was discovered in Honeywell XL Web II controller XL1000C500 XLWebExe-2-01-00 and prior, and XLWeb 500 XLWebExe-1-02-08 and prior. Password is stored in clear text.
Honeywell equIP series and Performance series IP cameras and recorders, A vulnerability exists in the affected products where IP cameras and recorders have a potential replay attack vulnerability as a weak authentication method is retained for compatibility with legacy products.
The affected product is vulnerable to a heap-based buffer overflow, which may allow an attacker to manipulate memory with controlled values and remotely execute code on the OPC UA Tunneller (versions prior to 6.3.0.8233).
Controller may be loaded with malicious firmware which could enable remote code execution
Server or Console Station DoS due to heap overflow occurring during the handling of a specially crafted message for a specific configuration operation.
Controller DoS due to stack overflow when decoding a message from the server
Experion server DoS due to heap overflow occurring during the handling of a specially crafted message for a specific configuration operation.
Controller DoS may occur due to buffer overflow when an error is generated in response to a specially crafted message.
Honeywell Notifier Web Server (NWS) Version 3.50 is vulnerable to a path traversal attack, which allows an attacker to bypass access to restricted directories. Honeywell has released a firmware update to address the problem.
The following versions of MAXPRO VMS and NVR, MAXPRO VMS:HNMSWVMS prior to Version VMS560 Build 595 T2-Patch, HNMSWVMSLT prior to Version VMS560 Build 595 T2-Patch, MAXPRO NVR: MAXPRO NVR XE prior to Version NVR 5.6 Build 595 T2-Patch, MAXPRO NVR SE prior to Version NVR 5.6 Build 595 T2-Patch, MAXPRO NVR PE prior to Version NVR 5.6 Build 595 T2-Patch, and MPNVRSWXX prior to Version NVR 5.6 Build 595 T2-Patch contain an SQL injection vulnerability that could give an attacker remote unauthenticated access to the web user interface with administrator-level privileges.
A file inclusion vulnerability exists in the confd.exe module in Honeywell Experion PKS R40x before R400.6, R41x before R410.6, and R43x before R430.2, which could lead to accepting an arbitrary file into the function, and potential information disclosure or remote code execution. Honeywell strongly encourages and recommends all customers running unsupported versions of EKPS prior to R400 to upgrade to a supported version.
Honeywell HDZP252DI 1.00.HW02.4 and HBW2PER1 1.000.HW01.3 devices allow a video replay attack after ARP cache poisoning has been achieved.
Honeywell ControlEdge through R151.1 uses Hard-coded Credentials. According to FSCT-2022-0056, there is a Honeywell ControlEdge hardcoded credentials issue. The affected components are characterized as: SSH. The potential impact is: Remote code execution, manipulate configuration, denial of service. The Honeywell ControlEdge PLC and RTU product line exposes an SSH service on port 22/TCP. Login as root to this service is permitted and credentials for the root user are hardcoded without automatically changing them upon first commissioning. The credentials for the SSH service are hardcoded in the firmware. The credentials grant an attacker access to a root shell on the PLC/RTU, allowing for remote code execution, configuration manipulation and denial of service.
Honeywell Experion PKS C200, C200E, C300, and ACE controllers are vulnerable to improper neutralization of special elements in output, which may allow an attacker to remotely execute arbitrary code and cause a denial-of-service condition.
Honeywell Experion PKS Safety Manager (SM and FSC) through 2022-05-06 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0053, there is a Honeywell Experion PKS Safety Manager insufficient logic security controls issue. The affected components are characterized as: Honeywell FSC runtime (FSC-CPU, QPP), Honeywell Safety Builder. The potential impact is: Remote Code Execution, Denial of Service. The Honeywell Experion PKS Safety Manager family of safety controllers utilize the unauthenticated Safety Builder protocol (FSCT-2022-0051) for engineering purposes, including downloading projects and control logic to the controller. Control logic is downloaded to the controller on a block-by-block basis. The logic that is downloaded consists of FLD code compiled to native machine code for the CPU module (which applies to both the Safety Manager and FSC families). Since this logic does not seem to be cryptographically authenticated, it allows an attacker capable of triggering a logic download to execute arbitrary machine code on the controller's CPU module in the context of the runtime. While the researchers could not verify this in detail, the researchers believe that the microprocessor underpinning the FSC and Safety Manager CPU modules is incapable of offering memory protection or privilege separation capabilities which would give an attacker full control of the CPU module. There is no authentication on control logic downloaded to the controller. Memory protection and privilege separation capabilities for the runtime are possibly lacking. The researchers confirmed the issues in question on Safety Manager R145.1 and R152.2 but suspect the issue affects all FSC and SM controllers and associated Safety Builder versions regardless of software or firmware revision. An attacker who can communicate with a Safety Manager controller via the Safety Builder protocol can execute arbitrary code without restrictions on the CPU module, allowing for covert manipulation of control operations and implanting capabilities similar to the TRITON malware (MITRE ATT&CK software ID S1009). A mitigating factor with regards to some, but not all, of the above functionality is that these require the Safety Manager physical keyswitch to be in the right position.
UNSUPPORTED WHEN ASSIGNED [An attacker can capture an authenticating hash and utilize it to create new sessions. The hash is also a poorly salted MD5 hash, which could result in a successful brute force password attack. Impacted product is BCM-WEB version 3.3.X. Recommended fix: Upgrade to a supported product such as Alerton ACM.] Out of an abundance of caution, this CVE ID is being assigned to better serve our customers and ensure all who are still running this product understand that the product is end of life and should be removed or upgraded.
Honeywell OneWireless
Wireless Device Manager (WDM) for the following versions R310.x, R320.x, R321.x, R322.1, R322.2, R323.x, R330.1 contains a command injection vulnerability. An attacker who is authenticated could use the firmware update process to potentially exploit the vulnerability, leading to a command injection. Honeywell recommends updating to
R322.3, R330.2 or the most recent version of this product2.